Contents 1. Precautions ............................1-1 Installing the air conditioner ......................1-2 Power supply and circuit breaker ....................1-3 During operation ..........................1-4 Disposing of the unit ........................1-5 Others ..............................2. Product Specifications ......................2-1 The Feature of Product ......................... 2-2 Product Specifications ........................
Page 3
Contents 9. Troubleshooting ..........................9-1 Items to be checked first ........................ 9-2 Checking and Testing operations ....................9-3 Fault Diagnosis by Symptom 9-12 ....................... 9-4 PCB Inspection 9-18 ........................... 10. Reference for Installation 10-1 ....................... 10-1 Selecting Area for Installation ....................
Do not place a cloth or other materials over it. G Remove the batteries if you don’t use the remote control for a long time. (If applicable) G Use the remote control within 7 meters from the indoor unit. (If applicable) Samsung Electronics...
G Young children or infirm persons should be always supervised when they use the air conditioner. G Max current is measured according to IEC standard for safety. G Current is measured according to ISO standard for energy efficiency. Samsung Electronics...
• Felt Structure : New felt has selected to reduce the noise coming out of the compressor. Double layered felt structure absorbs noise by two times and felt is also covering top of the compressor to reduce the noise even more. Samsung Electronics...
ø9.52x7.5 ø9.52x7.5 ø9.52x7.5 ø18x535 ø18x535 ø18x535 Drain Hose DxL(mm) Cross Flow Fan Cross Flow Fan Cross Flow Fan Type Blower Type Resin/steel Resin/steel Resin/steel Motor Rated Output Heat Exchanger 2ROW 10STEP 2ROW 14STEP 2ROW 14STEP Refrigerant Control Unit Samsung Electronics...
Page 8
Heating 1,099x315x217 WxHxD Outer Dimension inch 43.3x12.4x8.5 Weight Liquid mmxL(m) ø6.35x7.5 Refrigerant Pipe Size mmxL(m) ø12.7x7.5 ø18x600 Drain Hose DxL(mm) Cross Flow Fan Type Blower Type Resin /steel Motor Rated Output Heat Exchanger 2ROW 16STEP Refrigerant Control Unit Samsung Electronics...
Page 9
ø9.52x7.5 ø9.52x7.5 ø12.7x7.5 ø18x550 ø18x550 ø18x920 Drain Hose DxL(mm) Cross Flow Fan Cross Flow Fan Cross Flow Fan Type Blower Type Resin/steel Resin/steel Resin/steel Motor Rated Output Heat Exchanger 2ROW 14STEP 2ROW 14STEP 2ROW 16STEP Refrigerant Control Unit Samsung Electronics...
Page 10
Product Specifications(cont.) Model MH023FVEA MH020FVEA MH026FVEA Item INDOOR UNIT Type Wall-mounted Wall-mounted Cooling 2.00 2.60 Heating 2.20 2.90 Dehumidifying Cooling Perfor- Air Volume /min mance Heating Cooling Noise dB(A) Heating Power ø,V,Hz 1,220~240,50 1,220~240,50 Cooling Power Consumption Heating Power Cooling 0.18...
Page 11
Liquid mmxL(m) ø6.35x7.5 ø6.35x7.5 Refrigerant Pipe Size mmxL(m) ø9.52x7.5 ø12.7x7.5 ø18x550 ø18x550 Drain Hose DxL(mm) Cross Flow Fan Cross Flow Fan Type Blower Type Resin/steel Resin/steel Motor Rated Output Heat Exchanger 2ROW 10STEP 2ROW 15STEP Refrigerant Control Unit Samsung Electronics...
Page 12
Liquid mmxL(m) ø6.35x7.5 ø6.35x7.5 Refrigerant Pipe Size mmxL(m) ø9.52x7.5 ø9.52x7.5 Drain Hose DxL(mm) ø20x2,000 ø20x2,000 Cross Flow Fan Cross Flow Fan Type steel steel Blower Type Motor Rated Output Heat Exchanger 2ROW 14STEP 2ROW 14STEP Refrigerant Control Unit Samsung Electronics...
