This manual is for qualified personnel. The tasks described in this manual may only be performed by qualified personnel. 1.3 Additional Information You will find further information on special topics such as designing a line circuit breaker or the description of the operating parameters in the download area at www.SMA.de/en. Installation Guide STP10-17TL-IEN102611...
Notes on this Manual SMA Solar Technology AG 1.4 Symbols Used The following types of safety instructions and general information appear in this document as described below: DANGER! DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
The free design program "Sunny Design" (www.SMA.de/en/SunnyDesign) will assist you. The manufacturer of the PV modules must have approved the modules for use with this Sunny Tripower unit. You must also ensure that all measures recommended by the module manufacturer for long-term maintenance of the module properties are taken (see also Technical Information "Module Technology", in the download area of...
Page 10
(e.g. Sunny Data Control or Sunny Explorer). To change the grid-relevant parameters, you need a personal access code, the so-called SMA Grid Guard code. The application form for the personal access code can be found in the download area at www.SMA.de/en in the category "Data Sheet" of the respective inverter.
Grounding the PV generator Comply with the local requirements for grounding the PV modules and the PV generator. SMA Solar Technology AG recommends connecting the generator frame and other electrically conductive surfaces in a manner which ensures continuous conduction and ground these in order to have optimal protection of the system and personnel.
Safety SMA Solar Technology AG 2.3 Explanation of Symbols This section gives an explanation of all the symbols shown on the inverter and on the type label. 2.3.1 Symbols on the Inverter Symbol Explanation Operation Display. Shows the operating status of the inverter.
Page 13
SMA Solar Technology AG Safety Symbol Explanation Observe all documentation accompanying the inverter. The inverter must not be disposed of with the household waste. For further information on disposal, see section 13.5 ”Disposing of the Inverter” (page 98). CE mark. The inverter complies with the requirements of the applicable EC guidelines.
Product Description SMA Solar Technology AG 3 Product Description The Sunny Tripower is a multi-string inverter which converts the DC current of a PV generator into AC current. To do this, it is equipped with 2 separate MPP trackers which can be connected to different PV modules.
Detailed information on the setting parameters of this function is available in the Technical Description "Sunny Tripower reactive power feeding and grid safety management" in the download area at www.SMA.de/en in the "Technical Description" category of the respective inverter. Installation Guide...
Unpacking SMA Solar Technology AG 4 Unpacking 4.1 Scope of Delivery Check the delivery for completeness and for any visible external damage. Contact your dealer if anything is damaged or missing. Object Number Description Sunny Tripower Electronic Solar Switch (ESS) Rear panel (wall mounting bracket)
SMA Solar Technology AG Unpacking Object Number Description Contents of Sunclix DC plug connector bag 10 / 12 DC plug connector Sunny Tripower 10000TL / 12000TL: 10 units (5 x plus, 5 x minus) Sunny Tripower 15000TL / 17000TL: 12 units (6 x plus, 6 x minus)
Installing the Device SMA Solar Technology AG 5 Installing the Device 5.1 Safety DANGER! Danger to life due to fire or explosion! Despite careful construction, electrical devices can cause fires. • Do not mount the inverter on flammable construction materials. • Do not install the inverter in areas where highly flammable materials are stored.
Page 19
SMA Solar Technology AG Installing the Device • Vertical installation or tilted backwards by max. 15°. • The connection area must point downwards. • Never install the device with a forward tilt. • Do not install horizontally. • Install the inverter at eye level. Given the weight of the device, this will facilitate disassembling if service work is necessary.
Installing the Device SMA Solar Technology AG 5.3 Mounting the Inverter with Rear Panel 1. Use the rear panel as a drilling template and mark the positions of the drill holes. Display 2. Mount the rear panel. Use 1 upper hole on the right and on the left and the hole in the middle.
Page 21
SMA Solar Technology AG Installing the Device 3. Attach the inverter to the rear panel so that the enclosure of the inverter is flush with the rear panel. – For two people to transport the inverter, each person must use the recessed grips underneath and at the same time take a hold of the upper edge of the lid.
Page 22
Installing the Device SMA Solar Technology AG 7. Screw the eye bolt supplied into the hole provided to secure the enclosure from being lifted off. Only tighten the eyebolt hand-tight. 8. Using the two M5x10 cylinder head screws provided, secure the enclosure on the underside to prevent the enclosure from being lifted off the rear panel (for torque, see section 14 ”Technical Data”...
