Do you have a question about the HLP-C100 Series and is the answer not in the manual?

Questions and answers

Vlamco Belgium
January 29, 2025

We have on the controller HLP-C100 the indication E108 . Motor do not start , what to do.

Summary of Contents for Holip HLP-C100 Series

  • Page 1 Operating Manual ZHEJIANG HOLIP ELECTRONIC TECHNOLOGY CO., LTD. TEL: 0571-28891071 FAX: 0571-28891072 http: //www.holip.com...
  • Page 2 HLP-C100 Series Operating Manual...
  • Page 4: Table Of Contents

    - 21 - 5.3 Using digital in terminals to control the drive [AUTO] - 21 - 5.4 Forward, Reverse and Jog - 21 - 5.5 Multi-speed - 22 - Chapter 6 Parameter Overview - 23 - HLP-C100 Series Operating Manual...
  • Page 5 12.4 Force single coil - 82 - 12.5 Preset single register - 83 - 12.6 Force multiple coils - 84 - 12.7 Preset multiple regs - 85- 12.8 Read/write array - 85 - 12.9 Exception code - 87 - HLP-C100 Series Operating Manual...
  • Page 6: Chapter 1 Safety Precautions

    Otherwise it will cause the drive to protect or even damage the drive. ● Do not make any high voltage test with any component inside the inverter. These semi-conductor parts are subject to the damage of HLP-C100 Series Operating Manual...
  • Page 7: During The Power-Up

    1.2 During the power-up Danger ● Do not plug the connectors of the inverter during the power up to avoid any surge into the main control board due to plugging, which might cause the damage of the inverter. HLP-C100 Series Operating Manual...
  • Page 8: During The Operation

    Before touching any potentially live parts of the inverter, please wait at least 4 minutes. Otherwise, it may expose you to a risk of electrical shock. HLP-C100 Series Operating Manual...
  • Page 9: Chapter 2 Standards And Specifi Cations

    Control panel with LED display and potentiometer With coating on PCB Reserved Domestic sale Overseas sale Without RS485 With RS485 26-27 Reserved 28-3 1 VXXX Indicate sof tware version number, such as V235 means the version number is 2.35 . HLP-C100 Series Operating Manual...
  • Page 10: Particular Specifi Cations

    Digital: 0.001Hz; analogy: 0.5‰ of the f unctions resolution max. operating f requency ; Control LCP , digital terminal, local bus; command source Frequency setting LCP , analog, local bus; source Ramp control Selectable 8-speed steps; HLP-C100 Series Operating Manual...
  • Page 11 Scanning time 1ms; Control Terminals 1 relay outputs (FA- Relay output FB-FC) ; Digital output Scanning time 1ms; Power supply 10VDC power +10V supply; 1, RS+(TX+,RX+), Terminal number RS-(TX-, RX-); RS485 serial communication Ground for COM; RS485 HLP-C100 Series Operating Manual...
  • Page 12 Below 1000m altitude no de-rating is necessary but above 1000m the ambient temperature or the maximum output current should be decreased. Dcrease the output by 1% per 100m altitude above 1000m or reduce the max. ambient temperature by 1 degree per 200m. HLP-C100 Series Operating Manual...
  • Page 13: Chapter 3 Installation And Wiring

    ● Check if the inverter has got any damage or deformation during the transportation and handling; ● Check if there is one piece of HLP-C100 series inverter and one copy of the quick guide available when unpacking it; ● Check the information on the label to see if the specifi cations meet your order (Operating voltage and KW value);...
  • Page 14: Dimensions Of The Inverter

    ) recommended. Details of terminal tightening torques : Power(KW)and Voltage Torque(Nm) levels 1 ×200- 3×200- 3×380- DC connection/ Control Line Motor Relay 240V 240V 480V Brake terminals 0.37-1 .5 0.37-1 .5 0.75-2.2 1 .4 0. 1 5-0.4 HLP-C100 Series Operating Manual...
  • Page 15: Fuse Specifi Cations