Page 13
15.2 15.2 Liquid mmxL(m) ø6.35x7.5 ø6.35x7.5 Refrigerant Pipe Size mmxL(m) ø9.52x7.5 ø9.52x7.5 Drain Hose DxL(mm) ø20x2,000 ø20x2,000 Turbo Fan Turbo Fan Type steel steel Blower Type Motor Rated Output Heat Exchanger 2ROW 20STEP 2ROW 20STEP Refrigerant Control Unit Samsung Electronics...
Page 14
Liquid mmxL(m) ø6.35x7.5 ø6.35x7.5 ø6.35x7.5 Refrigerant Pipe Size mmxL(m) ø9.52x7.5 ø9.52x7.5 ø12.7x7.5 Type Turbo Fan Turbo Fan Turbo Fan Blower Type steel steel steel Motor Rated Output Heat Exchanger 2ROW 10STEP 2ROW 10STEP 2ROW 10STEP Refrigerant Control Unit Samsung Electronics...
Page 15
ø6.35x7.5 ø6.35x7.5 ø6.35x7.5 Refrigerant Pipe Size mmxL(m) ø9.52x7.5 ø9.52x7.5 ø12.7x7.5 Type Sirocco fan Sirocco fan Sirocco fan Resin/steel Resin/steel Resin/steel Blower Type Motor Rated Output Heat Exchanger 2ROW 12STEP 2ROW 12STEP 3ROW 10STEP Refrigerant Control Unit 2-10 Samsung Electronics...
DB70-00534A (MH✳✳✳FNEA/MH✳✳VF1-✳✳, Installation Plate except MH052FNEA) (Plate-Hanger) DB70-00703A (MH052FNEA) Remote Control DB93-03170Z Indoor Batteries for Remote Control DB47-90024A Unit User Manual DB98-28925A Installation Manual DB98-28926A ✳ The design and shape can be changed according to the model. 2-22 Samsung Electronics...
Page 28
DB70-00819A (MH✳✳FBEA except Installation Plate MH052FBEA) (Plate-Hanger) DB70-00824A (MH052FBEA) Remote Control DB93-04700S Indoor Batteries for Remote Control DB47-90024A Unit User Manual DB98-29019A Installation Manual DB98-29015A ✳ The design and shape can be changed according to the model. Samsung Electronics 2-23...
Page 29
Remote Control DB93-04700S Batteries for Remote Control DB47-90024A Indoor Unit User Manual DB98-29039A Installation Manual DB98-29040A DB39-00943D C/W COMM2 Wired Remote Controller cables DB39-01047A Connect Wire ✳ The design and shape can be changed according to the model. 2-24 Samsung Electronics...
Page 30
Insulation cover drain DB62-01959A Installation Manual DB98-27682A Indoor Unit Flexible hose DB94-01258C (Ass'y drain hose joint) Insulation drain DB62-01960B Rubber DB63-00237A (Grommet Hanger) Insulation cover band DB72-00109J ✳ The design and shape can be changed according to the model. Samsung Electronics 2-25...
Page 32
Product Specifications Indoor Unit Accessories(cont.) I MH✳✳✳FMEA(cont.) Item Descriptions Code-No. Q'TY Remark Installation manual DB98-27682A Indoor Unit Safety net DB63-01372A ✳ The design and shape can be changed according to the model. Samsung Electronics 2-27...
Page 33
Product Specifications Indoor Unit Accessories(cont.) I MH✳✳✳FJEA Item Descriptions Code-No. Q'TY Remark User Manual DB98-29318A Installation Manual DB98-29317A Seal-Install Outlet DB62-05580V Indoor Seal-Pipe SVC DB62-05691C Unit Cable-Tie DB65-10088C Wireless Remote Control DB93-06280E Battery DB47-90024A 2-28 Samsung Electronics...
Page 34
DB97-03906A/B Insulation-Install Outlet DB72-00143D Insulation-Install Inlet DB72-00143E Indoor Unit Drain Hose Joint DB94-00758A Rubber DB63-00237A (Grommet Hanger) Insulation-Drain Out DB62-03439H Insulation-Out DB62-03439J Insulation-Drain In DB62-03440H ✳ The design and shape can be changed according to the model. Samsung Electronics 2-29...
Page 35
Product Specifications Indoor Unit Accessories(cont.) I MH✳✳✳FEEA(cont.) Item Descriptions Code-No. Q'TY Remark Cable-tie DB65-10088C Indoor Drain Pipe Holder DB90-02064A Unit Wired remote controller Box DB97-01904G ✳ The design and shape can be changed according to the model. 2-30 Samsung Electronics...