Page 23
SMA Solar Technology AG Installing the Device Optional Theft Protection To protect the inverter from theft, you can lock it to the rear panel with a padlock. The lock must meet the following requirements: • Size: A: 6 – 8 mm diameter B: 23 –...
Electrical Connection SMA Solar Technology AG 6 Electrical Connection 6.1 Safety NOTICE! Electrostatic discharge can damage the inverter. Internal components of the inverter can be irreparably damaged by static discharge. • Ground yourself before touching a component. 6.2 Overview of the Connection Area...
Page 25
SMA Solar Technology AG Electrical Connection Object Description Electronic Solar Switch (ESS) socket Cable opening for the multi-function relay (M20, 5 mm … 13 mm) Cable feed-throughs for communication via RS485 (M32) Additional cable feed-through (M20) Cable feed-through for grid connection (AC) (M32, 14 mm … 25 mm)
Dimension the conductor cross-section with the help of the "Sunny Design" design program (www.SMA.de/en) in such a way that the conduction loss at nominal power does not exceed 1 %. The maximum cable lengths relative to the conductor cross-section are shown in the following table.
Page 27
SMA Solar Technology AG Electrical Connection Load Disconnection Unit You must install a separate three-phase circuit-breaker for each inverter in order to ensure that the inverter can be safely disconnected under load. The maximal permissible rating is located in section 14 ”Technical Data”...
Electrical Connection SMA Solar Technology AG Cable Requirements Position Name Value Cable diameter 14 ... 25 mm Conductor cross section Max. 16 mm² Strip insulation Approx. 12 mm The PE wire must be 5 mm longer than the L and N conductors! 6.3.2 AC Connection Procedure...
Page 29
SMA Solar Technology AG Electrical Connection 5. Check the correct country setting of the inverter using the supplement provided against the factory settings. If the inverter is not set to the desired country standard, then adjust the country standard using the rotary switches as described in section 6.5.3 ”Setting the Country Standard and Language...
Electrical Connection SMA Solar Technology AG 12. Screw cap nut tightly on to the cable at the feed- through. DANGER! Danger to life due to high voltages in the inverter! • Do not switch on the line circuit breaker until the PV generator has been connected and the inverter is securely closed.
SMA Solar Technology AG Electrical Connection 6.4 Connection of the PV Generator (DC) 6.4.1 Conditions for the DC connection The inverter has two input zones "A" and "B", each with its own MPP tracker. At input zone A up to 4 (Sunny Tripower models 10000TL / 12000TL ) or 5 strings (Sunny Tripower models 15000TL / 17000TL) respectively can be connected.
Page 32
Electrical Connection SMA Solar Technology AG Use of Adaptors Adaptors (branch connectors) are not to be visible or freely accessible in the immediate surrounding of the inverter. • The DC current flow may not be interrupted via adaptors. • Disconnect the inverter, as described in section 8 ”Disconnecting the Inverter”...
Page 33
SMA Solar Technology AG Electrical Connection • At installation, the DC input voltage should be at least 188 V (see section 14 ”Technical Data” (page 99)). This will ensure that the protective function of the integrated electronic string fuse is activated. Otherwise, a reversed polarity at the DC connection or a defective string will not be recognized by the inverter.
Electrical Connection SMA Solar Technology AG 6.4.2 Assembling the DC plug connector The connection cables of the PV modules must be equipped with the DC plug connectors provided for connecting the inverter. To assemble the DC plug connectors, proceed as follows: Make sure the plug connectors have the correct polarity.
Page 35
SMA Solar Technology AG Electrical Connection Result Action ☑ If the conductors are not visible in the • Loosen the clamping bracket with the help hollow cavity of the clamp, the cable is not of a screwdriver. in the correct position.
Electrical Connection SMA Solar Technology AG 6.4.3 Opening the DC Plug Connector 1. Screw the threaded joint off. 2. To release the plug, slot a screw driver into the side catch mechanism and lever out. 3. Carefully pull apart the DC plug connector.
SMA Solar Technology AG Electrical Connection 6.4.4 Connecting the PV Generator (DC) DANGER! Danger to life due to high voltages in the inverter! • Before connecting the PV generator, ensure that the AC line circuit breaker is switched off from all 3 phases.
