TECHNICAL CHANGES MUH-18RV - MUH-A18WV - 1. Refrigerant has changed. (R22 R410A) 2. Refrigerant system diagram has changed. • Compressor, stop valve and 4-way valve have changed. • Diameter of stop valve has changed. (Gas: [15.88 [12.7) • Accumulator has removed and high pressure receiver has been added.
Page 4
New Specification Current Specification The incompatible refrigerating oil easily separates from Since refrigerant and refrigerating oil are compatible each, refrigerant and is in the upper layer inside the suction muffler. refrigerating oil backs to the compressor through the lower Raising position of the oil back hole enables to back the position oil back hole.
Page 5
2.Refrigerant piping 1 Specifications Use the refrigerant pipes that meet the following specifications. Outside diameter Wall Pipe Insulation material thickness 0.8 mm 6.35 For liquid Heat resisting foam plastic 0.8 mm 9.52 0.8 mm Specific gravity 0.045 Thickness 8 mm 12.7 For gas 1.0 mm...
PART NAMES AND FUNCTIONS OUTDOOR UNIT MUH-A18WV - MUH-A24WV - MUH-A30WV - Air inlet Air inlet (back and side) (back and side) Piping Drainage hose Air outlet Air outlet Drain outlet ACCESSORIES Outdoor unit MUH-A24WV- MUH-A18WV- MUH-A30WV- Drain socket Drain cap {33 Drain cap {16 —...
SPECIFICATION Outdoor model MUH-A18WV - MUH-A24WV - Cooling Heating Cooling Heating Function Single phase Single phase Power supply 230V, 50Hz 230V, 50Hz Capacity — Dehumidification — Air flow(High) K /h 2,196 2,760 Starting current Compressor motor current 7.54 6.84 9.81 10.12...
NOISE CRITERIA CURVES MUH-A18WV- MUH-A24WV- FAN SPEED FAN SPEED SPL(dB(A)) LINE SPL(dB(A)) LINE High High Test conditions, Test conditions, Cooling : Dry-bulb temperature 35: Wet-bulb temperature 24: Cooling : Dry-bulb temperature 35: Wet-bulb temperature 24: Heating : Dry-bulb temperature 7: Wet-bulb temperature 6:...
OUTLINES AND DIMENSIONS MUH-A18WV- Unit: mm OUTDOOR UNIT Drainage hole [16.2 Air in Air in Drainage Air out 3holes [33 Service panel Liquid refrigerant pipe joint Refregerant pipe (flared) [6.35 Gas refregerant pipe joint Refregerant pipe (flared) [12.7 Open as a rule...
WIRING DIAGRAM MUH-A18WV - MODEL WIRING DIAGRAM OUTDOOR UNIT 21S4 RT61 CN661 CN721 2 3 4 INDOOR UNIT CN711 CONNECTING CIRCUIT BREAKER SR61 POWER SUPPLY ~ /N TAB20 230V 50Hz DEICER P.C.BOARD SYMBOL NAME SYMBOL NAME SYMBOL NAME COMPRESSOR CAPACITOR...
MUH-A30WV - MODEL WIRING DIAGRAM OUTDOOR UNIT RT61 RT62 RT63 CIRCUIT BREAKER CN711 1 2 3 CN661 CN662 CN724 CN721 SR62 21S4 SR61 TAB52 COM NO CN730 NR61 DEICER PC BOARD SYMBOL SYMBOL NAME SYMBOL NAME NAME CZ SURGE ABSRBER OUTDOOR FAN MOTOR (INNER PROTECTOR) TERMINAL BLOCK COMPRESSOR CAPACITOR...
PERFORMANCE CURVES MUH-A18WV - MUH-A24WV - MUH-A30WV - The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions, since operating conditions vary according to the areas where these units are installed. The following information has been pro- vided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
Page 16
2 2 Air flow should be set at MAX. 3 3 The unit of pressure has been changed to MPa on the international system of units(SI unit system). The conversion factor is : 1(MPa [Gauge]) =10.2(kgf/f f [Gauge]) (kgf/F[Gauge])(MPa[Gauge]) MUH-A18WV - MUH-A18WV - 230V 230V 35(:)
<MUH-A18/A24WV> During heating operation, the outdoor fan motor is controlled by the temperature of indoor coil thermistor RT12 for excess rise protection of compressor discharge pressure. (MUH-A18WV)Outdoor fan OFF : 52°C Outdoor fan ON : 48°C Outdoor fan (MUH-A24WV)Outdoor fan OFF : 58°C High pressure protection Outdoor fan ON : 55°C...
Page 26
NOTE : During high pressure protection and for 4 minutes and 15 seconds after high pressure protection, defrosting of outdoor heat exchanger is not detected by the defrost thermistor RT61. <MUH-A30WV> During heating operation, the outdoor fan and the compressor are controlled by the temperature of indoor coil thermistor RT12 for excess rise protection of compressor discharge pressure.
Page 27
5. R.V. coil control Heating · · · · · ON Cooling · · · · · OFF Dry · · · · · · · · OFF NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor. (HEAT) (COOL / DRY) 5 sec.
Page 28
(1) LEV opening correction by discharge temperature The LEV opening is corrected according to the temperature difference between target discharge temperature (Tb) and actual discharge temperature (Ta). 1 The LEV correction is used properly for two kinds according to the LEV opening status at operation off. Opening immediately before having stopped last time Rank 100 pulse or less...