Page 37
Rubber Leg DB73-20134A DB60-30010A Flare Nuts, 6.35mm (only MH070FXEA4B/ outer pipe diameter MH080FXEA4B) DB60-30010B Flare Nuts, 9.52mm (only MH070FXEA4B/ outer pipe diameter MH080FXEA4B) Installation Manual DB98-28896A ✳ The design and shape can be changed according to the model. 2-32 Samsung Electronics...
Page 38
I MH040FXEA2B/MH050FXEA2B/MH060FXEA3B/MH070FXEA4B/MH080FXEA4B/MH18VF1X/MH19VF1X(cont.) Item Descriptions Code-No. Q'TY Remark Ass'y -Label Kyoto Protocol DB98-28756A Outdoor ) kg ) kg ) kg Unit (MH060FXEA3B) Nipple Connector DB67-00789A (MH070FXEA4B /MH080FXEA4B) ✳ The design and shape can be changed according to the model. Samsung Electronics 2-33...
Page 39
DB39-00378E (Wire Harness-DC Source) (MIM-B13) Transmitter communication cable DB39-00253B (Connect Wire-COM) (MIM-B13) Transmitter Case DB61-00450B (Case-Relay PCB Out) (MIM-B13) Cable-tie DB65-10088B DB98-25776A Installation Manual (MIM-B13) ✳ The design and shape can be changed according to the model. 2-34 Samsung Electronics...
Cable miss-wiring Cable connection (Indoor & Outdoor unit) MPI error malfunction Cable connection (another indoor unit & The number of indoor unit mismatched outdoor unit), SW01(outdoor) Compressor discharge sensor error(Short/Open) Outdoor unit Outdoor unit error Outdoor unit (Error code) Samsung Electronics...
Page 41
Indoor unit heat exchanger temperature sensor error (open or short) Indoor fan motor malfunction Option Setting EEPROM error Option error Option Setting (option wasn t set up or option data error) Remote Control on/off Outdoor unit error Outdoor Unit Power Reset Samsung Electronics...
Page 42
Error of setting option switches for optional accessories EEPROM error EEPROM option error : On : Flickering : Off N If you turn off the air conditioner when the LED is flickering, the LED is also turned off. Samsung Electronics...
Page 43
2. Outdoor unit error Main-Inverter Micom(After 1 minute of (Display is unrelated with Main-Inverter detection) operation) : On : Flickering : Off N If you turn off the air conditioner when the LED is flickering, the LED is also turned off. Samsung Electronics...
Page 44
Error of setting option switches for optional accessories EEPROM error EEPROM option error MPI no feedback Error : On : Flickering : Off N If you turn off the air conditioner when the LED is flickering, the LED is also turned off. Samsung Electronics...
Page 45
: Off N If you turn off the air conditioner when the LED is flickering, the LED is also turned off. N If you re-operate the air conditioner, it operates normally at first, then detect an error again. Samsung Electronics...
Page 46
: Off N If you turn off the air conditioner when the LED is flickering, the LED is also turned off. N If you re-operate the air conditioner, it operates normally at first, then detect an error again. Samsung Electronics...
Outdoor unit sensor error - Condenser out sensor(Short/Open) - Self diagnosis Compressor Discharge temperature sensor error Compressor discharge sensor detached - Self diagnosis Compressor OLP sensor error (Short/Open) - Error condition : outdoor temperature under -20˚C - Error level : over 4.95V(-30˚C) under 0.5V(151˚C) Samsung Electronics...
Page 48
DC peak error (IPM Over Current) Compressor Vlimit Error DC link Voltage error (under 150V, over 410V) Abnormal compressor running (Compressor Rotation Error) Current sensor error DC link Voltage sensor error OTP Error Inverter micom zero-crossing error Piping(gas leak) NO GAS error(self diagnosis) Samsung Electronics...
✳ Setting is not required if you must Push the button to set the display panel to a value which has a default. Every time you push the button, the display panel reads . . . repeatedly. 3-10 Samsung Electronics...
Page 50
If all lamps of indoor unit are flickering, Plug out, plug in power plug again and press ON/OFF key to retry. If the unit is not working properly or all lamps are continuously flickering after setting the option code, see if the correct option code is set up for its model. Samsung Electronics 3-11...
