RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises. Recommendations For Smoke And Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
Table Of Contents Section 1. Features and Installation Highlights..................1-1 Capabilities and Functions ............................... 1-1 Compatible Devices ................................1-2 Important Installation Highlights (Installer Please Read)..................... 1-2 Section 2. Mounting and Wiring the Control ..................... 2-1 Installing the Control Cabinet and PC Board ......................... 2-1 Cabinet and Lock.................................
Page 4
Section 3. Programming Overview ......................3-21 About Programming................................ 3-21 Mechanics of Programming ............................3-21 Data Field Programming Procedures ........................3-21 Interactive Mode Programming (∗56, *57, ∗58, ∗79, ∗80, ∗81, ∗82) ................ 3-22 Loading Factory Defaults/Initializing for Download ....................3-22 Exiting the Programming Mode ..........................3-22 Zone Type Definitions ..............................
False Alarm Reduction. To program for False Alarm Reduction, follow the SIA Guidelines noted in the applicable programming fields. NOTE: Throughout this manual, device model numbers are Honeywell model numbers unless otherwise noted. Capabilities and Functions...
Powerline Carrier devices. Audio Alarm Using AAV Honeywell AVS system can be used to permit voice dialog between Verification module an operator at the central station and a person at the premises via...
S E C T I O N Mounting and Wiring the Control Installing the Control Cabinet and PC Board Cabinet and Lock 1. Mount the control cabinet to a sturdy wall in a clean, dry area, PUSH which is not readily accessible to ON LOCK CHECK UNTIL IT...
Programming Overview AC Power, Battery, and Ground Connections 1361 Transformer Wire Run Chart Connect the 1361 Transformer (1361CN in Canada) to terminals 1 and 2 on the Distance from control Wire Size control board. See Wire Run Chart for Up to 50 feet # 20 wire size to use.
Installation and Setup Guide Sounder (Bell) Connections Basic Connections 1. Make sounder connections to alarm output terminals 3 (+) and 4 (–). 2. If not using bell supervision, connect the supplied 820 ohm resistor across terminals 3 and 4. If using bell supervision, see Supervised Output paragraph below. •...
Programming Overview Keypad Notes Set device addresses. Refer to the instructions included with the devices and set each address according to the Table of Device Addresses. See Keypad Programming Fields (fields *190-*196) in Section 4. Data Field Programming for details on enabling keypad addresses, assigning keypad partitions and selecting keypad sounding options.
Installation and Setup Guide Hardwire Zones and Zone Expansion Hardwire Zones Normally Open Zones/ N.O. EOLR Zones 1. Connect open circuit devices in parallel across the loop; for EOLR zones, connect the EOLR across the loop wires at the last device. 2.
Programming Overview • • • • Fire Verification (zone type 16): The control panel will “verify” a fire alarm by Smoke Detector Notes resetting the smoke detectors after the first alarm trigger, and then waiting up to 90 seconds for a second alarm trigger. If the smoke detector or thermostat does not trigger again, the control will disregard the first trigger, and no alarm signal will occur.
Installation and Setup Guide Installing the RF Receiver and Wireless Transmitter Zones Compatible Receivers Use any ADEMCO 5800 Series Wireless Receivers, such as: RF Receiver No. of Zones 5881L/5882L up to 8 5881M/5882M up to 16 6150RF 5881H/5882H, up to 40 plus 16 buttons 5883, 6160RF Receiver Connections 1.
Programming Overview • Use this module only if you are using one or more wireless bi-directional keypads or Installing a 5800TM Module keyfobs with a wireless Receiver; 5800TM is not necessary if using a Transceiver (e.g., 5883). • The 5800TM must be set to address 28 (cut red-W1 jumper). •...
Installation and Setup Guide Installing a Keyswitch Keyswitch Connections 1. Connect the 4146 keyswitch's normally open momentary switch to a zone’s (2-8) terminals. Remove the 2000 ohm EOL resistor if connected across the selected zone. 2. Using a standard keypad cable as shown: Connect the yellow and white keyswitch wires to trigger connector pin 3 (+12V).
Programming Overview Connecting Relay Modules, Powerline Carrier Devices and Output Triggers 4204/4229 Relay Modules 1. Mount either remotely or in the control panel cabinet. 2. Connect each module to the control’s keypad terminals and set the device addresses as previously described in the Connecting Keypads and Other Addressable Device section.
