Appendix2. Object Property Table - LG BNU-BAC Installation & Owner's Manual

Hide thumbs Also See for BNU-BAC:
Table of Contents

Advertisement

Appendix 2
Appendix 2
Obejct Property table
O : indicates that the property is optional.
R : indicates that the property is required to be present and readable using BACnet services.
W : indicates that the property is required to be present, readable, and writable using BACnet
services.
• Analog Input Object Type (1)
Property Identifier
Object_Identifier
Object_Name
Object_Type
Present_Value
Description
Device_Type
Status_Flags
Event_State
Reliability
Out_Of_Service
Update_Interval
Units
Min_Pres_Value
Max_Pres_Value
Resolution
COV_Increment
Time_Delay
Notification_Class
High_Limit
Low_Limit
Deadband
Limit_Enable
Event_Enable
Acked_Transitions
Notify_Type
Event_Time_Stamps
Profile_Name
98 BACnet Gateway
Property Datatype
BACnetObjectIdentifier
CharacterString
BACnetObjectType
Real
CharacterString
CharacterString
BACnetStatusFlags
BACnetEventState
BACnetReliability
BOOLEAN
Unsigned
BACnetEngineeringUnits
REAL
REAL
REAL
REAL
Unsigned
Unsigned
Real
Real
Real
BACnetLimitEnable
BACnetEventTransitionBits
BACnetEventTransitionBits
BACnetNotifyType
BACnetARRAY[3] of BACnetTimeStamp
CharacterString
BACnet
BNU-BAC
R
R
R
R
R
R
R1
R
O
R
O
-
R
R
R
R
O
-
R
R
O
-
R
R
O
-
O
-
O
-
O2
-
O3
-
O3
-
O3
-
O3
-
O3
-
O3
-
O3
-
O3
-
O3
-
O3
-
O
-