    HLP-C1000D7523 HLP-C10001D523 HLP-C1000D7543 HLP-C10001D543 HLP-C10002D243 3.3.3 Installation and Direction Note: Install the unit and make sure that it is f ree f rom high moisture high temperature heavy dust metal f ragments and high oil mist. HLP-C100 Series Operating Manual...
  • Page 16: Wiring Terminal

    380V class: 3- phase 380-480V50/60Hz Single phase connected to R T U V W Power output, connect to the motor Connect the brake resistor, make sure to set C02. 1 0 -BR +BR C02. 1 1 etc. Ground terminal HLP-C100 Series Operating Manual...
  • Page 17 2 seconds. RS485 RS+, RS- RS485 + and RS485- ; communication Ground for Isolated f rom internal GND; communication Note: Only the machine with RS485 (type code number 25 is B) has RS+ RS- and COM; HLP-C100 Series Operating Manual...
  • Page 18 HLP-C100 Series 3.3.5 Wiring Basic Connection Diagram of HLP-C100 series inverter: Precautions for the main circuit wiring: ● While wiring the sizes and specifi cations of wires should be selected and the wiring should be executed according to the electrical engineering regulations to ensure the safety.
  • Page 19: Chapter 4 Operation And Display Interface

    C03.00 group C03 C03.00 Press key to shif t to f ractional part Turn clockwise to select parameter C03. 1 0 C03. 1 0 Press to show the fi rst option of C03. 1 0 HLP-C100 Series Operating Manual...
  • Page 20: Fwd/Rev Status

    20.5 4.2.2 FWD/REV Status Confi rm the direction of the motor according to the set value, as shown in the following table: Reference Running status Indicator Display STOP STOP HLP-C100 Series Operating Manual...
  • Page 21: Data Read-Outs

    (C16.01) is 50%, display accuracy: 0.001 Show the motor current Motor (C16. 1 4) is 9.00A, display Current accuracy: 0.01 Show the motor voltage Motor (C16. 1 2) is 380.0V, display Voltage accuracy: 0. 1 HLP-C100 Series Operating Manual...
  • Page 22: View Alarm Record

    4.2.4 View alarm record If the drive trips, fault code will be showed to illustrate the reason, all the trip record will be saved. Key-press LCP Display Action Description Press key to display the fi rst C00.04 basic C00.03. HLP-C100 Series Operating Manual...
  • Page 23: View State Parameter

    4.2.5 View state parameter View the status of input terminal, reference, feedback value, output f requency, output current, output voltage, and the power etc. Key-press LCP Display Action Description Press to display the fi rst basic C00.03 parameter C00.03. HLP-C100 Series Operating Manual...
  • Page 24 fi nish browse value of C16.01 . C16.60 Press to select C16.60. Press to view the value in C16.60, 0100 indicates status of 0000 FOR DI1 DI2 is 0, and status of REV is 1 . HLP-C100 Series Operating Manual...
  • Page 25: Led Display

    HLP-C100 Series 4.2.6 LED Display HLP-C100 Series Operating Manual...
  • Page 26: Chapter 5 Quick Application Guide

    5. Disconnect the digital input terminal FOR and GND to stop the f requency converter. 5.4 Forward, Reverse and Jog 1 . IO terminals connection as following: 2. Parameter initialization; 3. Set parameter as following: C03. 1 1=10Hz C03. 1 5=1, C03. 1 6=0 HLP-C100 Series Operating Manual...
  • Page 27: Multi-Speed

    C03. 1 0[2]=30 (Speed3=15Hz) , C03. 1 0[3]=40 (Speed4=20Hz) , C03. 1 0[4]=50 (Speed5=25Hz) , C03. 1 0[5]=60 (Speed6=30Hz) , C03. 1 0[6]=70 (Speed7=35Hz) , C03. 1 0[7]=80 (Speed8=40Hz) , 4. Press “AUTO” key on LCP; HLP-C100 Series Operating Manual...
  • Page 28: Chapter 6 Parameter Overview