Installation and Setup Guide On-Board Triggers Connect field wiring to the desired trigger pin on the 8-pin trigger connector centrally located above the terminal strip. • If using 1361X10 transformer and powerline carrier devices, use the SA4120XM-1 cable (part of 4120TR Trigger Cable). See Wiring the AC Transformer section for transformer connections.
Programming Overview Phone Line/Phone Module, Audio Alarm Verification (AAV), and Internet (IP) Connections Phone Line Connect incoming phone line and handset wiring to the main terminal block (via an RJ31X jack) as shown in the Summary of Connections diagram at the back of this manual. Wire colors represent the colors of the cable to the RJ31X jack.
Installation and Setup Guide Audio Alarm Verification Using the AVS System with AVS Module and AVST Remote Stations Connections The AVS system provides audio alarm verification via the phone line. (AVS System) Refer to the instructions included with the AVS system for installation procedures. The following is a summary.
Programming Overview RING RJ31X RING INCOMING TELCO PREMISES PHONES DIRECT CONNECT CORD COMMUNICATION MODULE RJ45 CONNECTOR RSSI MODE 1 MODE 2 BATTERY FUSE GPPS KEYPAD 1 2 3 4 TRIGGER HEADER INCOMING HANDSET ECP TERMINALS PHONE LINE DATA DATA BELL RING RING AVST STATION...
Installation and Setup Guide Internet (IP) Connection Connection to the Internet can be made via hardwired high speed Internet connection and/or via an optional on-board VISTA-GSM4G module (using the wireless GSM digital cellular network). Use ∗29 Menu mode to program various internet reporting and supervision options.
Page 23
Programming Overview 2. Install the Antenna Adapter Plate. a. Punch out the large wiring hole knockout and the adjacent smaller knockout from the cabinet’s upper-right topside. b. Position the antenna adapter plate over the large knockout, aligning the plate’s pin with the smaller knockout and push until the adapter snaps into place.
Installation and Setup Guide IP/GSM Status There are three status LEDs used to indicate IP/GSM message and internal device status: LEDs • STATUS, green • MESSAGE, yellow • FAULT, red Each LED can have four different states - ON, OFF, FAST BLINK and SLOW BLINK. IP/GSM Status LED Meanings COLOR/LED DESCRIPTION...
Programming Overview Signal Strength and Status LED Meanings Color Label Indication RSSI on = signal strength (RSSI) display off = status display Yel (2) mode off = module operating in ECPmode Green web connection status ON = connected to web OFF = no web connection Green GPRS...
Programming Overview S E C T I O N Programming Overview About Programming • You can program the system at any time, even at the installer's premises prior to the actual installation. • Programming can also be performed remotely from the installer’s office/home, using an IBM personal computer, a modem, and Compass downloading software.
Installation and Setup Guide Interactive Mode Programming (∗ ∗ ∗ ∗ 56, *57, ∗ ∗ ∗ ∗ 58, ∗ ∗ ∗ ∗ 79, ∗ ∗ ∗ ∗ 80, ∗ ∗ ∗ ∗ 81, ∗ ∗ ∗ ∗ 82) Press [ ∗ ] + [Interactive Mode No.] (for example, ∗ 56) while in Program Mode. The Alpha Entering Interactive Mode display keypad will display the first of a series of prompts.
Page 29
Programming Overview • Assign to a zone that contains a foil-protected door or window (such as in a store), or to a zone Type 05 Trouble by Day/ covering a sensitive area such as a stock room, drug supply room, etc. Alarm by Night •...
Page 30
Installation and Setup Guide • Can be used on a zone when an output relay action is desired, but with no accompanying Type 23 * No Alarm alarm (e.g., lobby door access). Response • Usually assigned to all sensors or contacts on exterior doors and windows where bells and/or Type 24 Silent Burglary sirens are NOT desired.
S E C T I O N Data Field Programming About Data Field Programming The following pages list this control’s data fields in numerical order. Valid entries for each field are shown in italics. Explanations and special notes are presented below the entries. Use the separate Programming Guide to record the data for this installation.
Installation and Setup Guide Zone Sounds & Timing (∗ ∗ ∗ ∗ 31–∗ ∗ ∗ ∗ 39) Audible Exit Warning 0 = no; 1 = yes Single Alarm Sounding Per Zone (per armed period) Warning sound consists of slow continuous beeps until 0 = no limit on alarm sounding per zone the last 10 seconds, and then it changes to fast beeps.
