CHAPTER 2: INSTALLATION
CAUTION:

Ground and sensitive ground CT inputs

NOTE:
OTE
345 TRANSFORMER PROTECTION SYSTEM – QUICKSTART GUIDE
Before working on CTs, they MUST be short circuited.
Two ground inputs - one per winding - are referred to throughout this manual as the
Ground Current or Sensitive Ground Current inputs. Before making ground connections,
consider that the relay automatically calculates the neutral (residual) current from the sum
of the three phase current phasors. The following figures show three possible ground
connections (or three possible sensitive ground connections).
The ground inputs (Terminals D8 and E8 for W1, and D12 and E12 for W2) are used in
conjunction with a Zero Sequence CT as source, or in the neutral of wye-connected source
CTs. When using the residual connection set the GROUND CT PRIMARY setpoint to a value
equal to the PHASE CT PRIMARY setpoint.
In cases where the relay is equipped with sensitive ground CT (terminals D8 and E8 for W1,
and D12 and E12 for W2) the sensitive ground current input is intended for use with a CT in
a source neutral of a high-impedance grounded system, or on ungrounded systems. On
ungrounded systems it is connected residually with the phase current inputs. In this case,
the SENSTV GND CT PRIMARY setpoint should be programmed to a value equal to the
PHASE CT PRIMARY setpoint. The sensitive ground current input can be connected to a
Zero Sequence CT for increased sensitivity and accuracy when physically possible in the
system.
The Sensitive Ground input must only be used on systems where the maximum ground
current does not exceed 100 times the rated current for 1 second.
The ground CT wiring in the figure below, shows 3 possible ways for wiring the Winding 1
ground CT (terminals D8, E8). The Winding 2 ground CT wiring (terminals D12, E12) is similar.
Figure 2-17: Ground/Sensitive Ground wiring
Transformer Winding 1
Transformer Winding 1
D8
E8
N
I
G
GROUND
GROUND CURRENT INPUT
GROUND CURRENT INPUT
For Winding 2 ground CT, use relay terminals D12-E12 in the same wiring configuration as
shown above for Winding 1.
E5
A
D5
E8
D8
I
N
G
GROUND
GROUND CURRENT INPUT
GROUND CURRENT INPUT
WITH ZERO SEQUENCE CT
WITH ZERO SEQUENCE CT
ELECTRICAL INSTALLATION
A
B
C
E7
E6
SR345
B
C
PHASE CURRENT
PHASE CURRENT
INPUTS
D6
D7
E8
D8
I
N
G
GROUND
GROUND CURRENT INPUT
GROUND CURRENT INPUT
WITH RESIDUAL CONNECTION
WITH RESIDUAL CONNECTION
897730.CDR
29