Vogelzang International BX42E Owner's Manual

Vogelzang International BX42E Owner's Manual

Hide thumbs Also See for BX42E:

Advertisement

DELUXE BOXWOOD STOVE
Owners Manual
Model BX42E
(save this manual for future reference)
NOTE: THIS STOVE IS
READ ALL INSTRUCTIONS CAREFULLY
NOT A UL LISTED STOVE.
BEFORE INSTALLING OR OPERATING
THIS STOVE. FAILURE TO FOLLOW INSTRUC-
TIONS MAY RESULT IN PROPERTY DAMAGE,
NOTE: IT IS RECOMMENDED INSTALLATION
BODILY INJURY, OR EVEN DEATH.
BE COMPLETED BY A QUALIFIED HEATING
EQUIPMENT INSTALLER!
REFER TO MARKINGS ON STOVE LABELS FOR
DO NOT INSTALL IN A MOBILE HOME.
ADDITIONAL INFORMATION.
SAFETY NOTICE: IF THIS STOVE IS NOT PROPERLY INSTALLED, A HOUSE/BUILDING FIRE MAY
RESULT. FOR YOUR SAFETY, CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT PERMITS,
RESTRICTIONS, AND INSTALLATION REQUIREMENTS FOR YOUR AREA.
www.NorthlineExpress.com
NorthlineExpress.com
Call us at 1-866-667-8454
Page 1
VGZ-005 / 20120202.0
BX42E-SN /

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BX42E and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Vogelzang International BX42E

  • Page 1 DELUXE BOXWOOD STOVE Owners Manual Model BX42E (save this manual for future reference) NOTE: THIS STOVE IS READ ALL INSTRUCTIONS CAREFULLY NOT A UL LISTED STOVE. BEFORE INSTALLING OR OPERATING THIS STOVE. FAILURE TO FOLLOW INSTRUC- TIONS MAY RESULT IN PROPERTY DAMAGE, NOTE: IT IS RECOMMENDED INSTALLATION BODILY INJURY, OR EVEN DEATH.
  • Page 2: Safety Precautions

    This is not safe. Use approved masonry or an Persons with lung conditions or owners of sus- Underwriters Laboratories Listed UL 103 HT continued on next page www.NorthlineExpress.com NorthlineExpress.com Call us at 1-866-667-8454 Page 2 / BX42E-SN VGZ-005 / 20120202.0...
  • Page 3 INSTALLED IN A HALLWAY OR NEAR A STAIR- CASE, as it may block egress in the event of a fire. 31. DO NOT INSTALL IN A SLEEPING ROOM. www.NorthlineExpress.com NorthlineExpress.com Call us at 1-866-667-8454 Page 3 VGZ-005 / 20120202.0 BX42E-SN /...
  • Page 4: Table Of Contents

    Chimney Connection Systems & Clearances ..........17 NOTE: A PROFESSIONAL, LICENSED HEAT- ING AND COOLING CONTRACTOR MUST BE CONSULTED IF YOU HAVE QUESTIONS REGARDING THE INSTALLATION OF THIS SOLID FUEL BURNING APPLIANCE. www.NorthlineExpress.com NorthlineExpress.com Call us at 1-866-667-8454 Page 4 / BX42E-SN VGZ-005 / 20120202.0...
  • Page 5: Tools And Materials Required For Installation

    ASSEMBLY INSTRUCTIONS NOTICE: Vogelzang International Corp. grants no warranty, stated or implied, for the installation or maintenance of your wood stove and assumes no responsibility of any incidental or consequential damages. tools required materials required (NOTE: The following items are NOT included with your stove) Safety Glasses 1/8”...
  • Page 6: Locating The Stove

    PER NFPA 211 18" FLOOR PROTECTOR 74" 36" SIDEWALL 18" COMBUSTIBLE CONSTRUCTION PER NFPA 211 18" 18" (TOP VIEW) 52" Figure 6 – Minimum Clearance Dimensions from Combustible Surfaces www.NorthlineExpress.com NorthlineExpress.com Call us at 1-866-667-8454 Page 6 / BX42E-SN VGZ-005 / 20120202.0...
  • Page 7: Minimum Clearances

