R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Model Nomenclature: General Overview NOTE: Above model nomenclature is a general reference.
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Horizontal Installation Mounting Horizontal Units Horizontal Unit Location...
Page 6
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Horizontal Installation Figure 3: Typical Horizontal Unit Installation Air Coil - To obtain maximum performance, the air coil should...
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Field Conversion of Air Discharge Overview - Horizontal units can be fi...
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Horizontal Installation Condensate Piping Figure 6: Horizontal Condensate Connection...
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Vertical Installation Figure 7: Vertical Unit Mounting Vertical Unit Location...
Page 10
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Vertical Installation Sound Attenuation for Vertical Units - Sound attenuation Condensate Piping for Vertical Units - Vertical units utilize...
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Water Connection Installation The female locking ring is threaded onto the pipe threads External Flow Controller Mounting...
Page 12
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Ground-Loop Heat Pump Applications antifreeze solution is used in most areas to prevent freezing.
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Ground-Loop Heat Pump Applications Open Loop - Ground Water Systems Table 2: Antifreeze Percentages by Volume...
Page 14
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Ground-Water Heat Pump Applications valve or water control valve on the discharge line.
Rev.: 3/22/2012 The ClimateMaster Water Quality Table provides water quality requirements for ClimateMaster coaxial heat exchangers. When water properties are outside of those requirements, an external secondary heat exchanger must be used to isolate the heat pump heat exchanger from the unsuitable water. Failure to do so will void the warranty for the coaxial heat exchanger.
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 7 A u g . , 2 0 1 1 B Hot Water Generator The HWG (Hot Water Generator) or desuperheater option Electric water heaters are recommended.
Page 17
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Hot Water Generator ANTI-SCALD Installation...
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Hot Water Generator Warning! The HWG pump Is fully wired from the 5.
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Electrical - Line Voltage WARNING! CAUTION!
Page 20
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Electrical - Line Voltage Figure 16: TT/TS Single Phase Line Voltage WARNING!
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Electrical - Low Voltage Wiring Thermostat Connections Low Water Temperature Cutout Selection...
Therefore, only relay or triac based thermostats should be used. Figure 23: Two-Stage Piping Two-stage Units Solenoid Tranquility 27™ (TT) two-stage units should be designed with Flow Valve Regulator two parallel valves for ground water applications to limit water use during rst stage operation.
300 psig and a cut-in pressure of 250 psig. This pressure switch can 24Vac Hot be ordered from ClimateMaster with a 1/4” internal are 24Vac Common connection as part number 39B0005N02. Fault LED...
1. Heating Settings: The heating setting determines the heating ® CFM for Tranquility 27 (TT) and Tranquility 20 (TS) units. Tap 1 is the lowest CFM setting, while tap 4 is the highest CFM setting.
Page 25
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B ECM Blower Control Table 5: ECM Board Tap Settings Cooling settings: TT, TS Units...
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B CXM Controls Air coil low temperature (FP2): The FP2 thermistor temperature Safety Features –...
Page 31
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B CXM Controls CXM Control Start-up Operation The control will not operate until all inputs and safety controls...
Page 32
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B CXM Controls Safety Features –...
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Unit Commissioning And Operating Conditions Operating Limits Environment –...
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Unit Start-Up and Operating Conditions operate in the proper sequence.
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Unit Operating Conditions Table 9a: TT Coax Water Pressure Drop Table 9b: TS Coax Water Pressure Drop...
Page 37
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Unit Operating Conditions Table 11: TT Series Typical Unit Operating Pressures and Temperatures TT026...
Page 38
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Unit Operating Conditions Table 11: TT Series Typical Unit Operating Pressures and Temperatures: Continued TT064...
Page 39
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Unit Operating Conditions Table 12: TS Series Typical Unit Operating Pressures and Temperatures: Continued Full Load Cooling - without HWG active...
Page 40
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Unit Operating Conditions Table 12: TS Series Typical Unit Operating Pressures and Temperatures: Continued Full Load Cooling - without HWG active...
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Unit Operating Conditions Table 12: TS Series Typical Unit Operating Pressures and Temperatures: Continued Full Load Cooling - without HWG active...
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Preventive Maintenance Water Coil Maintenance Condensate Drain...
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B CXM Process Flow Chart WARNING! WARNING! HAZARDOUS VOLTAGE! DISCONNECT...
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Performance Troubleshooting Performance Troubleshooting Htg Clg Possible Cause...
R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A R e v. : 9 M a r c h , 2 0 1 1 B Troubleshooting Form Refrigerant Circuit Diagram Look up pressure drop in...
97B0045N03 ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specifi...
Need help?
Do you have a question about the Tranquility 27 and is the answer not in the manual?
Questions and answers