Mitsubishi Electric MELSEC iQ-F FX5U User Manual page 105

Programmable controller
Hide thumbs Also See for MELSEC iQ-F FX5U:
Table of Contents

Advertisement

Handling of 24 V DC input
■Input terminal
For FX5U CPU module, input module (extension cable type), powered input/output module and high-speed pulse input/output
module
Sink input
When a no-voltage contact or NPN open collector transistor output
is connected between an input (X) terminal and the [0V] terminal
and the circuit is closed, the input (X) turns on.
The input display LED turns on.
Fuse
L
N
100 to 240 V AC
S/S
0V
24V
*1
X0
X1
X7
*1 Input impedance
RUN terminal setting
X0 to X17 of the CPU module can be used as RUN input terminals by
setting parameters.
MELSEC iQ-F FX5 User's Manual (Application)
For input module (extension connector type) and input/output module
• FX5-CEX/D, FX5-C32ET/D
When a no-voltage contact or NPN open collector transistor output is connected between an input (X) terminal and the [COM] terminal and the circuit is
closed, the input (X) turns on.
At this time, the LED corresponding to the DISP switch lights up.(FX5-C16EX/D does not have the DISP switch.)
*1
X0
X1
COM
*1 Input impedance
• FX5-CEX/DS, FX5-C32ET/DSS
In the sink input, the input (X) is turned on by connecting 24 V DC [+] with
the [COM] terminal, and connecting a no-voltage contact or NPN open
collector transistor output between the input terminal and 24 V DC to close
the circuit.
At this time, the LED corresponding to the DISP switch lights up.
(FX5-C16EX/DS does not have the DISP switch.)
• Sink input wiring
*1
X0
X1
COM
*1 Input impedance
Source input
When a no-voltage contact or PNP open collector transistor output
is connected between an input (X) terminal and the [24V] terminal
and the circuit is closed, the input (X) turns on.
The input display LED turns on.
Fuse
24 V DC
Fuse
24 V DC
Fuse
L
N
100 to 240 V AC
S/S
0V
24V
*1
X0
X1
X7
*1 Input impedance
In the source input, the input (X) is turned on by connecting 24 V DC [-] with
the [COM] terminal, and connecting a no-voltage contact or PNP open
collector transistor output between the input terminal and 24 V DC to close
the circuit.
At this time, the LED corresponding to the DISP switch lights up.
(FX5-C16EX/DS does not have the DISP switch.)
• Source input wiring
*1
X0
X1
COM
*1 Input impedance
6
Fuse
24 V DC
6 WIRING
103
6.5 Input Wiring

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-f fx5u seriesMelsec iq-f fx5u-u-hw-e09r536

Table of Contents