Page 38
Electrical Connection SMA Solar Technology AG 1. Check the connection cables of the PV modules for correct polarity and that the maximum input voltage of the inverter is not exceeded. With an ambient temperature over 10 °C, the open circuit voltage of the PV modules should not exceed 90 % of the maximum input voltage of the inverter.
Page 39
SMA Solar Technology AG Electrical Connection NOTICE! Risk of fire with the PV generator due to a failure to detect reverse currents! The integrated electronic string fuse monitors the PV generator and protects it against dangerous reverse currents. To activate the electronic string fuse, proceed as follows when connecting the strings: •...
Page 40
Action The display is not showing There is a fault in the Sunny Tripower. anything after 30 seconds • Contact the SMA Serviceline (see section 16 ”Contact” and the Sunny Tripower is (page 116)). not beeping although the DC input voltage is over 188 V.
Page 41
SMA Solar Technology AG Electrical Connection 6. Follow the same procedure to connect all further strings. It is no longer necessary to wait 30 seconds. Number of Strings - Sunny Tripower 10000TL / 12000TL The Sunny Tripower models 10000TL / 12000TL only have 4 strings at input A! 7.
Page 42
Electrical Connection SMA Solar Technology AG 8. If the Sunny Tripower does not beep or display an error message, you can disconnect the Electronic Solar Switch. ☑ The display switches off. ☑ You can now commission the inverter as described in section 7 ”Commissioning” (page 58).
In some countries, the local power supply line requirements demand a mechanism which prevents the parameters for grid feeding from being able to be changed. Some country data sets are therefore protected and can only be unlocked with a personal access code, the so-called SMA Grid Guard code.
Page 44
The data set can only be unlocked by entering a personal, 10-digit SMA Grid Guard code which is valid for a maximum of 10 grid-feed hours. The application form for the personal access code can be found in the download area at www.SMA.de/en in the category "Data Sheet"...
The settings of each country data set are specified in the operation parameters. The parameters can be read out using a communication device. The description of the operating parameter is available in the download area at www.SMA.de/en in the category "Technical Description" of the respective inverter.
Page 46
Electrical Connection SMA Solar Technology AG (A) (B) Country data set Display language Grid Guard Country protection VDE0126-1-1 Italian Switzerland AS4777.3* English Australia Enel-GUIDA* Italian Italy Enel-GUIDA* German Italy RD1663-A Spanish Spain RD1663/661 Spanish Spain Not programmed** Greece English Greece...
Page 47
SMA Solar Technology AG Electrical Connection (A) (B) Country data set Display language Grid Guard Country protection MVtg Directive int Spanish Spain MVtg Directive int Not programmed** Czech Republic Customer English Flexible Customer German Flexible Customer French Flexible Customer Spanish...
Electrical Connection SMA Solar Technology AG 6.5.2 Expansion of shutdown thresholds The deactivation criteria (voltage, frequency) are specified via country parameters. Sunny Tripower inverters have the additional country data set "MVtgDirective". This parameter expand the deactivation limits of the inverter for voltage and frequency to a maximum / minimum. This...
SMA Solar Technology AG Electrical Connection 6.5.3 Setting the Country Standard and Language using Rotary Switches 1. Disconnect the inverter as described in section 8 ”Disconnecting the Inverter” (page 67). 2. Set the arrows on both rotary switches (A and B) using a screw driver (2.5 mm) to the desired positions (see table in section 6.5.1 ”Checking the...
Electrical Connection SMA Solar Technology AG 6.6 Communication 6.6.1 Bluetooth Communication via Bluetooth with a communication device is activated as standard. Networking via Bluetooth with other inverters is deactivated ex works. The following setting options are possible via a rotary switch: Switch position...
SMA Solar Technology AG Electrical Connection 6.6.2 Multi-function relay The inverter is equipped with a multi-function relay as standard. This can be activated, for instance, simultaneously with the red error LED beside the display. Other functions are being planned can be later retrofitted via a firmware update.
SMA Solar Technology AG Electrical Connection Connection Procedure 1. Switch off AC and DC supply voltage. 2. Disconnect the inverter as described in section 8 ”Disconnecting the Inverter” (page 67). 3. Loosen the display screw and raise the display until it snaps into place.
