HITACHI SPLIT-UNIT AIR CONDITIONER
INSTALLATION MANUAL
Indoor Unit
Outdoor Unit
RAS-S10CY
RAC-S10CY
RAS-5115CY
RAC-5115CY
RAS-S13CY
RAC-S13CY

SAFETY PRECAUTION

G
Read the safety precautions carefully before operating the unit.
G
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
!
WARNING ........ Incorrect methods of installation may cause death or serious injury.
!
CAUTION ......... Improper installation may result in serious consequence.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of operating
the unit as described in the user's guide.
WARNING
!
G
Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may
occur if you do the installation work yourself.
G
Please observe the instructions stated in the installation manual during the process of installation. Improper
installation may cause water leakage, electric shock and fire.
G
Make sure that the units are mounted at locations which are able to provide full support to the weight of the units.
If not, the units may collapse and impose danger.
G
Observe the rules and regulations of the electrical installation and the methods described in the installation manual
when dealing with the electrical work. Use wire which is specified for the air conditioner. A short circuit and fire
may occur due to the use of low quality wire or improper work.
G
Be sure to use the specified wire for connecting the indoor and outdoor units. Please ensure that the connections
are tight after the conductors of the wire are inserted into the terminals. Improper insertion and loose contact may
cause over-heating and fire.
G
Please use the specified components for installation work. Otherwise, the units may collapse or water leakage,
electric shock and fire may occur.
G
Do not mix any coolant other than R-22 into the cooling circulation path when mounting or shifting the unit. If it
is mixed with air, the high pressure in the circulation path will rise and this may result in broken copper pipes or
faults.
!
G
Be sure to use the earth line. Do not place earth line near gas or water pipes, lightning conductor
and the earth line of telephone. Improper earthing may cause electric shocks.
G
A circuit breaker should be installed depending on the mounting size of the unit. Without a circuit breaker, the
danger of electric shock exists.
G
Do not install the unit near a location where there is flammable gas. The outdoor unit may
catch fire if flammable gas leaks around it.
G
Please ensure smooth flow of water when installing the drain hose.
1
Installation of Hanger, Wall Penetration and Installation of Protection Pipe
!
CAUTION
G
The draining of the water container inside the indoor unit can be done from the left.
Therefore the hanger must be fixed horizontally or slightly tilted towards the side of
drain hose. Otherwise, condensed water may overflow the water container.
Direct Mounting On The Wall
G
Please use hidden beams in the wall to hold the hanger.
450mm
125mm
80mm
45mm
60mm
780mm
Mark
Screw for Hanger
Please use more
than 4 screws.
Procedures of Installation and Precautions
G
Procedures to fix the hanger.
1. Drill holes on wall.
2. Push plug into the holes.
(As shown below)
(As shown below)
Procedures to fix the holder of remote control.
G
1. Drill holes on wall.
2. Push plug into the holes.
(As shown below)
(As shown below)
Wall Penetration and Installation of Protection Pipe
Drill a ø 65mm hole on
G
wall which is slightly tilted
Indoor
Outdoor
towards the outdoor side.
Seal with
Drill the wall at a small
putty
Seal with
angle.
putty
G
Cut the protection pipe
according to the wall
thickness.
G
Empty gap in the sleeve
of protection pipe should
WALL
Protection
be completely sealed
pipe
with putty to avoid
Sleeve of
protection
dripping of rain water into
pipe
the room.
<
>
IA539: A
INS RAS/RAC-S10CY (E1)
1
Black
G
Carefully read through the procedures of proper
installation before starting installation work.
G
The sales agent should inform customers regarding
the correct operation of installation.
Tools Needed For Installation Work
G
+ – Screwdriver
G
Measuring Tape
G
Saw
G
ø 65mm Power Drill
G
Allen Key (
G
Wrench (14, 17, 19, 22mm)
G
Gas Leakage Detector
G
Pipe Cutter
G
Plastic Tape
G
Pliers
G
Flare Tool
CAUTION
2
Installation of the Indoor Unit
VERTICALLY DOWNWARD PIPING
Preparation
G
Connect connecting cord.
G
Pull out the pipe, connecting cord and drain hose.
Installation
