Do you have a question about the Series 63 and is the answer not in the manual?
Questions and answers
rodolfo lainez
January 22, 2025
how can add water to my boiler PEERLESS, series 63??
1 comments:
Mr. Anderson
February 10, 2025
To add water to your Peerless Series 63 boiler, follow these steps:
1. Turn Off the Boiler: Ensure the boiler is turned off to avoid any risk of injury or equipment damage.
2. Locate the Water Feeder: Identify the automatic or manual water feeder connected to the boiler's water supply line.
3. Check the Sight Glass: Observe the water level in the sight glass. The correct level is typically around the middle of the glass.
4. Add Water: - If the boiler has an automatic water feeder, it should add water to maintain the correct level. If it is not functioning, inspect the feeder for any issues. - For a manual water feeder, open the valve slowly to allow water to enter the boiler. Monitor the sight glass carefully to avoid overfilling.
5. Stop Adding Water: Once the water level reaches the proper height (middle of the sight glass), stop adding water.
6. Turn On the Boiler: Once the water level is correct, turn the boiler back on.
If you encounter issues, such as the water level not changing or overfilling, contact a qualified technician for assistance.
USING THIS MANUAL USING THIS MANUAL DANGER A. INSTRUCTION MANUALS The Series 63/64™ Installation, Operation & Indicates a condition or hazard which will cause Maintenance Manual is divided into four basic sections: severe personal injury, death or major property damage.
2. For servicing the burners provide not less than 24" A. GENERAL from the front of the boiler. Series 63/64™ boilers are supplied knocked down for field 3. The remaining clearances should be 6" from all sides. assembly or completely assembled as packaged boilers.
1000 appliances other than fan assisted and for the Btu/hr (44 cm per 1000 W) of total input rating Series 63/64™ Boiler shall be determined as of all equipment. See Figure 1.2 for an follows: illustration of this arrangement.
Page 6
PREINSTALLATION 4. Outdoor Combustion Air: Outdoor combustion air is ii. Where communicating with the outdoors to be provided through one or two permanent through horizontal ducts, each opening shall openings. The minimum dimension of these air have a minimum free area of 1 in per 2000 openings is 3 inches (76 mm).
Page 7
5. Combination Indoor and Outdoor Combustion Air: If ii. Where the free area through a louver or grille the required volume of indoor air exceeds the is not known, it shall be assumed that wooden available indoor air volume, outdoor air openings or louvers will have 25% free area and metal ducts may be used to supplement the available louvers and grilles will have 75% free area.
PREINSTALLATION WARNING G. PLANNING THE LAYOUT Liquefied Petroleum (LP) is heavier than air and may Prepare sketches and notes of the layout to minimize the collect or “pool” in a low area in the event of a leak possibility of interferences with new or existing from defective equipment.
BOILER PLACEMENT & ASSEMBLY 2. BOILER PLACEMENT & ASSEMBLY 5. Insert the push nipples into the nipple ports of one of A. PACKAGED BOILER the split block ends. Make sure the nipples are clean and free of burrs. Use a block of wood to protect the 1.
BOILER PLACEMENT & ASSEMBLY 11. If the sections do not draw together using the torque 5. Slide the burner tray under the cast iron block specified above, the block must be separated and the assembly and attach to the end sections using the 1/4" nipples replaced before reassembly is attempted.
5. Position the Inner Front Panel between the side panels and align the mounting holes on the side 1. The Series 63™ boilers employ a wrap-around style flanges with the clearance holes on the side panels. jacket while the Series 64™ boilers use an individual Attach with four #10 x 1/2"...
Page 12
BOILER PLACEMENT & ASSEMBLY 7. Attach the Draft Hood to the Flue Collector using #10 x 1/2" sheet metal screws provided. Refer to Figure 2.7. Figure 2.7: Draft Hood Attachment Figure 2.8: Label & Rating Plate Locations 8. Position the Top Jacket Panel so that the flanges 10.
3. VENTING c. Do not connect the vent for this boiler into any A. CHIMNEY OR VENT vent system which operates with positive pressure. 1. Inspect the existing chimney or vent system. Make sure it is in good condition. Inspect chimney liner d.
VENTING a. Orient the vent damper operator to facilitate a. Seal any unused openings in the common venting connection of the vent damper harness to system. knockout on right side of boiler. b. Visually inspect the venting system for proper size and horizontal pitch and determine there is no b.