    50~1000 (Um.n) Motor *C01.23 Frequency (f m. 20~400 Motor Current *C01.24 Dep.on motor date (Im.n) Motor Nominal *C01.25 100~9999 Speed (nm.n) Motor Cable *C01.42 0~150 Length C01.55 0~999 Characteristic-U C01.56 0~400 Characteristic-F C01.71 Start Delay 0.0~10.0 HLP-C100 Series Operating Manual...
  • Page 29 0: Preset reference + Actual Reference source 1,2 C03.07 reference 1 : Preset reference calculation priority Preset C03. 1 0 -100.00~100.00 0.00 Reference C03. 1 1 Jog Speed [Hz] 0.0~400.0 Catch up/slow C03. 1 2 0.00~100.00 0.00 Down Value HLP-C100 Series Operating Manual...
  • Page 30 Time C03.80 Jog Ramp Time 0. 1 0~300.00 0: Linear; 2: Sine C03.84 Ramp 5 Type ramp; Ramp 5 Ramp C03.85 0. 1 0~300.00 up Time Ramp 5 Ramp C03.86 0. 1 0~300.00 down Time HLP-C100 Series Operating Manual...
  • Page 31 C04. 1 8 Current Limit 0~300 Max. Output *C04. 1 9 0.0~400.0 65.0 Frenquency Warning Speed C04.52 0.0~400.0 Warning Speed C04.53 0. 1 ~400.0 65.0 High Missing Motor *C04.58 0: Off; 1 : On; Phase Function HLP-C100 Series Operating Manual...
  • Page 32 53: No alarm; 55: Running reverse; Terminal VI C06. 1 0 0.00~9.99 0.07 Low Voltage Terminal VI C06. 1 1 0. 1 0~10.00 10.00 High Voltage Terminal VI C06. 1 2 0.00~19.99 0. 1 4 Low Current HLP-C100 Series Operating Manual...
  • Page 33 0.0~10.00 0.01 Gain Process PI C07.34 0. 1 0~9999.00 9999.00 Integral time Process PI Feed C07.38 0~400 Forward Factor On Reference C07.39 0~200 Bandwidth Process PI C07.41 -100-100 Output Low Process PI C07.42 -100-100 Output High HLP-C100 Series Operating Manual...
  • Page 34 C08.36 0.010~10.000 5.000 Delay C08.94 Bus Feedback 1 -32768~32767 2~6: 2kHz~6kHz; Switching C14.01 7: 8kHz; 8: 10 kHz; Frequency 9: 12kHz; 10: 16kHz; Over *C14.03 0: Off; 1 : On; modulation Damping Gain C14.08 0~200 Factor HLP-C100 Series Operating Manual...
  • Page 35 0: Do not reset; C15.06 Counter 1 : Reset Counter; Fault Log: Error C15.30 0~255 Code Internal Fault C15.3 1 -32767~32767 Reason C15.40 FC Type View FC type View power size of C15.41 Power Section the drive HLP-C100 Series Operating Manual...
  • Page 36 View sof tware ID C15.50 Power Card Power card Frequency View f requency C15.51 Converter converter No. Serial Number Power Card View power card C15.53 Serial number serial number View parameter list C15.92 Parameter List of the drive HLP-C100 Series Operating Manual...
  • Page 37 Note: Reference signed with “*”in parameter No. column means this parameter can’t be modifi ed when the motor is running. In factory setting column, “*” means the default setting for this parameter is determined by the drive type. HLP-C100 Series Operating Manual...
  • Page 38: Chapter 7 Parameter Description