The upper part of the Indoor unit is hanged on the hanger.
G
G
The projection at the lower part of the Indoor unit is hooked onto the hanger.
125mm
Hanger
Refrigerating
Pipe
45mm
115mm
Level
Protection
Pipe
Drain Hose
Hanger
450mm
G
Push up the (PUSH) sections at the
Line
bottom of the indoor unit and pull the
Weight
Hole for pipe
bottom plate towards you. Then the
claws are released from the stationary
plate.
(The (PUSH) sections are indicated by
2 arrows in the right figure)
3. Fix the hanger on wall
with 4.1 x 32 screw
HORIZONTAL PIPING
(As shown in figure below)
Preparation
Change of Drain Hose and Installation Procedures.
G
Exchange the location of drain hose and drain cap during horizontal piping as shown in
figure below. Be sure to plug in the drain hose until the insulating material folds upon itself.
G
Please use pliers to pull out the drain cap.
(This is an easier way to remove the drain cap).
Drain cap
Please insert
until here
! WARNING
!
CAUTION
2 ~ 5mm
Be sure that the wire is not
in contact with any metal
HORIZONTAL & DOWNWARD PIPING – MAKING OPENINGS
in the wall. Please use the
During horizontal or downward piping, use a knife to cut
G
protection pipe as wire
passing through the hollow
openings as shown in figure. Then smoothen the edges of
part of the wall so as to
openings with a file.
prevent the possibility of
Pipe
damaged by mouse.
support
Unless it seals completely,
any air with high humidity
flows from outdoor and
any dew may drop.
Pull up the pipe after
bending downward
THE CHOICE OF MOUNTING SITE
WARNING
!
G
The unit should be mounted at stable, non-vibratory location which
can provide full support to the unit.
!
CAUTION
G
No nearby heat source and no obstruction near the air outlet is
allowed.
G
Knife
G
The clearance distances from top, right and left are specified in
4mm)
figure below.
G
The location must be convenient for water drainage and pipe
connection with the Outdoor unit.
G
To avoid interference from noise please place the unit and its
remote controller at least 1m from the radio, television and inverter
type fluorescent lamp.
G
To avoid any error in signal transmission from the remote controller,
please put the controller far away from high-frequency machines
and high-power wireless systems.
G
The installation height of indoor unit must be 2.3m or more in a
non public area.
Names of Indoor Components
No.
Component's Name
Qty
Mounting Plate
1
1
Screw for Mounting Plate
6
2
( 4 . 1 x 3 2 )
Holder for Remote
Controller
1
3
AAA Size Battery
4
2
Screw for holder of
Remote Controller
2
5
( 3 . 1 x 1 6 )
Remote Controller
6
1
Purifying Filter
1
7
Hole cover sticker
1
8
Connecting cords, pipe and
drain hose must be laid
together with Vinyl tape.
Hanger
1
CAUTION
!
Lift the body
of the unit
Please pull the lower part of
upwards and
the Indoor unit outwards to
then force it
check if the unit is hooked
downwards.
onto the hanger. Improper
2
installation
may
Connecting
vibration and noise.
Projection
Cord
HOW TO REMOVE INDOOR UNIT
[Push] mark positions
Drain cap
Drain hose
Drain hose
Please insert
until here
Condensed water may leak out if not inserted properly.
Openings
G
Turn the piping while holding down the lower
portion of pipe-support by hand.
1/6/09, 9:24
(Please note the following matters and obtain permission from customer before installation).
G
The outdoor unit must be mounted at a location which can sup-
port heavy weight. Otherwise, noise and vibration will increase.
G
Do not expose the unit under direct sunshine or rain. Besides,
ventilation must be good and clear of obstruction.
G
The air blown out of the unit should not point directly to animals
or plants.
G
The clearances of the unit from top, left, right and front are specified
in figure below. At least three of the above sides must be open
air.
G
Be sure that the hot air blown out of the unit and noise do not
disturb the neighbourhood.
G
Do not install at a location where there is flammable gas, steam,
oil and smoke.
G
The location must be convenient for water drainage.
G
Place the outdoor unit and its connection wire at least 1m away
from the antenna or signal line of television, radio or telephone.
This is to avoid noise interference.
The Length of Indoor Unit
Power Cord
about
0.9m
about 1.6m
Figure showing the Installation
of Indoor and Outdoor Unit.
Do not alter the power cord.
!
CAUTION
In case the pipe length is more than 8m, add refrigerant R22 at