Page 51
✳ Setting is not required if you must Push the button to set the display panel to Every time you push the button, the display panel reads a value which has a default..repeatedly. 3-12 Samsung Electronics...
Page 52
If all lamps of indoor unit are flickering, plug out, plug in power plug again and press the ON/OFF key to retry. If the unit is not working properly or all lamps are continuously flickering after setting the option code, see if the correct option code is set up for its model. Samsung Electronics 3-13...
Page 53
✳ Setting is not required if you must Push the button to set the display panel to a value which has a default. Every time you push the button, the display panel reads . . . repeatedly. 3-14 Samsung Electronics...
Page 54
If all lamps of indoor unit are flickering, Plug out, plug in power plug again and press ON/OFF key to retry. If the unit is not working properly or all lamps are continuously flickering after setting the option code, see if the correct option code is set up for its model. Samsung Electronics 3-15...
Cabinet Front lower to detach the Cabinet Front. (Use +Screw Driver.) 3) Detach the Cabinet Front like the picture on the right side. 4) Loosen 1 screw(CCW)fixed to assemble Plate Control Out with Cabinet-Side RH. (Use +Screw Driver.) Samsung Electronics...
Page 58
5) Loosen 2 fixing screws(CCW)on the rear side of Cabinet-Side RH. (Use +Screw Driver.) 6) Loosen 4 screws(CCW)fixed to assemble Bracket Valve with Cabinet-Side RH. (Use +Screw Driver.) 7) Loosen 2 fixing screws(CCW)of Cabinet Side LF. (Use +Screw Driver.) Samsung Electronics...
Page 59
Ass’y Ass'y Control Out. Control Out 2) Detach several connectors from the PCB of Ass'y Control Out. 3) Detach 2 Connect Wires from Reactor. 4) Loosen 1 screw(CCW)fixed to assemble Ass'y Control Out with Partition. (Use +Screw Driver.) Samsung Electronics...
Page 60
2) Detach the Terminal Cover and detach the Connect Comp Wire from Compressor. 3) Disassemble the Felt Comp Sound. 4) Loosen the 3 bolts(CCW)at the bottom of Compressor like the picture on the right side. (Use Monkey Spanner.) Samsung Electronics...
Page 61
5) Loosen 2 fixing screws, 5 bolts and detach the Front Cabinet. (Use +Screw Driver.) 6) Loosen 2 fixing screws and pull up the Control Box. (Use +Screw Driver.) 7) Loosen 9 fixing screws and detach the Cabinet Side. (Use +Screw Driver.) Samsung Electronics...
Page 62
1) Loosen the fixing nut and detach the Fan. & (Use +Screw Driver.) Motor 2) Loosen 4 fixing bolts and detach the Motor. (Use +Screw Driver.) 3) Loosen 4 fixing bolts and detach the Bracket Motor. (Use +Screw Driver.) Samsung Electronics...
Page 63
2) Disassemble the Inlet and Outlet Pipe by & welding. Compressor 3) Loosen the fixing screws of the Heat Exchanger. (Use +Screw Driver.) 4) Detach the Heat Exchanger. 5) Loosen 3 nuts of the Compressor. (Use Monkey Spanner.) 6) Detach the Compressor. Samsung Electronics...
Page 64
3) Loosen 2 fixing screws of the Ass'y Control Out. (Use +Screw Driver.) 4) Loosen 6 fixing screws and detach the Cabinet Upper. (Use +Screw Driver.) 5) Loosen 2 fixing screws, 7 bolts and detach the Cabinet Front. (Use +Screw Driver.) Samsung Electronics...
Page 65
Disassembly and Reassembly Parts Procedure Remark 6) Loosen 2 fixing screw and pull up the Control Box. (Use +Screw Driver.) 7) Pull the felt and detach it. 8) Detach the Terminal Cover and detach the comp lead wire. 4-10 Samsung Electronics...
Page 66
2) Disassemble the Inlet and Outlet Pipe by welding. Compressor 3) Loosen the fixing screw of the Heat Exchanger. (Use +Screw Driver.) 4) Detach the Heat Exchanger. 5) Loosen 3 nuts of the Compressor. (Use Monkey Spanner.) 6) Detach the Compressor. Samsung Electronics 4-11...
