Wiring; Terminal Connection Diagram; Main Circuit - Mitsubishi Electric FR-A700 Installation Manuallines

700 series fr-a740-00023 to 12120-ec
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Terminal connection diagram

3 WIRING

3.1 Terminal connection diagram
Source logic
*1. DC reactor (FR-HEL)
Be sure to connect the DC reactor
Main circuit terminal
supplied with the 01800 or more.
Control circuit terminal
When a DC reactor is connected to
the 01160 or less, remove the jumper
across P1-P/+.
Three-phase AC
power supply
*2. To supply power to the
control circuit separately,
remove the jumper across
R1/L11 and S1/L21.
Control input signals (No voltage input allowed)
Terminal functions vary with
the input terminal
assignment (Pr. 178 to Pr. 189)
(Refer to the Instruction
Manual)
holding selection
Multi-speed
selection
*3. JOG terminal can be used
as pulse train input terminal.
Use Pr.291 to select
JOG/pulse.
Second function selection
*4. AU terminal can be
used as PTC input
terminal.
Terminal 4 input selection
(Current input selection)
Selection of automatic restart
after instantaneous
Contact input common (Sink)
(Common for external power supply transistor)
24VDC power supply
Contact input common
(Common for external power supply transistor)
Frequency setting signal (Analog)
Frequency setting
potentiometer
1/2W1k Ω
*6
* 5. Terminal input specifications
can be changed by analog
input specifications
Auxiliary
switchover (Pr. 73, Pr. 267).
Set the voltage/current input
switch in the OFF position to
Terminal
select voltage input (0 to 5V/0
to10V) and ON to select
(Current
current input (4 to 20mA).
(Refer to the Instruction
Manual)
*6 . It is recommended to use 2W1kΩ
when the frequency setting signal
is changed frequently.
CAUTION
·
To prevent a malfunction due to noise, keep the signal cables more than 10cm away from the power cables.
·
After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
·
Set the voltage/current input switch correctly. Different setting may cause a fault, failure or malfunction.
3
Earth
(Ground)
MC
MCCB
R/L1
S/L2
T/L3
R1/L11
Jumper
S1/L21
*2
Earth
(Ground)
Forward
rotation
start
Reverse
rotation
start
Start self-
High speed
Middle
speed
Low speed
Jog mode
MRS
Output stop
Reset
power failure
10E(+10V)
10(+5V)
3
2
1
(+)
1
input
(-)
4 input
(+)
(-)
input)
Connector
for plug-in option
connection
Brake unit
*1
(Option)
R
*8
Jumper
Jumper
Jumper
P1
P/+
PX
PR
R
ON
EMC filter
ON/OFF
connecter
OFF

Main circuit

Control circuit
STF
STR
STOP
RH
RM
RL
JOG
*3
RT
RES
*4
AU
AU
PTC
CS
SD
PC
PU
connector
*5
Voltage/current
input switch
4 2
ON
USB
OFF
connector
0 to 5VDC
(Initial value)
2
0 to 10VDC
selected
*5
0 to 20mADC
5
(Analog common)
0 to ± 10VDC
(Initial value)
selected
0 to ± 5VDC
*5
4 to 20mADC
(Initial value)
4
0 to 5VDC
*5
selected
0 to 10VDC
Option connector 1
Option connector 2
Option connector 3
Terminating
resistor
*7. A CN8 connector is provided with the
02160 or more.
*8. Brake resistor (FR-ABR)
Remove the jumper across terminal PR-PX
when connecting a brake resistor.
(00023 to 00250)
CN8
N/-
Terminal PR is provided for the 00023 to 00620.
*7
Install a thermal relay to prevent an overheat
and burnout of the brake resistor.
(Refer to the Instruction Manual)
U
V
W
C1
Terminal functions
B1
Relay output 1
vary with the output
(Alarm output)
terminal assignment
A1
(Pr. 195, Pr. 196)
(Refer to the
C2
Instruction Manual)
B2
Relay output 2
A2
Open collector output
RUN
Running
Terminal functions
SU
vary with the output
Up to frequency
terminal assignment
IPF
(Pr. 190 to Pr. 194)
Instantaneous
power failure
(Refer to the
OL
Instruction Manual)
Overload
FU
Frequency detection
SE
Open collector output common
Sink / source common
* 10. It is not necessary
when calibrating the
indicator from the
operation panel.
(+)
CA
Analog current output
(0 to 20mADC)
(-)
(+)
AM
Analog signal output
(0 to 10VDC)
5
(-)
RS-485 terminals
TXD+
Data transmission
TXD-
RXD+
Data reception
RXD-
SG
GND
VCC
(Permissible load
5V
current 100mA)
Motor
IM
Earth (Ground)
Relay output