Speed Taps—Adjust
Switch Bank: S3
DIP Switch Number
Adjust Tap
3
Normal*
Off
+10% Adjust
On
-10% Adjust
Off
Normal
On
*Indicates factory setting
Comfort Mode Profiles
The multispeed circulator blower also offers several custom On/
Off ramping profiles. These profiles may be used to enhance the
cooling performance and increase the comfort level. The ramping
profiles are selected using DIP switches 5 and 6. See the "Profile"
illustrations for DIP switch positions and their corresponding
taps. Verify CFM by noting the number displayed on the dual 7-
segment LED display.
Ramping Profile Tap
A*
B
C
D
*Indicates factory setting
Profile A
Provides a 1-minute Off delay at 100% of the cooling
demand airflow.
100% CFM
Off
Cooling
Demand
Profile B
Ramps up to 50% of the full cooling demand airflow for
30 seconds.
The motor then ramps to 100% of the required airflow.
Provides a 1-minute Off delay at 100% of the cooling
demand airflow.
100% CFM
Off
50% CFM
¹⁄₂ min
Cooling Demand
Profile C
Ramps up to 85% of the full cooling demand airflow for
approximately 7¹⁄₂ minutes.
The motor then ramps to 100% of the required airflow.
26
4
Off
Off
On
On
DIP Switch
Number
5
6
Off
Off
On
Off
Off
On
On
On
100% CFM
1 min
100% CFM
1 min
Provides a 1-minute Off delay at 100% of the cooling
demand airflow.
85% CFM
Off
7¹⁄₂ min
Profile D
Ramps up to 50% of the full cooling demand airflow for
30 seconds.
Then ramps to 85% of the full cooling demand airflow for
approximately 7¹⁄₂ minutes.
The motor then ramps to 100% of the required airflow.
Provides a 30-second Off delay at 50% of the cooling
demand airflow.
50% CFM
Off
30 sec
6. Select the heating speed from the heating speed chart in the
Specification Sheet for your model. The Adjust Taps setting
(already established by the cooling speed selection)
determines which set of speeds are available. The selected
speed must provide a temperature rise within the rise range
listed with the particular model.
Example: The WGFM290508V4C is set for 990 CFM on
cooling, the "ADJUST" is set to "+" (plus). The 4 heating
speeds available are "A Plus," "B Plus," "C Plus" and "D
Plus." "A Plus" has a rise of 38°F for both stages which is
within the 20ºF to 50°F rise range for the WGFM290508V4C.
This setting will keep electrical consumption to a minimum.
Set the "Heat" speed DIP switches to "A."
Switch Bank: S4
Heating Tap
A
B*
Off
C
D
*Indicates factory setting
7. Select the desired heating speed tap by positioning DIP
switches 7 and 8 appropriately. Verify CFM by noting the
number displayed on the dual 7-segment LED display.
In general, lower heating speeds will reduce electrical
consumption, lower operating sound levels of the blower and
increase the outlet air temperature delivered to the home. The
speeds available allow the blower performance to be optimized
Off
for the particular homeowner's needs.
Profiles
A
B*
C
D
*Indicates factory setting
100% CFM
Cooling Demand
100% CFM
85% CFM
7¹⁄₂ min
Cooling Demand
DIP Switch Number
7
Off
On
Off
On
Pre-Run
Short-Run
-
-
-
30 sec/50
-
7.5 min/85
30 sec/50
7.5 min/85
100% CFM
Off
1 min
50% CFM
Off
30 sec
8
Off
Off
On
On
Off -Delay
60 sec/100
60 sec/100
60 sec/100
30 sec/50