Page 54
Electrical Connection SMA Solar Technology AG Seal in screw fitting There is a two-part seal in the screw fitting. If necessary, the inner seal can be removed to insert a thicker cable. The following guideline values apply: • Cable cross section with both seals: 5 - 8 mm •...
SMA Solar Technology AG Electrical Connection 11. Fold down the display and screw it tightly. 12. Re-commission the inverter as described in section 7 ”Commissioning” (page 58). 13. Switch on supply voltage. ☑ The multifunction relay is now operational. 6.6.3 Communication module The inverter can be equipped with a RS485 communication module in order to engage in wire-linked communication with special data acquisition devices (e.g.
Electrical Connection SMA Solar Technology AG 6.7 Retrofitting Overvoltage Protectors Type II The inverter can be equipped ex works with overvoltage protectors, or they can be retrofitted at a later time. The order number for both retrofit kits (one for input A, one for input A and B) can be found in section 15 ”Accessories”...
Page 57
SMA Solar Technology AG Electrical Connection – If overvoltage protectors are only required for input A, the two overvoltage protectors must be mounted in the two upper slots. – If input B is also to be fuse-protected, overvoltage protectors must be plugged into all slots.
Commissioning SMA Solar Technology AG 7 Commissioning 7.1 Commissioning the Inverter 1. Check that the device is fixed securely to the wall. (see section 5 ”Installing the Device” (page 18)). 2. Check that the country configuration is correct. (see section 6.5 ”Setting the Country Standard and Display Language” (page 43)).
Page 59
SMA Solar Technology AG Commissioning 9. Firmly connect the Electronic Solar Switch. 10. Switch on the line circuit breaker. 11. Switch on the power supply to the multifunction relay (if applicable). Self-test in accordance with ENEL guideline during initial commissioning...
Commissioning SMA Solar Technology AG 7.2 Display messages during initialization • Firstly, the firmware version of the internal processors appears in the text lines. • After an interval of 5 seconds, or after tapping on the lid, the serial number (or the description of the inverter) and the NET ID for communication via Bluetooth will appear.
SMA Solar Technology AG Commissioning 7.3 Self-test in accordance with ENEL guideline (only for Italy) 7.3.1 Starting the Self-Test by Tapping You can start the self-test by tapping on the enclosure lid. Prerequisite here is that the country configuration of the inverter has been set to Italy (Enel-GUIDA) or a reconfiguration based on the Enel‑GUIDA country data set has been carried out.
Commissioning SMA Solar Technology AG 7.3.2 Test Sequence Note the values which are displayed during the test sequence. These values must be entered into a test protocol. The test results of the individual tests are displayed three times one after the other.
Page 63
SMA Solar Technology AG Commissioning Undervoltage test The undervoltage test follows the overvoltage test and the inverter issues the adjacent display message for 5 seconds. During the test sequence, the voltage limit applied is shown in the display of the inverter. The voltage limit is increased successively until the shutdown threshold is reached and the inverter disconnects from the grid.
Commissioning SMA Solar Technology AG Maximum Frequency The maximum frequency test follows the undervoltage test and the inverter issues the adjacent display message for 5 seconds. During the test sequence, the frequency limit applied is shown in the display of the inverter. The frequency limit is reduced successively until the shutdown threshold is reached and the inverter disconnects from the grid.
SMA Solar Technology AG Commissioning Minimum Frequency After the maximum frequency test, the minimum frequency test takes place and the inverter shows the adjacent display message for 5 seconds. During the test sequence, the frequency limit applied is shown in the display of the inverter. The frequency limit is increased successively until the shutdown threshold is reached and the inverter disconnects from the grid.
Commissioning SMA Solar Technology AG 7.4 Activating the auto-adaptive string failure detection The process of auto-adaptive string failure detection is activated on delivery. You can deactivate the string failure detection system by setting a parameter via a communication device (e.g. Sunny WebBox or Sunny Explorer).
SMA Solar Technology AG Disconnecting the Inverter 8 Disconnecting the Inverter 8.1 Safety DANGER! Danger to life due to high voltages in the inverter! Death resulting from electric shock. The inverter operates at high voltages and must be disconnected prior to carrying out work on the device.
