Flavel MISERMATIC FORM series Installation, Maintenance & User Instructions
Flavel MISERMATIC FORM series Installation, Maintenance & User Instructions

Flavel MISERMATIC FORM series Installation, Maintenance & User Instructions

Battery ignition radiant convector gas fire

Advertisement

MISERMATIC
BATTERY IGNITION RADIANT CONVECTOR GAS FIRE
Installation, Maintenance & User Instructions
Hand these instructions to the user
Model No's FORM**EN are for use on Natural Gas (G20) at a supply
pressure of 20 mbar in G.B. / I.E.
** denotes colour variance

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MISERMATIC FORM series and is the answer not in the manual?

Questions and answers

V. Stanton
March 19, 2025

Is the battery holder on a misermatic underneath or at the back

1 comments:
Mr. Anderson
March 19, 2025

The battery holder is located at the bottom right-hand side (R/H/S) of the fire.

This answer is automatically generated

Summary of Contents for Flavel MISERMATIC FORM series

  • Page 1 MISERMATIC BATTERY IGNITION RADIANT CONVECTOR GAS FIRE Installation, Maintenance & User Instructions Hand these instructions to the user Model No’s FORM**EN are for use on Natural Gas (G20) at a supply pressure of 20 mbar in G.B. / I.E. ** denotes colour variance...
  • Page 2: Table Of Contents

    CONTENTS Page Section 1 Appliance Data Conditions of Installation. Flue & Chimney Suitability Fireplace/Surround Suitability Shelf Position Side Clearance Closure Plate Flue & Chimney inspection Chimney Catchment space 1.8.1 Brick Built Chimney 1.8.2 Fitting to Pre-Fab. Twin Wall Metal Flueboxes 1.8.3 Fitting to Pre-Cast Flue Installations Hearth Fitting...
  • Page 3: Appliance Data

    APPLIANCE DATA Main injector (1 off) Stereomatic Elbow size 76 Pilot Type. Copreci Single Flame 21100 / 161 Max. Gross Heat Input : 6.9 kW Min. Gross Heat Input : 2.5 kW Cold Pressure : 20.0 +/- 1.0 mbar (8.0 +/- 0.4 in w.g.) Ignition : Battery Ignition, 1.5V Electrode Spark Gap :...
  • Page 4: Conditions Of Installation

    CONDITIONS OF INSTALLATION In Great Britain :- It is law that all gas appliances are installed only by a registered installer in accordance with these installation instructions and the Gas Safety (Installation and use) Regulations 1998. Failure to install appliances correctly could lead to prosecution.
  • Page 5: Fireplace/Surround Suitability

    FIREPLACE / SURROUND SUITABILITY The fire is suitable for hearth mounting or wall mounting. It must not be fitted directly onto a carpet or other combustible material. It must not be fitted to combustible walls. This fire is suitable for the following hearth / surround types: Non-combustible hearths / surrounds.
  • Page 6: Chimney Catchment Space

    Brick / stone built chimneys and any chimney or flue which has been used for an appliance burning fuel other than gas must be thoroughly swept. The base of the chimney/flue must also be thoroughly cleared of debris etc. Any under floor air supply to the fireplace must be completely sealed off. Ensure that the inside of the chimney/flue is in good condition along its length and check that there is no leakage of smoke through the structure of the chimney during and after the smoke pellet test.
  • Page 7: Metal Flueboxes

    The front opening of the fireplace must be between 305mm and 440mm wide, and between 580mm and 650mm high. If the opening is larger than this, then a surround must be constructed in a suitable non-com bustible material to create an opening to these limits. Allow a minimum flat surface of 10mm around the opening to ensure that the closure plate can be sealed to the fireplace.
  • Page 8: Hearth Fitting

    This appliance has been tested for use in a pre-cast flue block complying with BS EN 1858. In accordance with BS EN 1858, pre-cast flues built with directly plastered faces (front or rear) are not correctly installed as to ensure proper operation with any type of gas fire.
  • Page 9: Packing Check List

    PACKING CHECK LIST 1 off Firebox / Burner Assembly 1 off Flue Spigot 1 off Closure Plate 1 off Literature / Loose Items Pack 1 off Pack of Screws & Fixings for Wall Mounting 4 off Ceramic Radiants – Packed inside firebox 1 off AA Battery 1 off Arthritic control knob and 2 off self adhesive pads INSTALLATION OF FIRE...
  • Page 10 Fig. 3 To Remove the Lower Outer Case Fixing Screws Fig. 4 Remove the Upper Outer Case Fixing Screws Remove the flue spigot restrictor if the fire if the fire is the to be fitted to a pre cast flue. The flue spigot restrictor is attached to the fire back with two screws.
  • Page 11 CLOSURE PLATE. Fit the closure plate to the fireplace opening and ensure that it has a flat sealing area of at least 10mm sealed on all sides. See Fig. 5 below Dimensions stated are for closure plate supplied Fireplace Opening 460mm Fig.
  • Page 12: Gas Connection

    WALL MOUNTING. (NON COMBUSTIBLE WALLS ONLY) NOTE: When the fire is wall mounted, the base of the fire must be a least 150mm above the floor level. Remove the feet from the base of the fire. (4 screws in each.) Mark the position of the upper fixing holes on the wall with reference to fig.
  • Page 13: Gas Soundness

