+01E_073002_STime_EXS21TLE.fm Page 1 Thuesday, June 19, 2008 4:50 PM
INSTALLATION INSTRUCTIONS
INFORMATION FOR THE PERSON IN CHARGE OF INSTALLATION (ELECTRICAL) WORK AND SERVICING
Safety Precautions
● Read these Safety Precautions before beginning installation or electrical work, and
perform the work only in the correct manner.
● Precautions in this manual are given in the form of "Warnings" or "Cautions." Both types
of precautions contain important information related to your safety, the safety of users,
and the correct operation, installation, or maintenance of the air conditioning system. Be
sure to carefully observe all relevant precautions.
This symbol refers to a hazard or unsafe practice which can result
in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result
CAUTION
in personal injury or product or property damage.
When installation work is completed, perform a test run and check that no trouble occurs.
Also be sure to explain the methods for using the product to the customer, based on the
contents of the Operation Manual. In addition, request that the customer keep and
conveniently store the "Information for the Person in Charge of Installation (Electrical) Work
and Servicing" together with the Operation Manual.
● Request installation and electrical work only from the dealer or a qualified air
conditioning specialist.
Attempting to carry out installation work on your own, and doing so incorrectly, may
result in electrical shock, fire, or other hazards.
● Installation procedures must be performed correctly, carefully following the instructions
in this document.
Failure to do so may result in electrical shock, fire, or other hazards.
● Electrical work must be performed by a qualified electrician. It must be performed in
accordance with technical standards related to electrical equipment, interior wiring
regulations, local codes, and the contents of these instructions. Be sure to use a
dedicated power supply circuit.
Insufficient power circuit capacity or improper electrical work may result in electrical
shock or fire.
● Use only the designated cables for wiring, and connect them securely. Fasten cables so
that no external force is applied to the terminal connections.
Insufficient connections or cable fastening may result in heat generation, fire, or other
hazards.
CAUTION
● Depending on the installation location, it may be necessary to install an earth leakage
breaker. Failure to do so may result in electrical shock or fire.
● Do not install in kitchens, workshops, or other locations where there is oil mist in the air.
● Do not install next to windows or in other locations exposed to direct sunlight or in direct
contact with outside air.
● Do not install near an elevator, automatic door, industrial sewing machine, or other
devices that can be expected to produce electrical noise.
Accessories for Schedule Timer
No.
Supplied parts
No.
Supplied parts
Q'ty
CN61 (T10) power wire
4
Spacers
1
1
Wire joints
5
(with current fuse) *1
1.2m length of connecting
wire *2
Operation
2
1
6
manual
Installation
7
manual
Screws
3
2
M4 × 25
*1 If the fuse blows as a result of a wiring short-circuit, miswiring, or overcurrent, replace it with a
125 V, 0.1 A fuse (Fig. 1).
*2 Use this connecting wire when using with weekly timer mode. Connect the provided
connecting wire (4 cores) to the power terminal (4P connector) of the schedule timer unit.
(Fig. 5)
Fig. 1
Indoor unit control PCB CN61
(T10) connector (6P orange)
1. Power wire
Fuse
Installing the Schedule Timer
<Note 1> Avoid twisting the inter-unit control wiring or the input/output wiring together with
power or other wiring, and avoid running them in the same metal conduit. Doing
so can cause malfunction.
<Note 2> Install the schedule timer at a location away from any sources of electrical noise.
<Note 3> Install a noise filter or take other appropriate action if electrical noise affects the
power supply circuit of the unit.
Model TCB-EXS21TLE
Fig. 2
Switch box for 1 switch (no cover)
or switch box for 2 switches (no cover)
M4 x 25 small
Spacer
flat-head screws (2)
Under-case
Schedule
(back case)
timer unit
Decorative
cover (panel)
(1) Open the panel on the schedule timer unit. Insert a standard (flathead) screwdriver or
similar tool into the notches on the bottom of the schedule timer unit to open and
remove the back case.
(2) Use the 2 supplied M4 small screws and install the schedule timer back case onto the
switch box. Before installing, use a screwdriver or similar tool to press on and open the
screw holes that correspond to the JIS box that is used.
When fastening the case, use spacers and do not tighten the screws too much. If the
schedule timer does not fit tightly against the wall, cut the spacers as required to make
adjustments.
(3) Connect the supplied power wire (2-core) and inter-unit control wire (3-core) to the
schedule timer unit.
("Wiring for Weekly Timer mode")
(4) Align the schedule timer unit with the tabs on the back case and press to install it.
Installation of connected schedule timers
● When installing schedule timers (remote controller switches, system controllers, etc.)
onto the wall, use the method shown in Figs. 3 and 4.
Fig. 3
More than
More than 125 mm
95 mm
(From wall)
(For connected
installation)
Remote controller
wiring outlet
Switch box for 1
switch (no cover)
Fig. 4
More than
More than
95 mm
125 mm
(For connected
(From wall)
installation)
Q'ty
2
6
Remote controller
wiring outlet
2
Switch box for 2 switches
(no cover)
1
* For maintenance reasons, leave a gap of 25 mm or more between the remote controller switch
and schedule timer if they are arranged in parallel above/below each other.
This remote controller has two methods of usage with the weekly timer and the
schedule timer.
The wiring method and switch setting are different in each case.
Wiring for Weekly Timer mode
● Wiring Diagram (Be sure to use the provided wires for the connection wiring.)
Fig. 5
Power terminal
Timer terminal
Wired
Schedule
remote
timer
controller
Clamp filter
Connecting wire
(accessory)
● Location
The schedule timer and wired remote controller can be located on
either the right and left.
● System Diagram
Fig. 6
: Terminal board
: Connector
DC12V
Wired
Schedule
Indoor
remote
timer
unit
4 wires
controller
Wiring for the Schedule Timer mode
<Basic Wiring Diagram>
Fig. 7
64 system central remote controller or
ON-OFF controller
Wiring
specifications (1)
Refrigerant system 1
(S-MMS)
Refrigerant system 2
(SDI/DI)
P1
Indoor unit
(Header unit)
U3 U4
U1 U2
U1 U2
U3 U4
L1
Schedule timer *1
L3
L2
P1
U1
U2
U1 U2
Indoor
Indoor
Indoor
unit
unit
Remote
Remote
Remote
controller
controller
controller
Schedule
timer *2
Wiring specifications (2)
Wiring specifications (2)
*1 In the case the schedule timer is connected to the 64 system central remote controller or
ON-OFF controller
*2 In the case the schedule timer is connected to the indoor unit for S-MMS
*3 In the case the schedule timer is connected to the TCC-LINK adapter
Wiring
Max. Length
P1: Power wire for schedule timer
100m
L1: Central control system wiring
Less than 1000m
L1+L2+
L2,L3,L4: Indoor/Outdoor communication
L3+L4
line
Less than 2000m
P1, L1, L2, L3 and L4 have no polarity.
<Note> ● This schedule timer is device connected to TCC-LINK.
● The maximum number of schedule timer units that can be connected is 8. (A
maximum of 10 schedule timer units and other central control devices can be
connected.)
● In the case of SDI/DI, an extra TCC-LINK adapter may be required.
● Wiring
● The schedule timer wiring can be connected by the following two methods. Select one of
these connection methods according to the actual installation location. When wiring,
extend the lengths of the wires using wire joints (accessory) and extension wires (field
supply).
<Note> ● When installing multiple schedule timers, avoid the use of
communication line.
● Connection diagram (Be sure to use the provided wires as the power
wiring.)
Wiring specifications (1)
If a 64 system central remote controller (or ON-OFF controller) is installed (power is
supplied from the 64 system central remote controller):
Fig. 8
Inter-unit control wiring
Connecting wire (accessory)
U1
U2
Field supply
Wire joint
(Not used)
64 system central remote controller
(Back side)
● Wiring procedures
Connect the provided connecting wire to the power terminal (4P
connector) of the schedule timer.
The terminal attached to the clamp filter must be connected to the
schedule timer.
● The power wiring and communication wiring has no polarity.
Outdoor
unit
Wiring specifications (2)
If a 64 system central remote controller (or ON-OFF controller) is not installed (power is
supplied from the indoor unit):
<Note>
(1) The only functions of the schedule timer are indoor unit ON/OFF and remote
controller enable/disable operations.
(2) It is required that during installation, a 64 system central remote controller or wired
remote controller be installed next to the schedule timer so that operation mode
and other information can be checked.