Disconnecting the Inverter SMA Solar Technology AG 8.2 Procedure 1. Disconnect the line circuit breaker from all 3 phases and and prevent it from being reactivated. 2. If it is connected, switch off the power supply to the multifunction relay and prevent it from switching back on.
Page 69
SMA Solar Technology AG Disconnecting the Inverter 7. Using a suitable voltmeter, test for absence of voltage to ground at the AC terminal. The max. permissible diameter of the probe tip is 2 mm. If there is voltage present, check the installation! 8.
Maintenance and Cleaning SMA Solar Technology AG 9 Maintenance and Cleaning 9.1 Checking Heat Dissipation If the inverter regularly reduces its output due to too high warming (temperature symbol on the display illuminates), this can be caused by the following: • The air grills on both sides are clogged with dirt particles.
SMA Solar Technology AG Maintenance and Cleaning 9.1.1 Cleaning the Air Grills The inverter sucks air in from underneath and on the upper left side and blows it out again via the air grills. Clean the air grills if they are dirty.
Maintenance and Cleaning SMA Solar Technology AG 9.1.2 Cleaning the Fan on the Underside of the Inverter 1. Disconnect the inverter as described in section 8 ”Disconnecting the Inverter” (page 67). 2. Wait for the fan to stop rotating. Cleaning the Fan Grills 3.
SMA Solar Technology AG Maintenance and Cleaning 8. Remove the fans and clean them with a soft brush, a paint brush or a cloth and water. NOTICE! Damage to the fan through the use of pressurized air. • Under no circumstances should you use pressurized air to clean the fan. This can damaged the fan.
Page 74
Maintenance and Cleaning SMA Solar Technology AG 5. Press the latches together to the middle. 6. Remove the fan by pulling it slowly and carefully to the side. 7. Unlock and remove the plug connectors. The fan cables are long enough that you can lift the fan far enough out to disconnect the internal plug connector in the inverter.
You will also need the installer password to access the installer mode. 1. Request the installer password from the SMA Serviceline (contact: see Page 116). 2. In the installer mode set the parameter "CoolSys.FanTst" and/or "Fan Test" to "on" (by means of a communication device).
Maintenance and Cleaning SMA Solar Technology AG 9.2 Checking the Electronic Solar Switch (ESS) for wear Check the Electronic Solar Switch for wear before plugging it in. To do this, check the metal tongues (A) on the inside of the plug for brown discoloration.
• You need to enter the SMA Grid Guard code in order to unlock certain parameter sets (for setting a new country data set via the rotary switches or changing other parameters ).
During an update, the relevant display message is shown in the text line of the display. Display Description < Inst. code valid > The SMA Guard Grid code entered is valid. The configured country data set is now unblocked and can be changed. If the configured country data set is protected, the unlocking is valid for a maximum of 10 feed-in hours.
SMA Solar Technology AG Messages Display Description < Update file OK > The file found is valid. 11.2 Error Messages When errors occur, a display message including the corresponding event number will appear in the text line of the display. By tapping on the enclosure lid, multi-line messages can be switched further.
Page 80
If the grid voltage is continually within the compliance with the voltage quality of the acceptable range, and this error is still grid. displayed, contact the SMA Serviceline. < Grid fault > • Check the power supply line for strong, short-term frequency The inverter has left the grid parallel variations.
Page 81
SMA Solar Technology AG Messages Event no. Cause Corrective measures < Waiting for grid voltage > or • Check AC installation < Installation failure grid connection > • Adjust the connection as described in < Check grid and fuses >...
Page 82
Messages SMA Solar Technology AG Event no. Cause Corrective measures < High discharge curr. > • Check the strings for ground faults, as < Check generator > described in section 12.2 ”Checking the PV Generator for a Ground The leakage current from the inverter and Fault”...
Page 83
• Repair the defect in the given string. strings could also be affected. 60 - 64 < Self diagnosis > or • Contact the SMA Serviceline (see < Interference device > section 16 ”Contact” (page 116)). < Self diagnosis > or • Ensure sufficient ventilation.
Page 84
< Param. setting failed > • Check the parameters of the SD card for valid values. • Ensure change rights via SMA Grid Guard code. < Update file defectiv. > • Re-format the SD card. • Re-save the files to the SD card.