15 gram per every meter exceeds. However, pipe length shall
Cut away shaded
not exceed 15m.
portion, and finish
the edge of the
opening so that
20
there is no burr.
Direction of Piping
Be sure to
completely
Horizontally
seal any
perpendicular
gap with
to the unit
putty.
Connection
There
are
4
directions
allowed, namely, horizontally
perpendicular to the unit,
vertically down from right,
horizontally out from right and
horizontally out to left.
Don't
form
the
piping
downward at the left of the unit.
Dimension of Mounting Stand
of the outdoor unit
(unit : mm)
35
mounting stand
12
35
500
100
700
INSTALLATION OF REFRIGERATING PIPES AFTER CONNECTION
G
The refrigerating pipes should be adjusted to fit into
the hole on the wall and then ready for further
connection.
The terminals of 2 connected pipes must be covered
G
with insulator used for terminal connection. Then the
pipes are wrapped with insulation pipe.
G
Connect the connecting cord after removing electrical
cover. (Refer to "CONNECTION OF POWER CORD")
G
After adjustment, fit the connecting cord and pipes
into the space available under the indoor unit. Use
holder to hold them tight.
8
Holder
Insulation pipe (must be wrapped with
vinyl tape at every 120mm).
Holder can be attached at the either of 2 places.
G
cause
Please select the easier position.
THE CONNECTION OF REFRIGERATING PIPE DURING THE
INSTALLATION OF INDOOR UNIT
Preparation To Install Refrigerating Pipes
The refrigerating pipes and connecting cord
G
transform and are attached.
G
The end of the refrigerating pipes are at locations
marked with "
" symbol.
Please bend at a small
radius to form an arc
0.85m
Installation
Hang the Indoor unit onto the hanger. Use the temporary stand
at the back of the Indoor unit to push its lower part 15cm
forwards.
Place the drain hose through the hole on the wall.
G
Wrap the refrigerating pipes with insulation pipe after
G
connecting refrigerating pipe.
G
Connect the connecting cord after removing electrical cover.
(Refer to "Connection of Power Cord")
G
After adjustment, the connecting cord and refrigerating pipes
are placed into the space available under the Indoor unit.
G
The projection of Indoor unit must hook to the hanger.
Heat insulation pipe
Pull this to the front
during the connection
Connecting
of refrigerating pipes
cord
to ease task.
Refrigerating pipe
3
Installation of Drain Hose
Condensed
Ditch
water pond
Bending
Condensed
upwards
water pond
You are free to choose the side (left or right) for the installation of drain
!
hose. Please ensure the smooth flow of condensed water of the Indoor
CAUTION
unit during installation. (Carelessness may result in water leakage.)
WARNING
!
!
CAUTION
2,300mm or more
6
5
4
3
G
The difference in height
between the indoor and
outdoor unit should be
kept max. 10m.
G
The connecting pipe, no
matter big or small,
should all be insulated
with insulation pipe and
then wrapped with plastic
tape. (The insulator will
deteriorate if it is not
wrapped with tape).
The connection of insulated
drain hose.
Please use insulated drain
hose for the indoor piping
(commercial product).
Drain hose
Connecting
cord
Pipe
! CAUTION
The rubber strap used for
G
fixing the insulator should
not be tied with great force.
Otherwise, this will damage
heat insulation and causes
water condensation.
Pipe
Rubber strap tied with great force
CAUTION
!
G
Please fix in the plastic core
after flaring to avoid plastic
chips entering the pipes.
below
5mm
Projection
Hook
about 15cm
Protection pipe
Drain hose
Connecting cord
Holder Connected section
!
CAUTION
Be sure that the
drain hose is not
loosely connected
or bend.

Advertisement

loading

Summary of Contents for Hitachi RAS-S10CY

  • Page 1: Safety Precaution

    The outdoor unit must be mounted at a location which can sup- the correct operation of installation. can provide full support to the unit. port heavy weight. Otherwise, noise and vibration will increase. HITACHI SPLIT-UNIT AIR CONDITIONER CAUTION CAUTION INSTALLATION MANUAL...
  • Page 2: Procedures Of Wiring

    Copper pipe When pumping starts, slightly loosen wire connection. the flare nut to check of air sucked in. Completely unscrew the spindle of the RAS-S10CY, RAS-5115CY RAS-S13CY Then tighten the flare nut. service valve (at 2 places) in anti- A (mm)

This manual is also suitable for:

Ras-5115cyRac-5115cyRac-s10cyRac-s13cyRas-s13cy