Table 9: Address Restrictions For The D7042, D7052, And D7053 - Bosch FPD-7024 Operation And Installation Manual

Fire alarm control panel
Hide thumbs Also See for FPD-7024:
Table of Contents

Advertisement

.
Table 8:
Compatible Devices (continued)
D7052 Mux Dual Input
Fire
D7053 Mux I&O Module
Fire
D7050/TH Mux Smoke
Detector
Table 9:
Address Restrictions for the D7042, D7052, and D7053
Install D7042 modules only at addresses:
9
17
73
81
137
145
201
209
Do not install D7052 and D7053 modules at these addresses
16
24
80
88
144
152
208
216
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
FPD-7024 | Operation and Installation Guide | 1.0
Connects to the multiplex bus of the FPD-7024 and provides two supervised input zones
for connecting conventional normally-open inputs. The D7052 draws operating power from
the FPD-7024.
Connects to the multiplex bus of the FPD-7024 and implements a supervised local loop,
and a Form C relay output. Up to 20 modules can be connected to each MUX bus. The
D7053 draws operating power from the FPD-7024.
The D7050/TH is a photo-electric smoke detector with a heat option. It connects to the
multiplex bus of the FPD-7024. The D7050 draws operating power from the
FPD-7024.
25
33
89
97
153
161
217
225
32
40
96
104
160
168
224
232
41
49
105
113
169
177
233
241
48
56
112
120
176
184
240
248
Overview
57
65
121
129
185
193
64
72
128
136
192
200
255
15

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FPD-7024 and is the answer not in the manual?

Questions and answers

Table of Contents

Save PDF