10-1. COMPULSORY DEFROSTING MODE FOR SERVICE By short circuit of the connector JPDS and JPSG(MUH-A18WV)/ JPG1 and R871(MUH-A24/A30WV) on the outdoor deicer P.C. board, defrosting mode can be accomplished regardless of the defrost interval restriction. (Refer to page 37 or 38.) Defrost thermistor RT61 must read below -3°C.
Page 30
Start Indoor unit Indoor unit Indoor unit operates. OPERATION INDICATOR operates. doesn't receive Outdoor unit lamp on the indoor unit is Outdoor unit the signal from doesn't operate flashing on and off. doesn't remote controller. normally. operate. Outdoor unit Unit doesn't Indoor unit Outdoor unit Indoor unit...
Page 31
INNER MAIN Color of Normal Abnormal PROTECTOR 145i 8: OPEN lead wire MUH-A18WV MUH-A24WV MUH-A30WV AUX.1 AUX.2 ( 88i15: CLOSE WHT – BLK 102 " ~ 126 " 55 " ~ 68 " 55.4 " ~ 67.7 " Open or –...
Page 32
Compressor and/or outdoor fan motor doesn’t operate. A A Check of outdoor unit MUH-A18WV Operate the unit in COOL or HEAT mode by pressing the EMERGENCY OPERATION switch. 3-minute time delay works. Test run operation operates for 30 minutes. Compressor Rectify the indoor and doesn't operate.
Page 33
MUH-A24WV MUH-A30WV Turn ON the power supply. Is there 230V AC to Check the outdoor power supply between on the and connection of wiring. outdoor terminal block Compressor does not operate. Is there 5V DC between Is there 230V AC between Rectify the connecting J101 - J401...
Page 34
Compressor and/or outdoor fan motor doesn’t stop. B B Check of outdoor unit MUH-A18WV Turn OFF the power supply. After 1 minute, turn ON power supply again. Is there 230V AC between 3 on the Does compressor stop? compressor contactor (52C) and N on the Rectify the connecting wire.
Check the outdoor power supply and connection of wiring. on the outdoor terminal block? Is there 5V DC between J205 + -J101 - (MUH-A18WV)/J101 + -J401 - (MUH-A24/A30 WV) on the deicer P.C. board?(Refer to page 37 or 38.) During EMERGENCY OPERATION, is there 10V DC between both ends of R601on the Replace the deicer P.C.
When OPERATION INDICATOR lamp flashes 10-time. Heating/ Cooling doesn't operate. Check of LEV (Expansion valve) MUH-A30WV 1 During pressing OPERATION SELECT button on remote controller, press RESET button. 2 First, release RESET button. 1 During pressing OPERATION SELECT (Confirm all displays of remote controller.) button on remote controller, press 3 Then release OPERATION SELECT button.
Page 37
MUH-A18WV - Outdoor deicer P.C. board CN711 CN721 Power supply input Outdoor fan motor R.V. coil 230V AC 230V AC 230V AC NR61 Varistor Fuse 2A/250V R601 5~10V DC Defrost interval time short pin (JPDS, JPSG) (Refer to page 29.)
2Pull the terminal while pull out the terminal pushing the locking slowly. Locking lever lever. Connector 12-1. MUH-A18WV - OUTDOOR UNIT OPERATING PROCEDURE PHOTOS 1. Removing the cabinet Photo 1 (1) Remove the screws of the cabinet. (2) Hold the down of the cabinet on the both side and remove the cabinet.
Page 40
OPERATING PROCEDURE PHOTOS 3. Removing the propeller and the outdoor fan motor (1) Remove the cabinet. (Refer to 1.) Photo 4 Set screws of the (2) Remove the propeller nut and the propeller. outdoor fan motor Propeller NOTE : Loose the propeller in the rotating direction for Lead clamps removal.
Page 41
12-2. MUH-A24WV - MUH-A30WV - NOTE : These photos are MUH-A30WV. OUTDOOR UNIT MUH-A24WV is almost the same as MUH-A30WV. OPERATING PROCEDURE PHOTOS 1.Removing the cabinet Photo 1 Screw of the top panel (1) Remove the screws of the service panel. (2) Remove the screws of the top panel.
Page 42
OPERATING PROCEDURE PHOTOS 3. Removing the propeller and the outdoor fan motor Photo 5 (1) Remove the cabinet. (Refer to 1.) (2) Remove the propeller nut and the propeller. NOTE : Loose the propeller in the rotating direction for Set screws of the removal.
PARTS LIST MUH-A18WV - 13-1. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS DEFROST THERMISTOR Part numbers that are circled are not shown in the illustration. Q'ty/unit Symbol Part No. Part Name in Wiring Remarks MUH-A18WV- Diagram E02 817 233...
Page 44
MUH-A24WV - 13-2. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS...
Page 45
MUH-A24WV - 13-2. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS Part numbers that are circled are not shown in the illustration. Q'ty/unit Symbol in Wiring Remarks Part No. Part Name MUH-A24WV - Diagram E02 819 297 TOP PANEL E02 821 630 OUTDOOR HEAT EXCHANGER E02 821 301...
Page 46
MUH-A30WV - 13-3. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS...
Page 47
MUH-A30WV - 13-3. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS Part numbers that are circled are not shown in the illustration. Q'ty/unit Symbol Part No. Part Name in Wiring Remarks MUH-A30WV - Diagram TOP PANEL E02 819 297 E02 819 309 THERMISTOR RT62, RT63...
Page 48
E02 444 705 DRAIN CAP E02 444 706 DRAIN CAP HEAD OFFICE: MITSUBISHI DENKI BLDG.,2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN C C Copyright 2003 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD Distributed in Nov. 2003. No.OB322 6 New publication, effective Nov. 2003 Made in Japan...