Page 33
Data Field Programming Primary/Secondary Account Numbers SESCOA/Radionics Select 0 = Radionics (0-9, B-F); 1 = SESCOA (0-9 only) Enter 4 or 10 digits, depending on selection in Select SESCOA or Radionics format. *48 Report Format field. Enter 0–9; # + 11 = B, Select 0 for all other formats.
Installation and Setup Guide Expert Zone Programming Menu Mode Trouble Report Code (0 = no report; 1-F = see description above *59 For quickly programming zone information, but is Sent if a zone has a trouble condition. See UL System recommended only for those already familiar with *56 Reporting Note above *59.
Data Field Programming Output Device Mapping Menu Mode Recent Closing Report V21iPSIA only Use this menu mode to enter output devices/powerline Always enabled. Field does not apply to other controls. carrier devices into the system. See Output Device Similar to the Exit Error condition described in field Programming section for procedures.
Page 36
4 = log Bypass and Restore; 8 = log Open/Close x = log combination of events (add value of entries) UL installations using the AAV feature must use the Honeywell AVS system. This system can record up to 100 system events in a Exit Delay Restart/Reset must be disabled.
Data Field Programming † NOTE: If “15” is entered to bypass an answering machine, Phone Line Monitor Enable (continued) Entry 1: Sets the length of time a phone line fault must and a 4286 Phone Module is included in the system, you should note the following: remain after detected before the second digit option is When calling in from an off-premises phone, the user...
Installation and Setup Guide *160 *167 Pager 1 Phone No. Pager 3 Characters Enter up to 20 digits. Enter up to 16 characters See field ∗161 for explanation of entries. If fewer than If entering fewer than 20 digits, exit by pressing [∗] + next field number.
Data Field Programming Configurable Zone Type Fields Configurable Zone Type Options Auto Restore (entry 2): Faults on zones set for this option are • The system allows you to define up to four custom cleared; restore messages sent upon restoral of faults. zone types based on the options described at right.
Page 40
Installation and Setup Guide Configurable Zone Type Charts ENTRY 1 ENTRY 2 Response when system disarmed and zone is: Auto Restore Vent Zone Intact EOL Open Shorted RF zone normal RF zone N/A RF zn off-normal INTACT OPEN SHORTED 0 = normal 0 = normal 0 = normal 0 = no...
Touch Screen Keypad (AUI) Enable Keypad Programming Fields The system supports up to four touch screen style To enable keypads: keypads (e.g., Symphony Advanced User Interface 1. Set desired address at keypad (refer to keypad’s (AUI), and 6270 Touch Screen keypad. instructions for setting the address).
Page 42
Installation and Setup Guide *191 *197 Keypad 3 Device Address 18 Exit Time Display Interval See field *190 for entries and explanation. 0 = no display; 1-5 = seconds between display updates If enabled, keypads display the exit time remaining after *192 Keypad 4 Device Address 19 arming the system, updated at the interval selected (i.e.
S E C T I O N Menu Mode Programming Zones and Partitions Each protection zone needs to be programmed with various attributes using *56 Zone Programming mode or ✱ 58 Expert Programming Mode. The system can control two independent areas of protection (known as partitions) for use by independent users, if desired, by simply assigning zones to one or the other partition during zone programming.
Page 44
Installation and Setup Guide Zone Number Enter Zn Num. wired 01-08 (and 09-48†); wireless 09-48; RF button zones 49-64 (00 = Quit) 91 = addr. device report enable; 92 = duress report enable; 95, 96, 99 =emerg. zones [ ∗ ] to continue; 00 to quit †...
Page 45
Menu Mode Programming Input Device Type (In) 10 INPUT TYPE 2 = AW (Aux wired zone) RF TRANS 3 = RF (supervised RF transmitter) 4 = UR (unsupervised RF transmitter) 5 = Button type RF transmitter (unsupervised). [ ∗ ] to continue This prompt is skipped for zones 2-8, or 2-16 if zone-doubling was enabled at “Hardwire Type”...
Installation and Setup Guide If Serial or Loop Numbers do not match after activating the transmitter E n t d A 0 2 2 - 4 0 6 3 1 [ ∗ ] to continue R c v d A 0 2 2 - 4 0 6 4 1 If the serial number transmitted does not match the serial number entered, a display similar to the one shown appears.