BOILER PIPING 4. BOILER PIPING 3. If the boiler is piped in a secondary loop separate A. WATER BOILER PIPING – SINGLE from the system expansion tank, the boiler circulator BOILER should be located on the return side of the boiler pumping away from the common piping.
BOILER PIPING 3. Pipe the steam header a minimum of 24" above the B. WATER BOILER PIPING – MULTIPLE normal water line using swing joints to attach the BOILERS risers into the steam header. Refer to the PB Heat Water Installation Survey and Hydronics Institute Residential Hydronic Heating Use Threaded Fittings for Manifold Piping Installation Design Guide for guidance on multiple boiler...
BOILER PIPING 6. The use of a Hartford Loop in all installations is D. STEAM BOILER INDIRECT WATER recommended to ensure reliability of the system. A HEATER PIPING check is required on the pump discharge of all pumped return systems. 1.
FUEL PIPING 5. FUEL PIPING Table 5.1: Gas Input & Valve Inlet A. INSTALLATION Gas Input (CFH) Gas Valve Inlet (NPT) 1. Pipe gas to the boiler in accordance with local codes. Model Nat. Gas LP Gas Nat. Gat LP Gas In the absence of local regulations refer to the National Fuel Gas Code, ANSI Z223.1/NFPA 54.
Page 19
FUEL PIPING 5. Refer to table 5.4 for minimum supply pressure for the purpose of input adjustment. Table 5.4: Minimum Supply Pressure Natural Gas Supply Pressure Model (in. Water) 63-03L 5.00 63-03 5.00 63-04L 5.00 63-04 5.35 Figure 5.3: Gas Train Manifold – 64-07 & 64-08 63-05L 5.00 Natural Gas, Standing Pilot...
CONTROLS & TRIM 6. CONTROLS & TRIM 3. Pressure/Temperature Gauge: A. WATER BOILER CONTROLS & TRIM Install the pressure/temperature gauge (theraltimeter) 1. Safety Relief Valve: supplied with the boiler into the 1/2" tapping located on the right side of the boiler. Refer to Figure 6.2 for a.
CONTROLS & TRIM B. STEAM BOILER CONTROLS & TRIM 1. Safety Valve: a. Pipe the boiler safety valve provided into the 3/4" tapping on the left side of the boiler as shown in Figure 6.4. Be sure that the relief valve is sized in accordance with local code requirements.
ELECTRICAL 7. ELECTRICAL 2. Mount the blocked vent switch in the rear of the A. CONNECT SUPPLY WIRING boiler on the draft hood as shown in Figure 7.2. 1. All electrical wiring must be done in accordance with local codes. In the absence of local codes use ANSI/NFPA 70 “The National Electrical Code.”...
ELECTRICAL 4. Mount the ignition module, if required (spark ignited D. WIRING DIAGRAM INDEX units only), as shown in Figure 7.4. Table 7.1: Wiring Diagram Index - Water Boilers Standing Pilot, Fig. 7.6 Fig. 7.7 Natural Gas Standing Pilot, Fig. 7.6 LP Gas Spark Ignition, Fig 7.8...
BOILER OPERATION 8. BOILER OPERATION normal water level is about 25-7/8" above the boiler A. SYSTEM INSPECTION foundation (about 2/3 of the gauge glass). 1. Confirm that all water, gas, and electricity are 2. Pumped Return Systems with Boiler Feed Unit - turned off.
BOILER OPERATION 6. Spark-Ignited Pilot Ignition Check c. Note: If the meter is not automatically corrected for temperature and pressure, the meter reading a. Turn up the Operating Temperature Control for a must be corrected to actual conditions during the call for heat.
BOILER OPERATION WARNING 12. Close the make up water valve and open the boiler drain valve. Cleaning the boiler requires the use of very hot water 13. Drain the boiler completely. Then refill and drain and corrosive chemicals. Use care when handling to again one or two times to make sure all of the soda prevent injury.
BOILER OPERATION FOR YOUR SAFETY READ BEFORE LIGHTING WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, or loss of life. A. This appliance has a pilot which must be lighted by If you cannot reach your gas supplier, call the fire hand.
Page 38
BOILER OPERATION FOR YOUR SAFETY READ BEFORE LIGHTING WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, or loss of life. A. This appliance has a pilot which must be lighted by If you cannot reach your gas supplier, call the fire hand.