    “1” means display the item, “0” means does not display the item. For example, if you want to display the states of the temperature and the terminal VI on LCP. Transform the binary code to decimal digit, C00.33=1 ×2 +1 ×2 =24. HLP-C100 Series Operating Manual...
  • Page 39 [1] Enabled, none of parameter can be changed except this; Function: This feature used to prevent non-commissioning person to change the parameter settings. Attention: Main Menu Password f unction is only valid to LCP, not active to local bus. HLP-C100 Series Operating Manual...
  • Page 40: Parameter Group 01: Load And Motor

    20~400 Function: Enter the rated motor f requency f rom the nameplate data. Description of the choice: Default setting depends on the inverter size. Attention: Changing this parameter affects motor nominal speed set in C01 .25. HLP-C100 Series Operating Manual...
  • Page 41 0/Fn Function: This parameter is an array parameter [0-5], used f or setting f requency points [F0-F5] to manually form a V/F characteristic matching motor. Voltage at each point is def ined in par. C01.55, V/F HLP-C100 Series Operating Manual...
  • Page 42 Attention: Setting start delay to 0.0 sec. disables Start Function, [C01 .72], when start command is given. C01.72 Function Description Range Unit Default Setting Start Function Option: [0] DC Hold; [2] Coast; Function: Select [0], Motor is energized with DC holding current (par. C02.00) HLP-C100 Series Operating Manual...
  • Page 43 Option: [0] Coast, the inverter is off; [1] DC Hold, the motor is energized with a DC current. See par. C02.00 DC Hold Current for more information. Function: Here it is possible to select the stop f unction according to different applications. HLP-C100 Series Operating Manual...
  • Page 44: Parameter Group 02: Brakes

    DC-brake command, see C05. 1 * choice (5) ; DC brake cut in speed, see C02.04; C02.02 Function Description Range Unit Default Setting DC Braking Time 0.0~60.0 10.0 Function: This parameter defi nes DC brake current (C02.01) time during which HLP-C100 Series Operating Manual...
  • Page 45 Select whether to enable OVC, which reduces the risk of drive trip due to over voltage on the DC link caused by generative power f rom load. Attention: The OVC is not active/required if resistor brake has been chosen in C02. 1 0 (Brake Function). HLP-C100 Series Operating Manual...
  • Page 46: Parameter Group 03: Reference/Ramps

    If the f requency converter detects the corresponding terminals connected, then the bit is “1”, otherwise, the bit is “0”. Digital input terminal binary code and the corresponding relationship between pre- set values as follows: HLP-C100 Series Operating Manual...
  • Page 47 20 Hz, when only DI1 is on, the output f requency is 26 Hz, when only DI2 is connected, the output f requency is14Hz, when both DI1 and DI2 are on, the output f requency is 20Hz. HLP-C100 Series Operating Manual...
  • Page 48 [21] LCP potentiometer, use signals f rom LCP potentiometer as reference resource, see C06.8*; Function: C03. 1 5 C03. 1 6 defi ne up to three different reference signals, the sum of which defi nes is the actual reference. HLP-C100 Series Operating Manual...
  • Page 49 Function: This parameter is used for setting whether to save the data changed in the Up/Down f unction if the f requency stops or af ter it power down. C03.4* Ramp1 C03.40 Function Description Range Unit Default Setting Ramp 1 Type HLP-C100 Series Operating Manual...
  • Page 50 The corresponding relationship between state of the digital input terminals binary code and the selected ramp type are as follows: Binary system bit2 bit1 bit0 Ramp Group Terminal State HLP-C100 Series Operating Manual...
  • Page 51 C03.50 Function Description Range Unit Default Setting Ramp2 Type Option: [0] Linear: Motor ramp up to the preset f requency with a constant acceleration; [2] S-ramp: Motor ramp to the preset f requency with non-linear acceleration. HLP-C100 Series Operating Manual...
  • Page 52 Attention: Choose a ramp-down time such that no over-voltage arises in the inverter due to regenerative operation of motor and such that the generated current does not exceed the current limit set in C04. 1 8. HLP-C100 Series Operating Manual...
  • Page 53 C03.84 Function Description Range Unit Default Setting Ramp5 Type Option: [0] Linear: Motor ramp up to the preset f requency with a constant acceleration; [2] S-ramp: Motor ramp to the preset f requency with non-linear acceleration. HLP-C100 Series Operating Manual...
  • Page 54 C04. 1 8. selected digital input or serial communication port. See C05. 1 , choose [14]. HLP-C100 Series Operating Manual...
  • Page 55 0.10~300.00 Function: Enter acceleration time f rom 0Hz to rated Motor speed in C01 .25. Attention: Choose a ramp-up time such that the output current does not exceed the current limit set in C04. 1 8. HLP-C100 Series Operating Manual...
  • Page 56: Parameter Group 04: Limits/Warnings

