102

Symbols

I
max
Normal use (10 % overload capability)
I
2N
P
N
Heavy-duty use (50 % overload capability)
I
2hd
P
hd
Note: The ratings apply in ambient temperature of 40 °C (104 °F). In lower temperatures the ratings are
higher.

Input cable fuses

The recommended fuses are for branch circuit protection per NEC. Check that the
operating time of the fuse is below 0.5 seconds and the fuses are of the "non-
time delay" type . The operating time depends on the fuse type (T/L or aR), supply
network impedance and the cross-sectional area, material and length of the supply
cable. In case the 0.5 seconds operating time is exceeded with T/L fuses, ultrarapid
(aR) fuses will in most cases reduce the operating time to an acceptable level. The
fuses must be of the "non-time delay" type. See also Planning the electrical
installation /
Note 1: In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 2: Larger fuses must not be used.
Note 3: Fuses from other manufacturers can be used if they meet the ratings.
ACS800-U2 type
Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
-0080-2
-0100-2
-0120-2
-0140-2
-0170-2
-0210-2
-0230-2
-0260-2
-0300-2
Technical data
maximum output current. Available for 10 s ar start, otherwise as long as allowed by drive
temperature.
continuous rms current. 10 % overload is typically allowed for one minute every 5 minutes.
typical motor power. The power ratings apply to most 4-pole NEMA rated motors (230 V or
460 V).
continuous rms current. 50 % overload is typically allowed for one minute every 5 minutes.
typical motor power. The power ratings apply to most 4-pole NEMA rated motors (230 V or
460 V).
Thermal overload and short-circuit
Input
current
A
201
239
285
391
428
506
599
677
707
protection.
A
V
Manufacturer
250
600
Bussmann
300
600
Bussmann
400
600
Bussmann
500
600
Bussmann
600
600
Bussmann
600
600
Bussmann
800
600
Bussmann
800
600
Bussmann
800
600
Bussmann
Fuse
Type
JJS-250
JJS-300
JJS-400
JJS-500
JJS-600
JJS-600
1)
KTU-800
1)
KTU-800
2)
KTU-800
UL class
T
T
T
T
T
T
L
L
L