BOILER OPERATION FOR YOUR SAFETY READ BEFORE LIGHTING WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, or loss of life. A. This appliance is equipped with an ignition device Immediately call your gas supplier from a which automatically lights the pilot.
Page 40
BOILER OPERATION FOR YOUR SAFETY READ BEFORE LIGHTING WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, or loss of life. A. This appliance is equipped with an ignition device Immediately call your gas supplier from a which automatically lights the pilot.
MAINTENANCE 9. MAINTENANCE WARNING Product Safety Information Refractory Ceramic Fiber Product This appliance contains materials made from refractory ceramic fibers (RCF). Airborne RCF fibers, when inhaled, have been classified by the International Agency for Research on Cancer (IARC), as a possible carcinogen to humans. After the RCF materials have been exposed to temperatures above 1800°F, they can change into crystalline silica, which has been classified by the IARC as carcinogenic to humans.
MAINTENANCE A. GENERAL D. MONTHLY MAINTENANCE (WITH BOILER OPERATING) 1. Disconnect this boiler from the gas supply piping during any pressure testing of the gas system. 1. Check boiler room floor drains for proper functioning. 2. Check pipes adjacent to cold walls or in unheated spaces.
MAINTENANCE d. Remove the vent pipe, vent damper, top jacket 2. Inspect entire venting system for corrosion, support panels and flue collector. and joint integrity. Repair as necessary. e. Brush flueways with wire brush. 3. Check the pilot and main burner flame. See Figure f.
TROUBLE SHOOTING – SERVICE TIPS 10. TROUBLESHOOTING – SERVICE TIPS Problem Possible Cause Suggested Remedy Defective Thermocouple Replace Heavy Draft Blowing across Pilot Redirect Air Movement or Eliminate Plugged Pilot Orifice Replace Orifice Pilot Outage Check Manual Pilot Valve Check Main Gas Shut-Off Valve No Gas Check Manual Meter Valve Consult Gas Company...
Page 45
TROUBLE SHOOTING – SERVICE TIPS Problem Possible Cause Suggested Remedy Air Adjustment Screws Turned in Too Far Adjust Screws Out Low Gas Pressure in Manifold Adjust Main Gas Pressure Regulator (Insufficient Air Injection) or Check Line Pressure Burner Ports Partially Closed Replace Burners or Clean Ports (Rust, Dirt, Lint, etc) Burner(s) Burning with Yellow Flame...
Page 46
TROUBLE SHOOTING – SERVICE TIPS Problem Possible Cause Suggested Remedy Clogged returns on gravity system Clean or Re-Pipe Return Line(s) Incorrect near-boiler piping causing wet steam Correct Piping per Manual to system Trap failed open, allowing steam to enter returns Replace Trap or Trap Element Use smaller Air Vent or Use Two Small Vents in {Radiator Hammer} Large radiator may be...
REPAIR PARTS 12. REPAIR PARTS Repair parts are available from your installer or by contacting PB Heat, LLC, 131 S. Church, Bally, PA 19503. Note: Remember to include boiler model number and serial number when ordering parts. Figure 12.1...
Page 52
Series 63/64 ™ Boilers I n s t a l l a t i o n , O p e r a t i o n & M a i n t e n a n c e M a n u a l TO T H E I N S TA L L E R : This manual is the property of the owner and must be affixed near the boiler for future reference.
Need help?
Do you have a question about the Series 63 and is the answer not in the manual?
Questions and answers
how can add water to my boiler PEERLESS, series 63??
To add water to your Peerless Series 63 boiler, follow these steps:
1. Turn Off the Boiler: Ensure the boiler is turned off to avoid any risk of injury or equipment damage.
2. Locate the Water Feeder: Identify the automatic or manual water feeder connected to the boiler's water supply line.
3. Check the Sight Glass: Observe the water level in the sight glass. The correct level is typically around the middle of the glass.
4. Add Water:
- If the boiler has an automatic water feeder, it should add water to maintain the correct level. If it is not functioning, inspect the feeder for any issues.
- For a manual water feeder, open the valve slowly to allow water to enter the boiler. Monitor the sight glass carefully to avoid overfilling.
5. Stop Adding Water: Once the water level reaches the proper height (middle of the sight glass), stop adding water.
6. Turn On the Boiler: Once the water level is correct, turn the boiler back on.
If you encounter issues, such as the water level not changing or overfilling, contact a qualified technician for assistance.
This answer is automatically generated