Page 75
Exploded Views and Parts List 5-1-5 MH020FVEA/MH023FVEA/MH026FVEA/MH035FVEA/MH052FVEA 13-1 13-3 13-2 1-10 1-11 1-12 1-10 1-13 1-14 Samsung Electronics...
Page 76
Exploded Views and Parts List Parts List Q'TY MH023FVEA Code No. Description Specification SA/ SNA MH020FVEA MH026FVEA MH052FVEA MH035FVEA DB92-01087K ASS'Y PANEL FRONT ASS'Y HALF MIRROR DB92-01086J ASS'Y PANEL FRONT ASS'Y HALF MIRROR DB64-01633A PANEL FRONT HIPS,EMPIRE SILVER DB64-01638A PANEL FRONT...
Page 77
Exploded Views and Parts List Parts List(cont.) Q'TY MH023FVEA Code No. Description Specification SA/ SNA MH020FVEA MH026FVEA MH052FVEA MH035FVEA DB96-03149A ASS'Y EVAP-SUPPORT RH ASS'Y DB96-03817A ASS'Y EVAP-SUPPORT RH ASS'Y DB93-04636A ASS'Y CONTROL IN ASS'Y DB93-04664A ASS'Y CONTROL IN ASS'Y DB90-02167B...
Page 87
Exploded Views and Parts List 5-1-8 MH026FJEA/MH035FJEA 16 17 35-2 35-12 35-11 35-5 35-13 35-4 35-9 35-6 35-7 35-10 35-3 35-1 35-8 5-21 Samsung Electronics...
Page 88
ASS'Y CASE CONTROL PD ASSY 35-2 DB61-03540A SLIDER CASE PCB A ABS V0,T2.5 35-3 DB61-03541A SLIDER CASE PCB B ABS V0,T2.5 35-4 DB61-03537A CASE PCB MAIN ABS V0,T2.5 35-5 DB67-00896A CAP SWITCH ABS V0,T2.0 35-6 DB93-06169A ASS'Y PCB SUB SWITCH Samsung Electronics 5-22...
Page 89
DB61-03549A CASE PCB SWITCH ABS V0,T2.5 35-8 DB93-06164B ASS'Y PCB MAIN IN 35-9 DB65-00004U TERMINAL BLOCK 35-10 DB61-40291C HOLDER WIRE 35-11 DB63-02001A COVER CONTROL SGCC-M,T0.5 35-12 DB61-03550A CASE PCB ADDRESS ABS V0,T2.5 35-13 DB93-04640C ASS'Y PCB SUB 5-23 Samsung Electronics...
7. Schematic Diagram 7-1 Indoor Unit I MH✳✳✳FNEA/MH✳✳VF1-✳✳/MH✳✳FVEA This Document can not be used without Samsung's authorization. Samsung Electronics...
7-2 Outdoor Unit 7-2-1 MH040FXEA2B/MH18VF1X/MH19VF1X I Inverter BLDC Fan SMPS Inverter Micom Communication This Document can not be used without Samsung's authorization. Samsung Electronics...
Page 120
Schematic Diagram Schematic Diagram MH040FXEA2B/MH18VF1X/MH19VF1X(cont.) I Main Temperature sensor & EEV 485 Communication This Document can not be used without Samsung's authorization. Samsung Electronics...
Page 121
Schematic Diagram Schematic Diagram 7-2-2 MH050FXEA2B/MH060FXEA3B/MH070FXEA4B/MH080FXEA4B Temperature sensor & EEV SMPS Inverter This Document can not be used without Samsung's authorization. Samsung Electronics...
8-1 MAIN PCB(Indoor Unit) I MH✳✳✳FNEA/MH✳✳VF1-✳✳(MAIN PCB) The red number connecter is not used. & Power Temperature Sensor Motor RPM Feedback Auto Grill Remocon Module HVPS(High voltage Generator) Humidity Sensor BLADE-H Step Motor Anions Display Indoor Fan Motor Samsung Electronics...
Page 123
#2:Motor driving signal output_1 #2:MPI driving signal output (+) #3:Motor driving signal output_2 #3:Motor driving signal output_2 #3:DV12V #4:Motor driving signal output_3 #4:Motor driving signal output_3 #4:MPI feedback signal input #5:Motor driving signal output_4 #5:Motor driving signal output_4 Samsung Electronics...