    Pipe Connector to Ceiling ..18 inches CAUTION: KEEP FURNISHINGS AND OTHER Figure 8 – Top View COMBUSTIBLE MATERIALS AWAY FORM THE Minimum Corner Clearances from STOVE. Combustible Surfaces www.NorthlineExpress.com NorthlineExpress.com Call us at 1-866-667-8454 Page 7 VGZ-005 / 20120202.0 BX42E-SN /...
  • Page 8: Connector Pipe Installation

    This will allow any condensation COULD RESULT. in the flue to run back into the firebox. CORRECT WRONG WRONG Figure 9 – Stovepipe/Flue Connections www.NorthlineExpress.com NorthlineExpress.com Call us at 1-866-667-8454 Page 8 / BX42E-SN VGZ-005 / 20120202.0...
  • Page 9: Chimney Connections/Draft

    5. C o n t a c t y o u r l o c a l b u i l d i n g a u t h o r i t y for approved methods of installation and any necessary permits and/or inspections. Figure 11 - Chimney Construction Through Attic Space www.NorthlineExpress.com NorthlineExpress.com Call us at 1-866-667-8454 Page 9 VGZ-005 / 20120202.0 BX42E-SN /...
  • Page 10 Many prefabricated fireplaces are of the “zero- Figure 13 - Chimney Connection to Firebox clearance fireplace” category. These consist of mul- Through Masonry Wall tilayered metal construction. They are designed with www.NorthlineExpress.com NorthlineExpress.com Call us at 1-866-667-8454 Page 10 / BX42E-SN VGZ-005 / 20120202.0...
  • Page 11: Fireplace Installation

    Positioning the center of the stove pipe entry into the chimney 24” below the ceiling should insure proper clearance for a 6” stovepipe. Figure 14 - Fireplace Conversion www.NorthlineExpress.com NorthlineExpress.com Call us at 1-866-667-8454 Page 11 VGZ-005 / 20120202.0 BX42E-SN /...
  • Page 12: Operating Instructions

    Do not over- VICINITY OF THE STOVE — WHETHER IN USE fire the stove. OR IN STORAGE. continued on next page www.NorthlineExpress.com NorthlineExpress.com Call us at 1-866-667-8454 Page 12 / BX42E-SN VGZ-005 / 20120202.0...
  • Page 13: Adding Fuel

    TRASH OR FLAMMABLE LIQUIDS MAY CAUSE ashes on top of the fire. OVER FIRING. continued on next page www.NorthlineExpress.com NorthlineExpress.com Call us at 1-866-667-8454 Page 13 VGZ-005 / 20120202.0 BX42E-SN /...
  • Page 14: Stove Joints

    Following are some possible causes for improper draft. 1. The connector stovepipe may be pushed into the chimney too far, stopping the draft. www.NorthlineExpress.com NorthlineExpress.com Call us at 1-866-667-8454 Page 14 / BX42E-SN VGZ-005 / 20120202.0...
  • Page 15: Parts - Deluxe Boxwood

    ORDERING PARTS - BX42E BOXWOOD STOVE When ordering missing or replacement parts, always give the Model Number of the stove, Part Number, and Part Description. Use the illustrations and part lists provided to identify parts. Contact us at 616-396-1911 to order parts.
  • Page 16: Floor Protector Calculations

    Step 4: Compare Rsystem to Rspecs Rsystem = 1.231 is larger than Rspecs of 0.893. System R-value exceeds the required specifications and therefore is an acceptable alternative. www.NorthlineExpress.com NorthlineExpress.com Call us at 1-866-667-8454 Page 16 / BX42E-SN VGZ-005 / 20120202.0...
  • Page 17: Chimney Connection Systems & Clearances

    24 gauge thickness. Fasteners used to secure chimney section shall not penetrate chimney flue liner. www.NorthlineExpress.com NorthlineExpress.com Call us at 1-866-667-8454 Page 17 VGZ-005 / 20120202.0 BX42E-SN /...