Page 47
Menu Mode Programming Summary Screen Zn ZT P RC HW: RT 01-64 = zone number; [ ∗ ] to continue; 00 = quit 01 09 1 10 OR [D] to go to prompts for wireless key programming templates A summary screen appears, showing zone 1’s currently programmed values. Enter the zone number being programmed, then press [∗], which displays a summary Zn ZT P RC IN: L screen for that zone.
Installation and Setup Guide If Serial or Loop Numbers do not match after activating the transmitter Entd A022-4063 [ ∗ ] to continue Rcvd A022-4064 If the serial/loop number combination transmitted does not match the serial and loop number entered, a display similar to the one below will appear. If the loop number does not match, it will also be displayed.
Page 49
Menu Mode Programming Start Zone Number ENTER START ZONE • The system will search for the highest available consecutive 4-zone group (the four zones 00 = QUIT in the case of the 5804 and 5804BD), and display the lowest zone number of the group. If you want to start at a different zone, enter the zone desired, and press [✱].
Page 50
Installation and Setup Guide Wireless Key Predefined Default Templates GREEN/YELLOW LOOP 2 LOOP 3 SERIAL #2 LOOP 1 SERIAL #1 SERIAL #1 LOOP 3 YOU MUST LOOP 2 LOOP 2 PROGRAM THIS BUTTON RED/YELLOW LOOP 4 LOOP 1 LOOP 4 (YOU MUST PROGRAM SERIAL #2...
Menu Mode Programming About Output Device Programming (*79/*80 Menu Mode) Output Devices: The system supports up to 16 relays and/or Powerline Carrier devices (X-10 devices) plus 2 built-in trigger outputs in any combination. These 18 “outputs” are assigned to system-wide output numbers (01-18). Use *79 Menu Mode to assign output numbers and map them to device addresses.
Page 52
Installation and Setup Guide Start Output Device Mapping by pressing *79 while in Data Programming Mode. ∗ ∗ ∗ ∗ 79 Output Device Menu Mode Device Output Number ENTER OUTPUT NO. 01-18 = relays/X-10 00 = QUIT [ ∗ ] to continue; 00 to quit This is the logical (or reference) relay number as used in the system.
Menu Mode Programming Relay Position XX REL POSITION 1-4 = relay position [ ∗ ] to continue This is the actual (or physical) relay number with respect to the Relay Module upon which it is located. For 4204 modules, relay numbers are 1-4. For 4229 modules, relay numbers are 1-2.
Page 54
Installation and Setup Guide Activated By 01 Activated By: 0 = delete Zone List 1 = zone list (go to “A” prompt) 2 = zone type (go to “B” prompt) 3 = zone number (go to “C” prompt;) [ ∗ ] to continue Select where the initiating event for this output definition is to occur as follows: If you enter “0,”...
Menu Mode Programming “C” Zone Number (prompt appears if zone number was selected) 01 Enter Zn No. Enter the desired zone number associated with this output number. Press [ ✱ ] to continue. Enter the zone event that will activate this output. 01 Enter Event 0 = restore;...
Installation and Setup Guide Zone List Programming 1. Select an appropriate zone list number. 2. Add the desired zone numbers to be included in that list. ✱ Start Zone List Program Mode by pressing 81 while in Data Programming mode. *81 Menu Mode Zone List Number Zone List No.
Menu Mode Programming About Function Keys (*57 Menu Mode) The system provides the ability to program each of the four keypad function keys to perform one of 12 system operations. The end user can then activate the function by simply pressing and holding the programmed key for 2 seconds.
Installation and Setup Guide About Descriptor Programming (*82 Menu Mode) The system lets you assign zone descriptors for protection zones, keypad panics, and RF receiver supervision faults. Each description can be composed of a combination of words (up to 3) selected from a vocabulary of 196 words stored in memory (see a following page).
Menu Mode Programming Accept First Word ✱ Z N 0 1 B A C K 6 = save word and go to next word in this descriptor; 8 = save word and go to next zone Press [6] to accept the selected word and continue to the next word, or press [8] if this is the only word you are using for the descriptor.
