Mitsubishi Electric MELSEC iQ-F FX5U User Manual page 126

Programmable controller
Hide thumbs Also See for MELSEC iQ-F FX5U:
Table of Contents

Advertisement

■Source output type
AC power supply (100 to 240 V)
Breaker
Power ON
PL
MC
MC
Emergency
stop
MC
DC power supply
Power supply for loads connected to
PLC output terminals
As for emergency stop operation, see "DESIGN
PRECAUTIONS" at "Safety Precautions" field.
*1 The output circuit of the PLC does not have a built-in fuse.
Provide a fuse suitable for each load to prevent melting of the wires on the circuit board caused by output device breakdown due to load
short-circuiting.
*2 "" represents vacant terminals.
6 WIRING
124
6.6 Output Wiring
MC
CPU module transistor
output (source)
*1
Fuse
+V0
Y0
Load
+V1
Y4
Fuse
+V3
Y14
Load
*2
Output module transistor
output (source)
*1
Fuse
+V0
Y0
Y7
Load
Fuse
+V1
Y0
Y7
Load

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-f fx5u seriesMelsec iq-f fx5u-u-hw-e09r536

Table of Contents