    GAS TIGHTNESS Remove the pressure test point screw from the inlet elbow and fit a manometer. Turn on the main gas supply and light the fire as described in section 2.7 and carry out a gas tightness test. Check that the gas pressure is 20.0 mbar (± 1.0 mbar), 8.0 in w.g. +/- 0.4 in w.g.
  • Page 14: Lighting The Appliance

    LIGHTING THE APPLIANCE AN ARTHRITIC CONTROL KNOB IS SUPPLIED FOR USE WITH THIS PRODUCT IF REQUIRED, SEE SECTION 4.6 FOR FITTING INSTRUCTIONS. Light the pilot by depressing the control knob at the “off” position and turn anti-clockwise (with the control depressed) to the second position marked *.
  • Page 15: Final Checks

    Replacement of parts must be carried out by a competent person such as a GAS SAFE registered gas installer. The part numbers of the replaceable parts are as follows, these are available from your local Flavel stockist, whose details can be found on the BFM Europe website, address on the back page...
  • Page 16: Maintenance Instructions

    MAINTENANCE INSTRUCTIONS Servicing Notes Servicing should be carried out annually by a competent person such as a GAS SAFE registered engineer. The service should include visually checking the chimney and fire opening for accumulations of debris and a smoke test to check for positive up-draught in the chimney.
  • Page 17: Removal Of The Burner Assembly

    Fig. 10 Removing the Upper Outer Case Fixing Screws REMOVING THE BURNER ASSEMBLY FROM THE FIRE Remove the outer case as section 3.1 Unscrew the pilot from the pilot bracket attached to the burner. See section 3.3 Unscrew injector fixing bracket. See fig. 11 Unscrew four burner fixing screws.
  • Page 18: Removal Of The Control Tap

    Fig. 12 Burner removal Position of Burner Screws REMOVING THE CONTROL TAP / MICROSWITCH FROM THE FIRE Remove the outer case as section 3.1 Remove the service plate from the control valve air duct by unscrewing the two screws. See fig. 13 Unscrew the control valve lock-nut from the top of the control valve.
  • Page 19: Removal Of The Ods

    Fig. 14 Control Valve Panel Removal Remove 2 off Screws as Indicated To refit the control valve, reassemble in reverse order noting that the control tap locates with a flat in the control fixing panel. Carry out a gas soundness test after re-assembly. REMOVING THE ODS- PILOT ASSEMBLY Note : Because this appliance is fitted with an atmosphere sensing ODS-pilot it is not possible to replace the thermocouple separately, because the...
  • Page 20 Fig. 15 REPLACING THE RADIANTS When replacing the radiants, always ensure that they are correctly located as shown in Fig. 16 below. Fig. 16 Ensure that the rear face of the ceramic radiant is touching the front edge of the position- ing plate as indicated Front edge of the Positioning Plate...
  • Page 21: User Instructions

    SECTION 4 - USER INSTRUCTIONS 4.1 CONDITIONS OF INSTALLATION It is the law that all gas appliances are installed only by a competent (e.g. GAS SAFE Registered) Installer, in G.B. in accordance with the installation instructions and the Gas Safety (Installation and Use) Regulations 1998. Failure to install appliances correctly could lead to prosecution.
  • Page 22: About Your Fire

    ABOUT YOUR NEW FLAVEL MISERMATIC GAS FIRE The Flavel Misermatic gas fire incorporates a unique and highly developed heat exchanger which combined with the radiant plaques gives maximum heat whilst maintaining reasonable running costs Please take the time to fully read these instructions as you will then be able to obtain the most effective and safe operation of your fire.
  • Page 23: Operating The Fire

    OPERATING THE FIRE AN ARTHRITIC CONTROL KNOB IS SUPPLIED FOR USE WITH THIS PRODUCT IF REQUIRED, SEE SECTION 4.6 FOR FITTING INSTRUCTIONS. Light the pilot by depressing the control knob at the “off” position and turn anti-clockwise (with the control depressed) to the second position marked *.
  • Page 24 4.4.2 CLEANING THE RADIANTS The ceramics may discolour slightly over a period of time, this is normal for radiant fires. Any dust or small soot deposits that accumulate on the ceramics can easily be cleaned. Carefully remove the ceramics and brush gently with a soft brush. To remove the ceramic, remove the dress-guard as shown in fig.
  • Page 25: Replacing The Battery

    REPLACING THE BATTERY IN THE IGNITION GENERATOR The battery holder is located at the bottom R/H/S of the fire, unscrew the cap, fit a new AA battery and re-fit the cap. See Fig. 4 below. Fig. 4 Battery Cap Spark Generator AA Battery IN THE EVENT OF THE FIRE FAILING TO LIGHT, PLEASE VISUALLY CHECK FOR SPARKING AT THE IGNITION ELECTRODE ON THE PILOT.
  • Page 26: Fitting The Arthritic Control Knob

    FITTING THE ARTHRITIC CONTROL KNOB The arthritic control knob is supplied in the loose items pack, this item should be used if necessary as an aid to operate the control valve on the fire. To fit the arthritic control knob firstly fit the self adhesive pads to the arthritic control knob itself as shown below in Fig.
  • Page 27 Finally, re-fit the arthritic control knob assembly to the product as shown overpage Re-fit the control knob assembly to the fire as shown below in Fig. 7 / 8. Fig. 7 Ensure that the indentation in the arthritic control knob is positioned as shown below in Fig.
  • Page 28 GAS SAFE registered gas installer. The part numbers of the user replaceable parts are as follows, these are available from your local Flavel stockist whose details will be found on the BFM Europe website, address shown below Ceramic Radiant Plaques B-48680 Part No.