[ VIII Test Run Mode ]
2. 2-unit combination
(1) Cooling only operation
Model name of BC controller
Ambient
tempera-
ture
Indoor unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
ing
BC controller (1/2/3)
High pressure(63HS1)/
Low pressure(63LS)
Pressure
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
Outdoor
unit
Temp. of
each sec-
tion
Indoor unit
HWE0803A
Operation
Indoor
DB/WB
Outdoor
No. of connected units
No. of units in operation
Model
Main pipe
Branch pipe
Total pipe length
[lbs-oz]
Pulse
Discharge (TH4)
Heat exchanger outlet
(TH3)
Accumulator inlet
Accumulator outlet
Compressor inlet
Compressor shell bottom
LEV inlet
Heat exchanger inlet
- 167 -
Outdoor unit model
PURY-P144TSHMU-A
PURY-P72THMU-A
CMB-P108NU-GA
26.7°C/19.4°C [80°F/67°F]
35°C/- [95°F/-]
Unit
-
36/36/36/36
m
[ft]
-
kg
A
V
Hz
43
275/275/275/275
2000/2000/250
2.65/0.90
[384/130]
MPa
[psi]
76 [169]
41 [106]
14 [57]
°C
14 [57]
[°F]
23 [73]
34 [93]
PURY-P72THMU-A
4
4
5 [16-3/8"]
10 [32-3/4"]
45 [147-5/8"]
Hi
34.1 [75]
31.5
230
43
2.65/0.90
[384/130]
2.59/2.59
[375/375]
76 [169]
41 [106]
14 [57]
14 [57]
23 [73]
34 [93]
24 [75]
12 [54]
GB