Summary of Contents for Di-LOG DL6780 Combi Volt 1
Page 1
Di-LOG Instruction Manual DL6780 Combi Volt 1™ DL6790 Combi Volt 2™...
Page 2
7) Phase rotation test 8) Maintenance 9) Specification 1) Introduction Thank you for purchasing a Di-Log voltage continuity tester. This tester has been designed in accordance with the latest international safety standards. The combivolt testers are fully automatic voltage indicators capable of measuring AC/DC voltage up to 690 V.
Page 3
Caution! Dangerous voltage. Danger of electrical shock Continuous double or reinforced insulation complies with IEC536, class 11 CE Symbol of conformity, confirms conformity with relevant EU directives. The meter complies with EMC directives (89/336/EEC). Specifically standards EN 50081-1 and EN 50082-1 as well as the Low Voltage Directive (73/23/EEC) described in the standard EN 61010-1.
Page 4
L1 and L2. The continuity LED (6) will be lit and an audible tone should be heard. Before any test check the unit on a known voltage source. If the unit is defective it should be put out of service and returned to Di-Log for repair.
Page 5
4) Voltage test Always hold the test probes by the handles behind the finger guards.. Observe the safety notices at all times. An audible tone is present when an AC voltage and a negative DC voltage are indicated. The maximum switch on time is 30 s. When this time has elapsed you must wait 10 minutes before retesting.
Page 6
5) Single pole voltage detection Perform a function test prior to this test. This unit can be used as a single pole voltage detector when batteries are inserted. The single pole test is intended only as a quick check. The circuit must be checked again for the presence of voltage using the two pole method.
Page 7
7) Phase rotation test Perform a function test prior to this test. This unit can determine the phase rotation within a three phase supply. Connect test probe L2 to the supposed phase 2 and the test probe L1 to the supposed phase 1. If the R LED illuminates the phases are in the correct sequence 1 to 2.
Page 8
Connect test probe L2 to the supposed phase 3 and test probe L1 to the supposed phase 2. If the R LED illuminates the phases are in the correct sequence 2 to 3. Connect test probe L2 to the supposed phase 1 and the test probe L1 to the supposed phase 3.
Page 9
200g 200g 24 Month Warranty Di-Log instruments are subject to stringent quality controls. If in the course of normal daily use a fault occurs we will provide a 24 month warranty (only valid with invoice). Faults in manufacture and materials defect will be rectified by us free of charge, provided the instrument has not been tampered with and returned to us unopened.
Need help?
Do you have a question about the DL6780 Combi Volt 1 and is the answer not in the manual?
Questions and answers