Tyco MR601TEx Product Information

Tyco MR601TEx Product Information

Intrinsically safe enhanced optical smoke detector m600 series

Advertisement

MR601TEx INTRINSICALLY SAFE ENHANCED OPTICAL SMOKE DETECTOR
PRODUCT APPLICATION AND DESIGN INFORMATION
1.
INTRODUCTION
The MR601TEx Intrinsically Safe High Performance Optical
Smoke Detector forms part of the M600Ex series of plug in
detectors for ceiling mounting. The detector plugs into the
5BEx 5" Universal IS Base and is intended for two-wire
operation on the majority of the control equipment currently
manufactured by the company. The Intrinsically Safe High
Performance Optical detector is available in one sensitivity
setting only.
2.
INTRINSIC SAFETY
The detectors are for use in potentially explosive gas and dust
atmospheres (zone 0 gas, zone 20 dust).
The detectors are designed to comply with EN/IEC 60079-
0:2006, EN/IEC 60079-11:2007 and EN/IEC61241-11:2006 for
Intrinsically Safe apparatus. They are certified:
ATEX code:
Certificate:
Gas/Dust code:
IECEx Certificate:
These detectors are designed and manufactured to protect
against other hazards as defined in paragraph 1.2.7 of Annex II
of the ATEX Directive 94/9/EC.
© 2010 Tyco Safety Products
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
II 1 GD
BAS01ATEX1134X
Ex ia IIC T5
Ex iaD 20 T100°C
IECEx BAS 07.0056X
Fig. 1 Optical System Schematic
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
2.1
DETECTOR USE
It is recommended that the detector is used in conjunction with
a suitable isolator or shunt diode safety barrier in a certified
Intrinsically Safe system, ie, System 620.
2.2
SPECIAL CONDITIONS OF SAFE USE
The apparatus has a plastic enclosure which constitutes a
potential electrostatic hazard. The enclosure must be cleaned
only with a damp cloth.
3.
OPERATING PRINCIPLE
The MR601TEx operates by sensing the optical scatter from
smoke particles generated in a fire. While the optical scatter
detector can give good detection performance for the majority
of fires, some fast burning fires produce little visible smoke and
some produce very black smoke, neither of which are easily
detected by the optical scatter detector. (Such fires are
represented in EN54-7 by Polyurethane and Heptane type fires
respectively). These fires do, however, produce high heat
outputs with an associated rise in air temperature.
The detector has been designed to offer improved detection of
such fires, by detecting the rapid rate-of-rise of air temperature
and under these conditions, increasing the smoke detection
sensitivity. This gives an earlier detection of such fires and a
broader detection capability than a standard detector.
The MR601TEx detector has two sensing systems as follows:
An optical chamber with associated electronics
to measure the presence of smoke by light
scatter.
A thermistor with its associated electronics to
detect the presence of hot air draughts or high
temperatures.
M600 SERIES
01B-04-D12
5
5/10
PAGE 1 of 7

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MR601TEx and is the answer not in the manual?

Questions and answers

Summary of Contents for Tyco MR601TEx

  • Page 1 INTRINSIC SAFETY OPERATING PRINCIPLE The detectors are for use in potentially explosive gas and dust The MR601TEx operates by sensing the optical scatter from atmospheres (zone 0 gas, zone 20 dust). smoke particles generated in a fire. While the optical scatter...
  • Page 2: Optical System

    Fig. 2 Measuring Chamber Showing Smoke Flow Path OPTICAL SYSTEM The MR601TEx detects visible particles produced in fires by using the light scattering properties of the particles. The d e t e c t o r u s e s t h e o p t i c a l a r r a n g e m e n t s h o w n diagrammatically in Fig.
  • Page 3: Circuit Operations

    Fig. 4 Block Schematic of Detector CIRCUIT OPERATIONS FEATURES OF MEASURING CHAMBER A simplified block schematic of the detector is given in The MR601TEx uses vertical chevrons to exclude ambient Fig. 4. light. The emitter is subjected to a pulse stream only every 10s in Smoke incident on the detector is channelled into the order to reduce the quiescent current.
  • Page 4: Mechanical Construction

    PCB. The Dimensions PCB is then potted. The dimensions of the MR601TEx detector are shown in The chamber cover is clipped to the body over the optical Fig. 5. chamber ensuring the thermistor protrudes through the cover.
  • Page 5: Electrical Characteristics

    The response threshold value is normally given EN 61000-6-3 for Emissions in dB/m, (or % per m). © 2010 Tyco Safety Products PAGE 5 of 7 Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE...
  • Page 6: Installation Recommendations

    The MR601TEx is designed to respond to the mandatory tests TF2 to TF5 as required by BS5445 Pt 7. The MR601TEx gives an earlier response to TF5 fires than the MR601 due to its thermal circuit detecting the heat generated by this test of fire and the MR601TEx being ‘enhanced’.
  • Page 7: Cpd Information

    The detector is identified by the logo label, as shown in Fig. 9. GREEN Fig. 9 Detector identification © 2010 Tyco Safety Products PAGE 7 of 7 Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE...