Troubleshooting for SkyAir Indoor Unit
5.9

Malfunction of Heat Exchanger Thermistor (R3T)

C5
Remote Control
Display
Applicable
FFQ-B, FHQ-BU
Models
Method of
Malfunction detection is carried out by temperature detected by heat exchanger sensor (R3T).
Malfunction
Detection
Malfunction
When the heat exchanger thermistor becomes disconnected or shorted while the unit is running.
Decision
Conditions
" Failure of the sensor itself
Supposed
" Broken or disconnected wire
Causes
" Failure of electronic circuitry (indoor unit PCB)
" Failure of connector contact
Troubleshooting
Check No.02
Refer to P.299
292
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Check contact of connector
Is it normal?
YES
Disconnect the heat exchange
sensor (R3T) from X17A on
the indoor unit PC board and
measure the resistance.
Is the
thermistor normal?
(See note)
YES
HSee
Check No. 02
for "Thermistor temperature and resistance characteristics".
NO
NO
SiENBE18-621
Connect correctly.
Heat exchanger
sensor replacement.
If contact is OK,
replace indoor unit
PCB.
(Q0417)