Page 85
SMA Solar Technology AG Messages Event no. Cause Corrective measures < Update main CPU failed > • Contact the SMA Serviceline (see section 16 ”Contact” (page 116)). Internal device fault. < Update RS485I module failed > • Re-try update. Internal device fault: however, the inverter •...
Page 86
< Do not disconn. ESS > as described in section 8 ”Disconnecting the Inverter” (page 67). • Contact the SMA Serviceline (see section 16 ”Contact” (page 116)). < Connect ESS, do not open cover > • Connect the Electronic Solar Switch. Device failure or reverse current in the PV •...
Page 87
SMA Solar Technology AG Messages Event no. Cause Corrective measures < Inst. code invalid > • A valid SMA Grid Guard code has been entered. The SMA Grid Guard code entered (personal installer password) is invalid. < Grid param. locked >...
Sunny Tripower are in a safe errors (e.g. reversed poles or defective state. string). There is a defect in the Sunny 64 or 82 • Contact the SMA Serviceline (see Tripower section 16 ”Contact” (page 116)). STP10-17TL-IEN102611 Installation Guide...
SMA Solar Technology AG Failure search 12.2 Checking the PV Generator for a Ground Fault If the inverter displays event number "35", "36" or "37", there is probably a ground fault in the PV generator. Check the strings for ground faults, as described in the following: 1.
Failure search SMA Solar Technology AG 3. Repeat step 2 for each string. Result Action ☑ You have found a ground fault. • The installer of the PV generator must remedy the ground fault in the affected string before you may reconnect the string to the inverter.
Page 91
2 and 3. Result Action ☑ There is a conducting There is probably a different fault in the inverter. connection. • Continue with point 8. • Consult the SMA Serviceline for details on further procedure. Installation Guide STP10-17TL-IEN102611...
Page 92
The varistors are specially manufactured for use in the inverter and are not commercially available. You must order replacement varistors directly from SMA Solar Technology AG (see section 15 ”Accessories” (page 115)). Use original varistors only that are sold by SMA Solar Technology AG.
Page 93
SMA Solar Technology AG Failure search 9. Pre-screw all 4 screws of the DC lid and then tighten them (see section 14 ”Technical Data” (page 99)). 10. Re-commission the inverter as described in section 7 ”Commissioning” (page 58). ☑ The varistors have now been replaced and the inverter is back in operation.
Since the failure of one varistor is generally due to factors that affect all varistors in a similar way (temperature, age, inductive overvoltages), SMA Solar Technology AG recommends replacing all overvoltage protectors at once. The order numbers for both retrofit kits (one for input A, one for input A and B) can be found in section 15 ”Accessories”...
Page 95
SMA Solar Technology AG Failure search 4. Remove all overvoltage protectors from the slots. Press together grooved surfaces on both sides. The green strip in the window (A) signals that the overvoltage protector is in perfect operating condition. A red strip in the window indicates that the overvoltage protector is faulty.
SMA Solar Technology (see section 12.4 ”Replacing overvoltage protectors type II” (page 94)). Prior to returning your inverter to SMA Solar Technology AG, you must swap over the upper and lower lids of your inverter with the corresponding transport lid.
Page 97
• Fasten the lock washers for all 6 screws with the toothing facing toward the lid. 5. Screw the lower lid tight. ☑ Your inverter is now ready to be sent back to SMA Solar Technology AG. 6. Now mount the upper lid of your inverter onto the replacement device in the same manner.
Dispose of the inverter at the end of its service life in accordance with the disposal regulations for electronic waste which apply at the installation site at that time. Alternatively, send it back to SMA Solar Technology AG with shipping paid by sender, and labeled "ZUR ENTSORGUNG"...
SMA Solar Technology AG Technical Data 14 Technical Data 14.1 Sunny Tripower 10000TL DC input Maximum DC power at cos ϕ = 1 10,200 W DC max Maximum DC voltage * 1,000 V DC max MPP voltage range 320 V … 800 V DC nominal voltage...
Technical Data SMA Solar Technology AG Power factor, adjustable cos ϕ … 0.8 lagging leading Supply phases Connection phases Overvoltage category Test voltage 2.55 kV (DC, 1 s routine testing) 4.25 kV (DC, 5 s type testing) Surge testing voltage 10 kV Internal consumption in night mode < 1 W...