    Function: Set the minimum limit for Motor Speed, the motor speed low limit can be set to correspond to the minimum output f requency of the motor shaf t . The motor speed low limit must not exceed the Motor Speed High Limit in C04. 1 4. HLP-C100 Series Operating Manual...
  • Page 57 Function: Enter the n value, when the motor speed exceeds this limit, the high display reads Speed High. Attention: This setting must be within normal motor f requency range, otherwise, it may trigger an error warning. HLP-C100 Series Operating Manual...
  • Page 58 (e.g. small motor running pure U/ f mode). However, choosing [0] Of f, f unction disabled, may lead to overheating, Holip strongly recommends to make an active setting to avoid motor damage. C04.6* Speed Bypass C04.61...
  • Page 59: Parameter Group 05: Digital Input/Output

    [1 7] Preset ref. bit2, same as [15]; [28] Catch up, select catch up to increase the resulting reference value by the percentage set in par. C03. 1 2; [29] Slow down, select slow down to reduce the resulting reference HLP-C100 Series Operating Manual...
  • Page 60: Parameter Group 06: Analog In/Out

    7.7 Parameter Group 06: Analog In/Out C06.1* Analoge Input 1 C06.10 Function Description Range Unit Default Setting Terminal VI Low Voltage 0.00~9.99 0.07 Function: Enter VI Low Voltage corresponding to Min. reference/feedback set in C06. 1 4. HLP-C100 Series Operating Manual...
  • Page 61 C06. 1 0 or C06. 1 2. C06.15 Function Description Range Unit Default Setting Terminal VI High -4999.000~4999.000 50.000 Ref. /Feedb. Function: Enter VI High Ref./Feedb. Corresponding to max voltage or max current set in C06. 1 1 or C06. 1 3. HLP-C100 Series Operating Manual...
  • Page 62 Terminal VI Mode Option: [0] Voltage mode; [1] Current mode; Function: Select the input to be present on analog input VI. C06.8* LCP Potmeter The LCP potmeter can be select either as reference resource or relative reference resource. HLP-C100 Series Operating Manual...
  • Page 63: Parameter Group 07: Controller

    PI-controller will be initialized to the current f requency when the output f requency can not be changed. This can prevent the integrator continue to integrate on an error when the PI-controller can’t adjust output f requency. HLP-C100 Series Operating Manual...
  • Page 64 Function: Process PI controller output low limit, 100% corresponds to C04. 1 9. C07.42 Function Description Range Unit Default Setting Process PI Output High -100-100 Function: Process PI controller output High limit, 100% corresponds to C04. 1 9. HLP-C100 Series Operating Manual...
  • Page 65: Parameter Group 08: Comm. And Options

    [4] Max. speed, Run motor at max.f requency until communication resumes; [5] Stop and trip, Stop motor and restart f requency in order to restart via either LCP or Digital input . Function: Select action to be taken in case of timeout. HLP-C100 Series Operating Manual...
  • Page 66 [3] No parity (2 stop bit) ; C08.35 Function Description Range Unit Default Setting Min. Response Delay 0.001~0.50 0.010 Function: Def ine the minmum delay time f rom receiving a request to transmitting the respond out. HLP-C100 Series Operating Manual...
  • Page 67: Parameter Group 14: Special Functions

