When you change one of the following texts, the status ("State") at the web server
changes from "Generated" to "Not updated":
Message receiver 1...4
Fault input 1...2
Text for: No fault
Text for: Fault
You can change the following texts without influencing the "State" of the device list:
Name (web server).
Bus device name.
You must update the device web pages of the web server to apply all text changes
to the menu.
• You can update device web pages on user levels "Administrator" and "Service".
• Click "Update" on the Service and "Generate" on the Administrator level to start
updating (see "Create device web pages").
The following update procedure applies to the Service level:
1.
Select the web server
2.
Click
.
Update
The device web pages are updated.
Note
: This process may take a few minutes.
3.
Wait until the message "
The device list for the web server display status "Generated".
Web server
Commissioning
.
Process finished" appears.