SMA Solar Technology AG Technical Data General data Electronics protection rating * IP65 Connection area protection rating * IP54 Protection class Noise emission (typical) No data * according to DIN EN 60529 Protective Equipment All-pole DC disconnection unit Electronic Solar Switch,...
Page 102
Technical Data SMA Solar Technology AG Efficiency Peak efficiency η 98.1 % European efficiency η 97.7 % euro STP10-17TL-IEN102611 Installation Guide...
SMA Solar Technology AG Technical Data 14.2 Sunny Tripower 12000TL DC input Maximum DC power at cos ϕ = 1 12,250 W DC max Maximum DC voltage * 1,000 V DC max MPP voltage range 380 V … 800 V DC nominal voltage 600 V...
Page 104
Technical Data SMA Solar Technology AG Connection phases Overvoltage category Test voltage 2.55 kV (DC, 1 s routine testing) 4.25 kV (DC, 5 s type testing) Surge testing voltage 10 kV Internal consumption in night mode < 1 W Mechanical data Width x height x depth...
Page 105
SMA Solar Technology AG Technical Data General data Electronics protection rating * IP65 Connection area protection rating * IP54 Protection class Noise emission (typical) No data * according to DIN EN 60529 Protective Equipment All-pole DC disconnection unit Electronic Solar Switch,...
Page 106
Technical Data SMA Solar Technology AG Efficiency Peak efficiency η 98.1 % European efficiency η 97.7 % euro STP10-17TL-IEN102611 Installation Guide...
SMA Solar Technology AG Technical Data 14.3 Sunny Tripower 15000TL DC input Maximum DC power at cos ϕ = 1 15,340 W DC max Maximum DC voltage * 1,000 V DC max MPP voltage range 360 V … 800 V DC nominal voltage 600 V...
Page 108
Technical Data SMA Solar Technology AG Connection phases Overvoltage category Test voltage 2.55 kV (DC, 1 s routine testing) 4.25 kV (DC, 5 s type testing) Surge testing voltage 10 kV Internal consumption in night mode < 1 W Mechanical data Width x height x depth...
Page 109
SMA Solar Technology AG Technical Data General data Electronics protection rating * IP65 Connection area protection rating * IP54 Protection class Noise emission (typical) No data * according to DIN EN 60529 Protective Equipment All-pole DC disconnection unit Electronic Solar Switch,...
Page 110
Technical Data SMA Solar Technology AG Efficiency Peak efficiency η 98.1 % European efficiency η 97.7 % euro STP10-17TL-IEN102611 Installation Guide...
SMA Solar Technology AG Technical Data 14.4 Sunny Tripower 17000TL Maximum DC power at cos ϕ = 1 17,410 W DC max Maximum DC voltage * 1,000 V DC max MPP voltage range 400 V … 800 V DC nominal voltage 600 V DC nom...
Page 112
Technical Data SMA Solar Technology AG Test voltage 2.55 kV (DC, 1 s routine testing) 4.25 kV (DC, 5 s type testing) Surge testing voltage 10 kV Internal consumption in night mode < 1 W Mechanical data Width x height x depth 665 mm x 690 mm x 265 mm Weight 65 kg...
Page 113
SMA Solar Technology AG Technical Data General data Electronics protection rating * IP65 Connection area protection rating * IP54 Protection class Noise emission (typical) No data * according to DIN EN 60529 Protective Equipment All-pole DC disconnection unit Electronic Solar Switch,...
Page 114
Technical Data SMA Solar Technology AG Efficiency Peak efficiency η 98.1 % European efficiency η 97.7 % euro STP10-17TL-IEN102611 Installation Guide...
SMA Solar Technology AG Accessories 15 Accessories In the following overview you will find the corresponding accessories and spare parts for your product. If required, you can order these from SMA Solar Technology AG or your dealer. Name Brief description SMA order number...
Contact SMA Solar Technology AG 16 Contact If you have technical problems concerning our products, contact the SMA Serviceline. We require the following information in order to provide you with the necessary assistance: • Inverter type • Serial number of the Sunny Tripower •...
The use of supplied software produced by SMA Solar Technology AG is subject to the following conditions: • SMA Solar Technology AG rejects any liability for direct or indirect damages arising from the use of software developed by SMA Solar Technology AG. This also applies to the provision or non-provision of support activities.