    Option: [0] Off, Disable the overmodulation f unction to avoid torque ripple on the motor shaf t; [1] On, Connects the overmodulation f unction to obtain an output voltage up to 15% greater than mains voltage; Function: This feature allows more accurate speed control near and over HLP-C100 Series Operating Manual...
  • Page 68 If reset have been done and the running signal is active, f requency converter will restart automatically. Attention: If the auto reset mode is selected, the f requency converter may possibly restart automatically af ter the alarm disappear. HLP-C100 Series Operating Manual...
  • Page 69 Function: This f unction ensures the output voltage is independent of any voltage fl uctuations in the DC link . Low torque ripple. In some cases, this dynamic compensation may cause resonance problems in DC link circuit and then this f unction should be disabled. HLP-C100 Series Operating Manual...
  • Page 70: Parameter Group 15: Drive Information

    C15.31 Function Description Range Unit Default Setting Internal Fault Reason -32767~32767 Function: This parameter contains internal f ault reasons, mostly used in combination with alarm 38. HLP-C100 Series Operating Manual...
  • Page 71 Unit Default Setting FC ordering No. Description of Choice: View ordering number of the FC. C15.47 Function Description Range Unit Default Setting Power Card Ordering No. Description of Choice: View ordering number of the power card. HLP-C100 Series Operating Manual...
  • Page 72: Parameter Group 16: Data Readouts

    Function: View the total remote reference, the total reference is sum of pulse, analog, preset, LCP Potmeter, local bus and f reeze reference. C16.05 Function Description Range Unit Default Setting Motor Speed [RPM] 0~9999 Function: View motor speed. HLP-C100 Series Operating Manual...
  • Page 73 C16.34 Function Description Range Unit Default Setting Inverter Temp. 0~255 Function: View the temperature of drive’s heatsink. C16.5* Ref./Feedb. C16.52 Function Description Range Unit Default Setting Feedback -4999.000~4999.000 Function: View analog or pulse feedback in HZ. HLP-C100 Series Operating Manual...
  • Page 74 Function: View the last received reference f rom the FC port. C16.9* Diagnosis Readouts C16.90 Function Description Range Unit Default Setting Alarm Word 0~0xFFFFFFFFUL Function: View the alarm word sent via the serial communication port in hex HLP-C100 Series Operating Manual...
  • Page 75 Fan Fault U phase loss Undefi ned Undefi ned Undefi ned V phase loss Undefi ned Undefi ned Undefi ned W phase loss Undefi ned Undefi ned Undefi ned Undefi ned Undefi ned Undefi ned Undefi ned HLP-C100 Series Operating Manual...
  • Page 76 Function: View the Warning Word 1 sent via serial communication port in hex code. C16.93 Function Description Range Unit Default Setting Warning Word 2 0~0x7FFFFFFFUF Function: View Warning Word 2 sent via serial communication port in hex code. HLP-C100 Series Operating Manual...
  • Page 77: Chapter 8 Accessory Specifi Cation

    15m. More than fi ve types of shielded cable is recommended for use in the presence of electromagnetic interference environment. 8.2.2 Mounting steps An external LCP mounting kit is provided; users need to open a hole (size as shown below). The installation steps are as follows: HLP-C100 Series Operating Manual...
  • Page 78: Chapter 9 Emc

    EMC fi lter capacitors, this may cause damage to the inverter. If a drive with EMC fi lter is connected to the TN grid, the drive may be burned. Remove the RFI switch can help to reduce the leakage currents. HLP-C100 Series Operating Manual...
  • Page 79: Chapter 10 Warnings/Alarms And Fault Handling

    Missing phase on supply side or too high voltage imbalance. Mains Phase The allowed power imbalance A.04 E.04* Loss of HLP-C100 series inverter is 3% of the rated voltage.(IEC Standard) Intermediate circuit voltage A.07 E.07 Over Voltage exceeds limit.
  • Page 80 A.79 E.79 Undefi ned fault Holip Company. Parameter E.80 Make parameter initialized. Initialization LCP Connection No communication between Er.84 with the inverter LCP and the inverter. failed Button is Refer to parameter group Er.85 disabled C04* HLP-C100 Series Operating Manual...
  • Page 81: Fault Indication And Trouble Shooting

