9.3
Multiple Battery Cabinets
Multiple DC Backup Source cabinets may be combined to extend the UPS backup runtime. Typically
these cabinets must be connected to a single point connection outside the UPS. Contact the factory if
using more than one DC Source Backup cabinet.
9.4
Power Terminal Blocks and Cable Sizing
Note: Always consult your site specific, local, state, and NEC electrical codes for wiring, cabling, and circuit
protection device requirements.
The Power Lugs for the 50-80kVA UPS are not designed for use with high-flex/locomotive-type
cabling.
Use of these conductors may lead to conductor strand breakage effectively reducing the
current carrying capacity of the conductor.
The terminal blocks for the 15-30 kVA UPS are shown in Figure 9.4.
Use only copper wires for external cables. See Appendix D for alternate voltage and cabling configurations.
TABLE 9.1 RECOMMENDED CABLE SIZE & TIGHTENING TORQUE FOR 15-30KVA UPS FOR
Block Number
AC Input A, B, C
AC Input Neutral (N)
2
AC Output A, B, C
AC Output Neutral (N)
2
Secondary Input A, B, C
Secondary Neutral (N)
2
Battery Terminals +/-
1
One battery string. (Consult factory if using more than one battery string.)
1
Size neutral cable appropriate to actual load type: balanced, unbalanced, non-linear.
2
The terminal blocks for the 15-30 kVA UPS are shown in Figure 9.4.
4400 Series Installation and Operation Manual – 64527-006
NOTICE
120/208V IN, 120/208V OUT
Cable Size (Min-Max) 75 °C Copper Wire in Conduit
Terminal Lug
15 kVA
Capacity (AWG)
(AWG)
#12 – #2
#4
#12 – #2
#2
#12 – #2
#4
#12 – #2
#2
#12 – #2
#4
#12 – #2
#2
#12 – #2
#6
20 kVA
25 kVA
30 kVA
(AWG)
(AWG)
(AWG)
#3
#2
#2
#2
#2
#2
#3
#2
#2
#2
#2
#2
#3
#2
#2
#2
#2
#2
#3
#2
#2
Tightening
Torque
2
35-44 in-lb
(4-5 N•m)
(6.5 x 1.2 mm
Flat blade
screwdriver)
41