Page 124
Motor Rpm FeedBack Melody ROOM/EVA IN Download Connector EVE OUT COM1 Indoor Fan Motor COM2 POWER & SUB PCB Connection Blade Step Motor Module PCB Connection Auto Grille Step Motor 1 Display PCB Connection Auto Grill Step Motor2 Samsung Electronics...
Page 125
PCB Diagram I MH✳✳✳FNEA/MH✳✳✳FBEA/MH✳✳✳FVEA/MH✳✳✳FJEA/MH✳✳VF1-✳✳(SUB PCB) The red number connecter is not used. External Signal MAIN PCB Connection Samsung Electronics...
Page 126
PCB Diagram I MH✳✳✳FKEA The red number connecter is not used. & Ventilator Drain Pump Float Switch Connection Fan-Motor Step Motor Power EEV Connection Motor Rpm Feed-Back Display PCB Connection EVA Out Sensor COM1 & ROOM/EVA IN Sensor COM2 Samsung Electronics...
Page 127
DC12V Out(Wired Remocon Power) : YW396-02V(WHT) Panel Louver(Stepping Motor) : SMW250-10(WHT) Micom Program Download : SMW200-10(BLK) “ External Control Out(Error, Compressor State) : SMW250-04(RED) Display PCB : SMW200-9(WHT) ‘ External Control In(On/Off Control Signal) : SMW250-02(RED) SSR Fan Control : SMW250-03(WHT) Samsung Electronics...
Page 128
#2~#5. Control SIGNAL #2~#5.Communication Signal #1. Communication Signal F1 #1.Communication Signal F1 #2. Communication Signal F2 #2.Communication Signal F2 CN20-MICOM Download2 CN10-MICOM Download1 > For Developer,Not for field >For Developer, Not for field > 7pin Downloader >10pin Downloader Samsung Electronics...
Page 129
Heater Temperature Option Switch Wired Remote Controller Power(12V) Fan (Tap Control) Control Signal Ventilator & Drain Pump “ Display Hot Coil ‘ Operating Check Signal Fan (SSR) HALL IC Trans In Download Main Power COM 1 Trans out Samsung Electronics...
8-2 MAIN PCB(Outdoor Unit) I MH040FXEA2B/MH18VF1X/MH19VF1X(INVERTER) & Power N Power Relay Power L Comp. Connector Wire & BLDC Fan : YAW396-07V(WHT) Reactor Connector Wire Main PCB Connector : SMW200-07(WHT) Samsung Electronics...
Page 131
PCB Diagram I MH040FXEA2B/MH18VF1X/MH19VF1X(MAIN) & Inverter PCB Connector : SMW200-07(WHT) Display PCB Connector : SMW200-07(WHT) OLP/Cond.Te temperature Sensor : SMAW250A-04(WHT) Outdoor/Discharge Temperature Sensor L SMAW250A-04(RED) EEV Connector : SMAW250A-06(WHT) DC5V Connector : SMW250-03(WHT) & Communication Samsung Electronics 8-10...
Page 132
PCB Diagram I MH050FXEA2B/MH060FXEA3B/MH070FXEA4B/MH080FXEA4B The red number connecter is not used. Power N COND/OLP Temperature Sensor & Power L DIS/OUT Temperature Sensor BLDC FAN EEV Connector AC FAN Comp. Connector Wire Communication 485 Reactor Connector Wire 8-11 Samsung Electronics...
The compressor stops intermittently in a The compressor stops intermittently or the fan speed of the COOL mode or DRY mode, and fan speed of the indoor unit decreases to prevent inside/outside air frozen indoor unit decreases. depending on the inside/outside air temperature. Samsung Electronics...
Total capacity of the indoor units Fan RPM (H:high,L:low,Blank:off ) Safety control Safety control • The EEV 2 and EEV 3 of MH040FXEA2B/MH050FXEA2B/MH18VF1X/ MH19VF1X models are always displayed as blank. • The EEV 3 of MH060FXEA3B model is always displayed as blank. Samsung Electronics...
Page 135
Button [K1] 1 times DIS 01 DIS 02 Display [DIS 01 ] is flickering on the setting time. Outdoor Temperature 0˚C or more less than 0˚C Time duration (Cool mode) (Heat mode) 5min~10min 20min~50min Samsung Electronics...
