Key S2: Source Key S1: Menu Error LED Key S4: Select Key S3: Info LCD display Figure 1: overview of the Mastervolt Sunmaster XS 4300/ 3200/2000. CONTENTS: v 1.1 November 2008 GENERAL INFORMATION.............................. 4 Product description............................. 4 Use of this manual.............................. 4 Validity of this manual ............................
The warranty is limited to the costs of repair and/or photovoltaic modules. replacement of the product by Mastervolt only. Costs for Depending on the application and in order to meet the installation labour or shipping of the defective parts are not local applicable regulations, the Sunmaster can be covered by this warranty.
Use of the Sunmaster other than as mentioned under § 2.2 is not considered to be consistent with the intended purpose. Mastervolt is not liable for any damage resulting from the above. EN / Sunmaster XS4300-3200-2000 / November 2008...
For example international standard IEC60364-7-712 prescribes a DC switch in solar electric installations in buildings. For this reason Mastervolt offers several models of the Sunmaster with integrated DC-switch. See chapter 3.2 to check if your Sunmaster is equipped with such a DC-switch.
• cabling and/or the terminal connections. RS485 communication cables. • Follow steps installation instructions in order of succession as described. • The DC switch, if installed, must stay in OFF-position during entire installation. November 2008 / Sunmaster XS4300-3200-2000 / EN...
Place the Sunmaster over the mounting bracket and then move it downwards until it is locked by the mounting bracket. Figure 12 Figure 15 EN / Sunmaster XS4300-3200-2000 / November 2008...
If connection has been made correctly and solar irradiation is sufficient, the Sunmaster will switch on automatically. Figure 17 This may take a few seconds. At first commissioning the country code must be selected. See section 4.3.2. November 2008 / Sunmaster XS4300-3200-2000 / EN...
If the correct country code is shown, press S2 to Disconnect the MultiContact connectors from the select Sunmaster. Remove the bottom plate of the Sunmaster and disconnect the AC wiring. Now the Sunmaster can be demounted in a safe way. EN / Sunmaster XS4300-3200-2000 / November 2008...
This is a normal effect which has a positive contribution to the efficiency and lifetime of the Sunmaster. LCD Display S1: Menu S2: Source Error LED S3: Info S4: Select Figure 23: operation of the LCD-display November 2008 / Sunmaster XS4300-3200-2000 / EN...
AC grid PV-string AC grid frequency Ω AC grid impedance* °C Internal temperature of Internal temperature of the inverter the inverter Energy generated today * ENS-models only (see chapter 3.2), else 0.00 is shown. EN / Sunmaster XS4300-3200-2000 / November 2008...
One day back in the past. displayed. Press and hold Scrolling days forward. This value represents the total operating hours of the selected input. Examples: Shows today’s data Shows yesterday’s data Shows data from one week ago November 2008 / Sunmaster XS4300-3200-2000 / EN...
Display switches between the firmware of Sunmaster. Never use any liquids, acids and/or scourers. the inverter (“XS”) and the display (“DS”). ►ERROR In case of a system failure, the cause of the failure is displayed. See section 5.3.5. EN / Sunmaster XS4300-3200-2000 / November 2008...
Sunmaster replacement of the Sunmaster. Fast blinking EF I2C FAIL Fast blinking ENS FAIL Fast blinking CB I2C FAIL Fast blinking HW VAC FAC Fast blinking HW RELAY Fast blinking HW ERROR 1-9 November 2008 / Sunmaster XS4300-3200-2000 / EN...
PG-13.5 gland and screw PG-13.5 gland and screw PG-13.5 gland and screw terminals 2.5 - 4 mm2 terminals 2.5 - 4 mm2 terminals 2.5 - 4 mm2 * Depending on country settings, see section 4.3.2 EN / Sunmaster XS4300-3200-2000 / November 2008...
Page 20
2 galvanic isolated RS485 QS databus connections External communication 2 galvanic isolated MasterBus connections Monitoring (optional) QS Data Control Basic (PC Software). Free download from www.mastervolt.com Monitoring (optional) QS PC-Link (connect the QS-databus to the PC) Monitoring (optional) Data Control Premium II: datalogger for up to 6 inverters with local, remote or internet...
SPECIFICATIONS OUTLINE DRAWINGS 356 [14.0] 142 [5.59] 356 [14,00] 142 [5,61] Figure 30: Dimensions in mm (inch) of the Sunmaster XS4300, XS3200, XS2000 EN / Sunmaster XS4300-3200-2000 / November 2008...
Delivery includes: 100 meter modular cable, 100 pcs. modular jacks and crimping tool. Mastervolt can offer a wide range of products for both grid connected and independent autonomous electrical installations, See our website www.mastervolt.com for an extensive overview of all our products.
Automatically after test operation. The test accuracy is better than 1V/ 0.1Hz if ACTUAL DAY TOTAL SYSTEM grid voltage and frequency are stable. Menu FL-test Blinking ASTERVOLT ASTERVOLT Automatically after test Figure 31 Actual EN / Sunmaster XS4300-3200-2000 / November 2008...
Page 24
ASTERVOLT ASTERVOLT Calculation by hand: UT = UG – (TIME * 11.5). FH-test Example: if UG = 230V and TIME = 4.00 s, Figure 33 UT = 230 - (4.00*11.5) = 184V. November 2008 / Sunmaster XS4300-3200-2000 / EN...
Page 25
Calculation by hand: FT = FG – (TIME * 0.05). Actual Example: if FG = 50.00 Hz and TIME = 6.00 s, Figure 35 the result is 50.00 - (6.00*0.05) = 49.70 Hz. EN / Sunmaster XS4300-3200-2000 / November 2008...
EN 61000-3-2, Dips, variations, flicker EN 61000-4-11 and -3-3 Immunity EN 55024 EN 61000-4-2 and -3 EN 61000-4-4, -4-5 and -4-6 LV directive 2006/95/EC Electrical safety EN 60950-1 Amsterdam, P.F. Kenninck, General Manager MASTERVOLT EN / Sunmaster XS4300-3200-2000 / November 2008...
Page 28
Snijdersbergweg 93, 1105 AN Amsterdam, The Netherlands Tel : + 31-20-3422100 Fax : + 31-20-6971006 Email : info@mastervolt.com...