These guidelines should be utilized by a qualifi ed service
agent.
LOCKOUTS
Soft Lockout
•
Occurs when a system safety device trips to break the
sequence of operation. The control will try to start the
system in a timed basis but will not reinstate operation
until the failure is corrected.
Hard Lockout
•
Occurs when the main controller fails and must be
replaced.
RESETTING THE HEATER CONTROL
•
Soft lockouts as diagnosed by the system error codes
require the gas control to be reset.
•
To reset the control, slide the "ON/OFF" switch to the
"OFF" position. Wait for 10 seconds and move the
switch back to the "ON" position.
•
If the problem that caused the control to lock out has
not been corrected, the control will remain or again go
back into lockout.
46
TROUBLESHOOTING GUIDELINES
www. johnwoodwaterheaters .com
IGNITION STATE AND TIMING
IGNITION STATE
5 seconds (NG models)
Pre-purge
15 seconds (LP models)
Hot Surface Igniter
10 seconds
(HSI) Warmup
Ignition Activation
3.5 seconds maximum
Period (IAP)
Flame Recognition
0.5 second
Period (FRP)
Trial For Ignition
IAP + FRP
Flame Stabilization
Not Applicable
Period
Inter-purge
30 seconds
Flame Failure
2 seconds max
Response Time
(@ 1uA fl ame current)
Post-purge
30 seconds
Pressure Switch (PS)
2 minutes
Prove Period
Pressure Switch (PS)
Fault Delay (failed
2 minutes
open/closed)
Soft Lockout
20 minutes
Energy Cut Off
Indefi nite
(ECO) Limit Lockout
TIMING
328126-000