List Of Commands - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

2.5.2

List of commands

The following shows the list of commands available in each data format.
List of commands for formats 1, 2 (GOT-A900 Series microcomputer connection)
Command
Command name
ASCII
Symbol
code
Batch read
RD
52
44
H
H
in word units
Batch write
WD
57
44
H
H
in word units
Random read
RR
52
52
H
H
in word units
Random write
RW
52
57
H
H
in word units
TR
54
52
Read clock data
H
H
TS
54
53
Set clock data
H
H
*1
Mixed specification of bit devices and word devices is also possible.
List of commands for formats 3 to 6 (A compatible 1C frame)
Command
Command name
ASCII
Symbol
code
BR
42
52
Batch read
H
H
JR
4A
52
in bit units
H
H
57
52
WR
Batch read
H
H
51
52
QR
in word units
H
H
BW
42
57
Batch write
H
H
JW
4A
57
in bit units
H
H
WW
57
57
Batch write
H
H
QW
51
57
in word units
H
H
BT
42
54
Test in bit units
H
H
JT
4A
54
(random write)
H
H
WT
57
54
Test in word units
H
H
QT
51
54
(random write)
H
H
*2
54
52
Read clock data
TR
H
H
*2
54
53
Set clock data
TS
H
H
*2
This is a dedicated command of GOT for the microcomputer connection.
*3
Specifies the address of bit devices in 16-point units. (Example: M0, M16, M32, and others)
Reads bit devices in 16-point units.
Reads word devices in 1-point units.
Writes to bit devices in 16-point units.
Writes to word devices in 1-point units.
Reads multiple different bit devices in 16-point units.
*1
Reads multiple different word devices in 1-point units.
Writes to multiple different word devices in 16-point units.
*1
Writes to multiple different word devices in 1-point units.
Reads the clock data of the GOT.
Sets the clock data of the GOT.
Reads bit devices in 1-point units.
Reads bit devices in 16-point units.
Reads word devices in 1-point units.
Writes to bit devices in 1-point units.
Writes to bit devices in 16-point units.
Writes to word devices in 1-point units.
Writes to multiple different bit devices in 1-point units.
Writes to multiple different bit devices in 16-point units.
Writes to multiple different word devices in 1-point units.
Reads the clock data of the GOT.
Sets the clock data of the GOT.
2. MICROCOMPUTER CONNECTION (SERIAL)
Description
Description
*3
*3
*3
2.5 Message Formats
2
Max. number of points
processed
64 words (1024 points)
64 points
64 words (1024 points)
64 points
64 words (1024 points)
64 points
64 words (1024 points)
64 points
Max. number of points
processed
64 points
64 words (1024 points)
64 points
64 points
64 words (1024 points)
64 points
64 points
64 words (1024 points)
64 points
2 - 21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents