Download Print this page

Philips Dynalite DUS704W Installation Manual page 3

Ceiling mount universal sensor

Advertisement

serial cable permanent connectors
Recommended Cable Colours
Green/White Pair
Orange/White Pair paralleled for +VE
Blue/White Pair
motion detection mounting location
• Fix the sensor to a firm section of wall
• Position the sensor so it is between 1.1 and 3.1 metres from the floor. Optimum height for the sensor is 2.1
metres.
• Slide the circuit board up or down so the marker on the housing matches up with the installed height on the
scale provided on the right hand side of the circuit board.
• Position the sensor so it is at least 2 metres away from electrical lighting such as neon and fluorescent
lights.
• Position the sensor as to avoid exposing it to direct sunlight and heating / cooling sources.
• Keep data cables away from electrical wiring.
• Select a location where persons are more likely to walk across the detection "fingers" rather than into them
(see diagram below).
• For programming instructions refer to Dynalite Tech Note – Setting up Motion Detection functions.
motion detection lens pattern
Top view
paralleled for GND
Blue for DATA
White for DATA-
connecting data cable
connect data cable in a "daisy chain"
Connect Data Cable in a "Daisy Chain"
DIMTEK 11 0
INSTALLATI ON DETAIL S
INPUT: 23 0 V 5 0-6 0Hz 10 A
O UTP UT: 1 x 230 V 10A
MOUNT VER TIC ALLY
AG AINST WALL
ENSUR E G OO D VENTILATI O N
FO LL O W INSTALLATION
INSTRUCTIO NS
Manuf a ctured by :
Uni t 6 -1 1 9 /1 3 3 McE VOY S t. A l e x andri a
NS W 2 0 1 5 A UST R A LIA
I SO LA TE F R O M
M A I N S S U PP LY B E FO R E
R E M O V I N G TH I S C O V ER
N O U S ER SE R V I C EA B LE PA R T S I N SI D E
SE R V I C E B Y Q U A LI F I E D PE R SO N N EL O N LY
Recommended Cable Types
Belden:
9503
Garland:
MCP3S
Hartland:
HCK603
M&M Cable:
B2003CS
Dynalite:
DYNET-STP-CABLE
Side view
DUS704W Installation Manual Rev G.doc
DIMTEK 11 0
INSTALLATI ON DETAIL S
INPUT: 23 0 V 5 0-6 0Hz 10 A
O UTP UT: 1 x 230 V 10A
MOUNT VER TIC ALLY
AG AINST WALL
ENSUR E G OO D VENTILATI O N
FO LL O W INSTALLATION
INSTRUCTIO NS
Manuf a ctured by :
Uni t 6 -1 1 9 /1 3 3 McE VOY S t. A l e x andri a
NS W 2 0 1 5 A UST R A LIA
I SO LA TE F R O M
R E M O V I N G TH I S C O V ER
M A I N S S U PP LY B E FO R E
N O U S ER SE R V I C EA B LE PA R T S I N SI D E
SE R V I C E B Y Q U A LI F I E D PE R SO N N EL O N LY
3

Advertisement

loading