Page 136
- On this mode the controller will ignore the manual address number set on the rotary switch on the indoor PCB. - To confirm the indoor address number assigned by this mode, use "TEST MODE" and the address number will be displayed on the LED display on the indoor unit. Samsung Electronics...
Page 137
02--communication with indoor unit C; 03--communication with indoor unit D; ✳ In case of Manual address mode,you can do pipe check operation for check whether you connect the pipes correctly or not. But you need set indoor address switch yourselves. Samsung Electronics...
Page 138
Switch Setting and Testing Operation (cont.) TO SET ADDRESSING MANUALLY BY ROTARY TYPE PICTURE MODEL SWITCH “SW02 ” MH020FV(N)EA MH023FBEA MH026FB(V/N)EA MH035FB(V/N)EA MH052FB(V/N)EA MH026FKEA 1 WAY CASSETTE MH035FKEA MH030FMEA MIN 4 WAY MH035FMEA MH052FMEA MH026FEEA SLIM DUCT MH035FEEA MAS-DUCT MH052FUEA MH026FJEA DONSOLE MH035FJEA Samsung Electronics...
Page 139
Cooling mode (indoor unit check) Heating mode (indoor unit check) → Outlet air temp.-Inlet air temp : From 11°K to 14°K (indicative delta T) In heating mode,the indoor fan motor can remain off to avoid cold air blown into conditioned space. Samsung Electronics...
Page 140
Indoor unit heat exchanger in temperature sensor error (open/short) E237 Condenser temperature sensor error (open/short) E251 Compressor Discharge temperature sensor error (open/short) E251 Compressor OLP sensor error (open/short) E320 Please, The System turn off and replace sensor which is related. Guidance Samsung Electronics...
Page 141
Replace outdoor unit’s ass’y control or indoor unit’s Step 2 EEV Coil ass’y control. Basically, This error caused by communication between Indoor Units and Outdoor Unit. Guidance First of all, check the all communication connection and PCB’s status. Samsung Electronics...
Page 142
This is caused by protection mode behavior. Analysis This is indoor Evaporator Freezing protection mode. Step 1 Please, check indoor unit, whether inlet or outlet grill is closed. Step 2 Please, check indoor unit, whether indoor fan is working. 9-10 Samsung Electronics...
Page 143
Check point Remarks These Error codes only apply with Try-run mode, in case of system have some defect as result of try-run operation. Analysis ✳ Refer to self-detection algorithm (Check Error Code meaning and check it out) Samsung Electronics 9-11...
2 digit alternatively. Any Error code on LED display? Wait for 5 minutes to check error code Consult error code table because some error judgement needs long time Check Major parts(See 12-5) Consult error code(Next Page) 9-12 Samsung Electronics...
Page 145
? Error related to outdoor controller except Consult LED pattern on wiring diagram on temperature sensor and communication outdoor controller between indoor unit and outdoor unit ? See Error Code Table and Check “Main checking point” Samsung Electronics 9-13...
Page 146
After power off this error will display until Blink DC LINK capacitor discharged.(Max 20sec.) Blink Option error (EEPROM error) Abnormal condition Blink Comp. peak current (Over Current) Blink Comp. starting error Comp. rotation error Blink DC-Link voltage error Blink Comp. V Limit Error 9-14 Samsung Electronics...
Page 147
Press K4 key on the outdoor display PCB for several times to change the display to sensor temperature value. Left 1 digit of the LED is data index and Right 3 digits are the value Index Value Remark Estimated Primary current value from The unit is 0.1A Compressor current Samsung Electronics 9-15...
Page 148
Press K4 key on the outdoor display PCB for several time to change the display to sensor temperature value. Left 1 digit of the LED is data index and Right 2 digits are the value. Index Value Remark Discharge sensor temperature OLP sensor temperature The unit is degree C Condenser sensor temperature Outdoor sensor temperature 9-16 Samsung Electronics...
Page 149
The step value range is MH040FXEA2B/MH050FXEA2B EEV-C step MH18VF1X/MH19VF1X between Zero and 480. MH060FXEA3B/MH070FXEA4B EEV-D step MH080FXEA4B 9-3-7 Pipe matching See 12-2 "Checking and Testing operations". 9-3-8 Checking Motor in indoor unit See 12-5 "Fault Diagnosis of Major Parts". Samsung Electronics 9-17...
