DeDietrich C 310 ECO User Manual page 9

Gas fired condensing boiler
Table of Contents

Advertisement

Indicative CO
value
2
Adjust to
Set to
Indicative O
value
2
Adjust to
Set to
P C310-280 (Pa)
P C310-350
P C310-430
P C310-500
P C310-570
Set the parameter to a value greater than or equal to 8, depending on
the options connected.
Then set the gas seal control pressure switch to a trigger pressure
equivalent to 50% of the admission pressure. Do not forget that the
admission pressure measured does not affect the closing pressure
(higher).
19. Press the Reset key to return the boiler to "user level"
20. Heat the installation to around 80°C and then stop the boiler
21. Bleed the heating installation and Checking the hydraulic
pressure
22. The boiler is now operational
23. Set the boiler regulation to the desired values
24. Switch the boiler on and fill in the label "Set to"
Each individual boiler is delivered with the following fixed
factory settings:
Burner regulation
Flow temperature
02/10/07 - 300015183-001-A
Natural gas H/E
(G20)
High speed (100%)
9,0%
±0,5%
9,0 ± 0,15%
4,8%
±0,5%
4,8 ± 0,25%
1300 ± 100
1020 ± 100
900 ± 10
1350 ± 100
1650 ± 100
- Modulating, depending on the
outlet temperature
- 90°C
C 310 ECO - C 610 ECO
Table of CO
- O
values
2
2
Low speed (±20%)
High speed (100%)
9,0%
±0,5%
9,0 ± 0,15%
4,8%
±0,5%
4,8 ± 0,25%
60 ± 10
42 ± 10
50 ± 10
65 ± 10
85 ± 10
Natural gas L/LL
(G25)
Low speed (±20%)
9,0%
±0,5%
±0,5%
9,0 ± 0,15%
9,0 ± 0,15%
4,8%
±0,5%
±0,5%
4,8 ± 0,25%
4,8 ± 0,25%
1150 ± 100
45 ± 10
840 ± 100
32 ± 10
750 ± 100
40 ± 10
1200 ± 100
50 ± 10
1500 ± 100
70 ± 10
9,0%
4,8%
9