Menu Mode Programming ∗ ∗ ∗ ∗ 29 Menu Mode for IP and GSM Module Programming This mode is for programming the Internet connection (IP) and optional VISTA-GSM4G Module configuration, collectively referred to as the Internal Device. NOTE: The Internal Device is automatically set to address 3 and cannot be changed. The following section describes the programming of the Internal Device using an alpha keypad.
Page 62
Installation and Setup Guide Internal Device (Ip and GSM) Default Values The programming default values for ∗29 Menu Mode are listed in the Table below. OPTION STANDARD DEFAULT VALUE ACTUAL ENTRY Internal Device Multi-Mode disabled Multi-Mode Address ?? (if Multi-Mode enabled) Primary City ID Primary CS ID Primary Sub ID...
Page 63
Menu Mode Programming Internal Device Selection I n t e r n a l D e vi c e Disable – IP – GSM – IP & GSM Select the desired type of internal device usage, IP and/or GSM (press [∗] to scroll choices). Press [#] to continue Multi-Mode (email reporting) M u l t i m o d e...
Page 64
Installation and Setup Guide Keypad Address (for Remote Access) K e y p a d A d d r e s s This prompt appears if remote access is enabled. ( 2 8 ) 1, 2, 5, 6 = emulated AUI address 17-23 = emulated standard keypad address For enhanced remote access features, choose an AUI address.
Page 65
Menu Mode Programming Notify Panel Of N o t i f y P a n e l O f _ Appears only if IP & GSM is selected as Internal Device option. N e i t h e r F a u l t Select from the following choices: •...
Installation and Setup Guide Programming IP/GSM Options via AlarmNet Direct Website To program the IP/GSM options via the AlarmNet Direct website (if you are already signed up for this service), go to: https://services.alarmnet.com/AlarmNetDirect/userlogin.aspx If you are not signed up for this service, click on “Dealer Sign-Up. Log in and follow the on-screen prompts.
Page 67
Menu Mode Programming IP/GSM Diagnostic Commands (continued) Prompt Function GSM Status Displays Status request PriRSSI 3/4G REG Only if GSM or IP/GSM OK = normal -xxxdbm stat enabled. i = IP off line PriRSSI – Primary Site I = IP fault reported RSSI level in dbm g = GSM off line 3/4G –...
• Activation ID (AID) and AID CRC numbers (found on the module’s label or on its carton) If you are not signed up for this service, click on “Dealer Signup” from the login screen to gain access to the Honeywell web-based programming. Dealer Sign-Up Direct Link: https://services.alarmnet.com/AlarmNetDirectP_Sign-Up.
Menu Mode Programming Programming Installer and User Schedules The system provides up to 32 schedules, which can be used to automatically control 11 types of system events at pre-defined times. Some events are reserved for the installer only. There are 16 schedules for use by the end-user, 16 for use by the installer. NOTES: •...
Page 70
Installation and Setup Guide Stop Time (For events 01-relay on/off; 02-user access; 03-latch key report) S T O P S M T W T F S 01-12 = hour; 00-59 = minute; 0 = AM; 1 = PM; Days = place “1” under days 0 0 1 0 0 0 0 H H M M A M Press [ ∗...
S E C T I O N System Communication and Operation Panel Communication with Central Station This system accommodates several formats for reporting alarms and other system conditions to the Central Station. The process of a successful transmission consists of both the method of communication between the control panel and the Central Station receiver;...
Page 72
Installation and Setup Guide The following table lists codes for reports sent in different formats: Code for Code for Type of 3+1/4+1 3+1/4+1 Code for Report Standard Expanded Alarm SSS(S) A SSS(S) A SSSS AZ AAA(A) Z Trouble SSS(S) T SSS(S) T SSSS Tt TTT(T) t...
System Communication ® Ademco Contact ID ® The Ademco Contact ID Reporting Format comprises the following: 4-digit or 10-digit subscriber number (depending on format selected). 1-digit event qualifier (“new” or “restore”). 3-digit event code. 2-digit Partition No. 3-digit zone number, user number, or system status number (see the following page). ®...
Installation and Setup Guide System Security Codes The systems provides one Installer code, one System Master code, plus a set of other user codes intended for other users of the system. These codes can each be assigned one of 5 authority levels, which determine the functions each code can perform as listed in the table below.