(3) If the 64 system central remote controller or other central control device is not
present, the schedule timer cannot be used in combination with a system that does
not utilize remote controllers including high wall (KRT series) systems.
Refrigerant system 3
(S-MMS)
Fig. 9
Outdoor unit
Indoor unit control PCB
(Header unit)
Outdoor unit
CN61(T10)
U1 U2
U3 U4
1. Supplied parts
TCC-LINK
U3
U4
(for SDI/DI)
adapter
U1
U2
(for S-MMS)
L4
U3 U4
P1
U1 U2
Indoor/Outdoor units communication line
Indoor
(for S-MMS)
unit
unit
Central control system wiring
(for SDI/DI)
Remote
controller
Schedule
timer *3
● The power wiring and communication wiring has no polarity.
● The length of the power wiring must be no more than 100 m.
The ground method of a shield wire (when using with the Schedule
Electric cable
Timer)
specifications
Fig. 10
2
0.5mm
Refrigerant system 1
(S-MMS)
2
MVVS 1.25mm
Shield wiring for
Outdoor unit
central control
2
(Header unit)
MVVS 2.0 mm
system (single-
point earth)
U1 U2
*4
Power
U3 U4
terminal
U1 U2
Schedule
64 System central
Timer *1
remote controller
or
ON-OFF controller
*4
U1 U2
Indoor
unit
Remote
Schedule
controller
Timer *2
*1 In the case the schedule timer is connected to the 64 system central remote controller or
ON-OFF controller
*2 In the case the schedule timer is connected to the indoor unit for S-MMS
*3 In the case the schedule timer is connected to the TCC-LINK adapter
<Grounding of the shield wires>
● The shield wires of the central control wiring should be connected at closed end, and
these should be single-point ground.
● The terminal end (*4) of the shield wires should be open and insulated.
Explanation to Customers
Clamp filter
● After work is completed, present the Operation Manual and Information for the Person in
Communication
Charge of Installation (Electrical) Work to the customer.
wiring
● Explain to the customer the methods for use of the system, as described in the
(blue + pink)
Operation Manual.
Blue
Blue
Pink
Memory Backup Switch
Power terminal
(4P connector)
After installation is completed, check that the backup switch on the reverse side of the
Communication
schedule timer PCB is turned to ON.
terminal (3P connector)
(The backup battery will retain the current time for up to 100 hours.)
Fig. 11
Schedule timer
Field supply
Communication
wiring
(blue + pink)
Power wiring
(black + white)
Blue
Blue
Pink
Black White
Wire joint
(Not used)
Power terminal
(4P connector)
Communication
terminal (3P connector)
Schedule timer
Refrigerant system 3
(S-MMS)
Refrigerant
system 2
Shield wiring for
Outdoor unit
(SDI/DI)
central control
(Header unit)
system (single-
point earth)
Outdoor
unit
U3 U4
U1 U2
U3 U4
Central control
system wiring
Indoor/Outdoor
units
communication line
TCC-LINK
adapter
*4
U3 U4
*4
U1 U2
U1 U2
Indoor
Indoor
Indoor
unit
unit
unit
Remote
Remote
Remote
Schedule
controller
controller
controller
Timer *2
Backup switch
OFF
ON
Backup battery
(E)

Advertisement

loading

Summary of Contents for Toshiba TCB-EXS21TLE

  • Page 1 +01E_073002_STime_EXS21TLE.fm Page 1 Thuesday, June 19, 2008 4:50 PM Wiring specifications (2) INSTALLATION INSTRUCTIONS Model TCB-EXS21TLE If a 64 system central remote controller (or ON-OFF controller) is not installed (power is supplied from the indoor unit): INFORMATION FOR THE PERSON IN CHARGE OF INSTALLATION (ELECTRICAL) WORK AND SERVICING <Note>...
  • Page 2 +01E_073002_STime_EXS21TLE.fm Page 2 Thuesday, June 19, 2008 4:50 PM When using with the Weekly-Timer, all switch settings except S41-1 must be OFF. ● Procedure for making fixed timer group settings (zone) ::: Continue from the previous section ::: Checking the Central Control Addresses and Operating the Units Remote Controller Enable Items Switch (1) (Substitute/Addition Selector) (1) First, use a 64 system central remote controller or the wired remote controllers to set About the Setting Switches...