    1 . Motor runs motor parameter settings are not correct, please adjust unsteadily motor parameter settings, if no effect, please contact Holip Company. Confi rm whether the screen display is normal; If screen display is properly, verif y if warning or alarm information displays;...
  • Page 82 If operation of the display screen is normal, please make without fault sure connection between motor and the f requency converter message is correct and then operate the drive in hand mode. Please contact Holip Company if motor can’t rotate. HLP-C100 Series Operating Manual...
  • Page 83: Chapter 11 Maintenance

    If it needs to be stored for a long time make sure to power it up one time within a year and the power-up time should be at least above fi ve hours. When powering up, supply voltage must be increased slowly with a voltage regulator to the rated voltage value. HLP-C100 Series Operating Manual...
  • Page 84: Chapter 12 Communication Protocol

    HLP-C100 Series Chapter 12 Communication protocol HLP-C100 series inverter follows the standard Modbus RTU protocol. 12.1 Format specifi cation Address Function code Data 8 bits 8 bits N*8 bits 16 bits 1) Address: 1-247 2) Function: HLP-C100 support following f unction code...
  • Page 85 Satety closed No alarm Alarm Reserved Reserved Reserved No warning Warning Not at reference At reference Hand mode Auto mode Out of f req range In f req range Stopped Running Reserved No voltage warning Voltage warning HLP-C100 Series Operating Manual...
  • Page 86: Read Coil Status

    48. Coil address 49 is f requency converter output f requency. 00 10 Data bits number is 16. 0x 0010 convert to decimal number is 16 3D C9 CRC check Receive data Field Description FC address Function The read byte number is 2 HLP-C100 Series Operating Manual...
  • Page 87: Read Holding Registers

    C03.03 is 60000*0.001=60.000 B5 7B CRC check 12.4 Force Single Coil Example: write parameter to RAM and EEPROM Transmit: 01 05 00 40 FF 00 8D EE (Hexadecimal) Receive: 01 05 00 40 FF 00 8D EE (Hexadecimal) HLP-C100 Series Operating Manual...
  • Page 88: Preset Single Register

    Receive: 01 06 03 F1 00 01 19 BD (Hexadecimal) Transmit data Field Description FC address Function 03 F1 The register address of C01 .01 is 101 * 10-1=1009 (0x03F1) 00 01 The parameter value is 1 19 BD CRC check HLP-C100 Series Operating Manual...
  • Page 89: Force Multiple Coils

    So if you want to set the f requency as feq, you can calculate: feq / C03.03 × 16384 then converts into hexadecimal. 16384 converts into hexadecimal is 0x4000. The reason to be multiplied 16384 is for a higher accuracy. HLP-C100 Series Operating Manual...
  • Page 90: Preset Multiple Regs

    00 02 Register number 52 14 CRC check 12.8 Read/Write array Example: write parameter 3 10[2] (index=2) Transmit: 01 06 00 08 00 02 89 C9 (Hexadecimal) Receive: 01 06 00 08 00 02 89 C9 (Hexadecimal) HLP-C100 Series Operating Manual...
  • Page 91 FC address Function 0C 1B The register address of C03. 1 0 is 3 10* 10-1=3099 (0x0C1B) 00 01 Register number Byte number 00 00 The value of 3 10[2] is 0 69 BB CRC check HLP-C100 Series Operating Manual...
  • Page 92: Exception Code

    0x12 Other exception 0x40 Invalid data address 0x41 Invalid length 0x42 Invalid length and value 0x43 Invalid parameter 0x82 The parameters has no bus connection 0x83 Factory settings, cannot be changed. HLP-C100 Series Operating Manual...