System Operation Keypad Functions The following is a brief list of system commands. For detailed information concerning system functions, refer to the User's Manual. For Touch Screen style keypad users, refer to the separate Touch Screen keypad (AUI) User’s Guide. Voice Keypads The 6150V/6160V Voice Keypads provide the following features: •...
Installation and Setup Guide SUMMARY OF ARMING MODES Arming Mode Features for Each Arming Mode Exit Delay Entry Delay Perimeter Armed Interior Armed AWAY STAY NIGHT-STAY only those zones listed in Night- Stay zone list INSTANT MAXIMUM Panic Keys There are three Panic keys (A, B, and C) that, if programmed, can be used to manually initiate alarms and send a report to the central station.
System Operation Various System Trouble Displays Alpha Display Fixed Disp. Meaning ALARM CANCELED will appear if an exit or interior zone contained a fault during closing at the time the Exit Delay ended (e.g., exit door left open), but the system was disarmed during the Entry Delay time.
S E C T I O N Testing the System About Test Procedures After the installation is complete, you should perform the following tests: System Test: Checks that all zones have been installed properly and the system responds to faults. Dialer Test: Checks that the phone connection to the central station is working properly.
Installation and Setup Guide NOTES: • All BR type units must physically be activated to clear the display. • When one button of a transmitter (RF, UR, or BR) is activated, all zones assigned to other buttons on that transmitter are cleared from the display. This also applies to 5816 and 5817 transmitters, which have multiple loops (zones).
S E C T I O N Specifications & Accessories Security Control 1. Physical: 12-1/2” W x 14-1/2” H x 3” D (318mm x 368mm x 76mm) 2. Electrical: VOLTAGE INPUT: 16.5VAC from plug-in 40VA transformer, ADEMCO 1361 (in U.S.A.) RECHARGEABLE BACKUP BATTERY: 12VDC, 4AH (sealed lead acid type).
Page 82
Installation and Setup Guide 2-Wire Smoke Detector: Detector Type Model No. Photoelectric w/heat sensor 2WT-B (System Sensor) Photoelectric 2W-B (System Sensor) Photoelectric 2151 w/B110LP base (System Sensor) Photoelectric FW-2S (Napco) Transformers: 1361: 16.5VAC, 40VA Plug-In Transformer (No. 1361CN in Canada) 1361X10: 16.5VAC, 40VA Powerline Carrier device Interface AC Transformer Sounders: AB12M 10”...
5800 Series Transmitter Input Loop Identification All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes. Each of the input loops requires its own programming zone (e.g., a 5804's four inputs require four programming zones). LOOP 3 LOOP 4 YOU MUST...
S E C T I O N Regulatory Agency Statements FEDERAL COMMUNICATIONS COMMISSION (FCC) PART 15 STATEMENTS The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the equipment. CLASS B DIGITAL DEVICE STATEMENT This equipment has been tested to FCC requirements and has been found acceptable for use.
Page 86
Installation and Setup Guide Industrie Canada AVIS: l’étiquette d’Industrie Canada identifie le matériel homologué. Cette étiquette certifie que le matériel est conforme aux normes de protection, d’exploitation et de sécurité des réseaux de télécommunications, comme le prescrivent les documents concernant les exigences techniques relatives au matériel terminal. Le Ministère n’assure toutefois pas que le matériel fonctionnera à...
Page 87
UL NOTICES Entry Delay No. 1 and No. 2 (fields ∗ 35, ∗ 36) cannot be greater than 30 seconds for UL Residential Burglar Alarm installations, and entry delay plus dial delay should not exceed 1 minute. For UL Commercial Burglar Alarm installations, total entry delay may not exceed 45 seconds.
S E C T I O N Limitations and Warranty WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons.
• Note the proper model number of this product, and the version level (if known) along with any documentation that came with the product. • Note your Honeywell customer number and/or company name. Having this information handy will make it easier for us to serve you quickly and effectively.
Page 94
Installation and Setup Guide Tamper switch......2-10, 9-2 UL ......2-2, 2-4, 2-11, 8-1 Zone Doubling........2-6 Telco Line ........2-13, 3 Zone Lists ....3-19, 5-12, 5-13 Telephone Line Monitoring ....1-1 Verify Operation ....... 2-7 Zone Not Used ....... 3-20 Temporal pulse sounding ....
Need help?
Do you have a question about the ADEMCO VISTA SERIES VISTA-21iP and is the answer not in the manual?
Questions and answers