9-4-2 Procedure 12-4-2 The parts should be replaced in the following procedure. Check for any faulty part. Detach the faulty part. Replace it with a new part. Check the operation of the new part. The repair is completed. 9-18 Samsung Electronics...
• It is harmful to the air conditioner if it is used in the following environments: greasy areas (including areas near machines), salty areas such as coast areas, areas where sulfuric gas is present such as hot spring areas. Contact your dealer for advice. Samsung Electronics 10-1...
2. Make sure that you put the remote control unit in an area not exposed to direct sunlight, and where there is no source of heat. 3. Make sure that you use the remote control unit in an area away from TVs, audio units, cordless phones, fluorescent lighting fixtures and other electrical appliances (at least 1 meter). 10-2 Samsung Electronics...
183kgf•cm with a torque wrench. Service port 7. Check for gas leakage. • At this time, especially check for gas leakage from the 3 way valve’s stem nuts, and from the service port cap. Samsung Electronics 10-3...
Page 154
6 Mount the valve stem nuts and the service port cap to the valve,and tighten them at the torque of 183kgf•cm with a torque wrench. 7 Check for gas leakage. - At this time,especially check for gas leakage from the 3-way valve ’s stem nuts,and from the service port cap. 10-4 Samsung Electronics...
7) Stop operation of the air conditioner. 8) Close the 3 way valve, disconnect the pressure gauge, and open the 3 way valve again. 9) Close the cap of each valve. Samsung Electronics 10-5...
Page 156
7) Stop operation of the air conditioner. 8) Close the 5/8" service valve, disconnect the pressure gauge, and open the 5/8" service valve again. 9) Close the cap of each valve. 10-6 Samsung Electronics...
6. Make sure you do not bend the connection pipes in the middle and store together with the cables. • 7. Move the indoor and outdoor units to a new location. • 8. Remove the mounting plate for the indoor unit and move it to a new location. Samsung Electronics 10-9...
Page 160
6. Make sure you do not bend the connection pipes in the middle and store together with the cables. • 7. Move the indoor and outdoor units to a new location. • 8. Remove the mounting plate for the indoor unit and move it to a new location. 10-10 Samsung Electronics...
200~220V, 50Hz Free Inverter Version 220~240V, 50Hz Redd Digital Scroll _,12.. Indoor 127V, 50Hz _,A,B.. Outdoor Indoor/Outdoor Type Refrigerant 1 way Slim 1 way R407C Mini 4 way R410A Silhouette Duct Slim Vivave Moderato Console CONV Outdoor Samsung Electronics 11-1...
Page 162
FREE JOINT MULTI FOR EUROPE Buyer code Product Type Capa Serial Version Indoor Capacity Multi *K BTU Basic - CAP Indoor(K BTU) MR(02R~) Outdoor Mode Refrigerant R410A Inverter Semi Product Indoor R407C Outdoor Indoor Type Vivave Moderato 11-2 Samsung Electronics...
Heat exchanger; A device, used to transfer heat from a fluid on one side of a barrier to a fluid ASS’Y EVAP/ASS’Y COND on the other side without bringing the fluids into direct contact. (Full name : assemble evaporator / assemble condenser) Samsung Electronics 11-7...
It occurs when the drain pump is plugged out or it is out of order. Check the power of the drain pump and the position of the drain hose, and when the pump is faulty, contact the drain pump manufacturer. Samsung Electronics do not manufacture drain pumps. So, we are not able to correct the drain pump problems.
Page 169
Set up a sun blind over the outdoor unit and clear the neighboring obstacles from the outdoor unit to provide good ventilation. When it goes off frequently during a heat wave, it would prevent the turn-off and increase the cooling capacity cleaning the outdoor unit or spraying some water to the heat exchanger. Samsung Electronics 11-9...
Page 170
There is a cost table. But, our service engineer needs to visit to total up the cost correctly. When you move in, make sure to contact Samsung Electronics Service Center or Authorized Service Agent in advance to streamline the process.
But generally the value of fresh indoor temperature is that below 0.2(m/s) of indoor air circulation, the temperature is 21~28˚C when the wall temperature is the same as the indoor's and relative humidity is 30~31% in summer, the winter temperature is 20~24˚C and relative humidity is 30~60% in winter. Samsung Electronics 11-11...
Need help?
Do you have a question about the MH020FVEA and is the answer not in the manual?
Questions and answers