Page 1
CHIGO Service mannal Room airconditioner Split Wall-Mounted Type NOTE: Before servicing the unit, please first read the service manual and then contact with your service center if meet problem...
Page 2
Table of Contents 1、Summary ………………………………………………………………………………………………………………3 2、Model explaining …………………………………………………………………………………………………….4 3、Installation ……………………………………………………………………………………………………………..4 4、Exploded view and part list ………………………………………………………………………………………..8 5、Operation principle ………………………………………………………………………………………………….8 6、Parameter ………………………………………………………………………………………………………………9 7、Wiring diagrams ……………………………………………………………………………………………………...13 8、PCB principle chart ………………………………………………………………………………………………..17 9、PCB function …………………………………………………………………………………..10、Troubleshooting………………………………………………………………………………..
1. Summary indoor unit Model 38B model 85 1.2 outdoor unit 9000BTU 12000~18000 BTU 22000 BTU 24000~26000 BTU model KFR-25GW/AGX1c(38B) KFR-35GW/AGX1c(38B) KFR-51GW/BGX1c(38B) CS-70H3A-T38AS indoor unit 790×270×180 790×270×180 940×270×180 1080×335×245 Dimension outdoor unit 700×225×500 795×255×510 795×255×510 870×310×700 model CS-25C3A-V85AY1 CS-35H3A-M85AH4 CS-51H3A-P85AH4A...
Special craft code:Q-Deal with contact quickly;S-Soft start;d- Outside tube in addition to frost The weather type code(T1 type code abridge) "C" CHIGO brand Such as: CS-25C3A-V85AY1 T1 climate type,wall split type air conditioner, cooling capacity is 2500W,power is 220V~/50Hz/1PH, refrigeration is R410A,the kernel of indoor unit is fresh 98,the pattern no. is 85,first time design, outdoor unit is 1HP of 2003 year。...
Page 5
There is risk of fire or electric shock. ■ For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized service center. Do not disassemble or repair the product, there is risk of fire or electric shock. ■ Always ground the product.
Page 6
■ Do not open the inlet grill of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.) There is risk of physical injury, electric shock, or product failure. ■ When the product is soaked (flooded or submerged), contact an Authorized service center. There is risk of fire or electric shock.
Page 7
■ Do not drink the water drained from the product. It is not sanitary could cause serious health issues. ■ Use a firm stool or ladder when cleaning or maintaining the product. Be careful and avoid personal injury. ■ Replace the all batteries in the remote control with new ones of the same type. Do not mix old and mew batteries or different types of batteries.
Page 21
Caution:Capacity is base on standard length and maximum allowance length is base of reliability.Oil trap should be install per 5-7 meters. 4、 Indoor unit and outdoor unit explosion diagram and spare parts list(see explosion diagram file) 5. Refrigerant cycle diagram (working principle)...
Page 24
833*330*270 860*350*265 990*377*300 990*377*300 Packing (W*H*D) 9/11 12/14 14/17 14/17 Net/Gross weight Model YDK-30-6 YDK-35-6A H YDK-38-6B YDK-40-6A 1 Input Fan motor Capacitor r/min Speed φ384×136 φ401×115 Φ401×115 Φ415*115 Fan motor diameter×height Air flow m3/h ≥500 dB(A) Noise level 700*225*500 795*255*540 795*255*540 850×295×605...
Page 25
YDK-38-4 Model Brand Fan motor Capacitor r/min 1330/1200/1050 Speed(hi/mi/lo) φ108×811 Fan motor diameter×height Air flow m3/h 1050 dB(A) 43-49 Noise level 1070×325×250 Dimension (W*H*D) Packing (W*H*D) 1280×400×305 18/21 Net/Gross weight YDK-60A-6F Model Input Fan motor Capacitor r/min Speed Fan motor diameter×height φ460χ180 m3/h...
Page 26
CS-21H3A-C38AY1A(EER≥ CS-21H3A-M**AY1(EER≥ Model 3.2) 2.9) Rated volt and frequency Ph-V-Hz 220-240V/50Hz 220-240/50 Cooling capacity (actual/label) 2100 2200 Cooling power input (actual/label) Cooling Heating current input (actual/label) EER (actual/label) 3.23 3.21 Heating capacity (actual/label) 2100 2300 Heating power input (actual/label) Heating Heating current input (actual/label) COP (actual/label)
Page 27
Model YDK-16-4 YDK-16-4G Power input capacity Fan motor Indoor Fan Speed RPM r/min 1150/950/850 1290 (High/Med/Low) Indoor fan dia.*length φ97×633 φ98x622 Rows*Tubes*Circuits 2*12*2 2*15*2 Tube pitch* row pitch*Fin 17.6*12.3*1.4 21*12.7*1.4 spacing indoor unit Tube outside dia.and typ φ7×0.32internal threaded pipe φ7/internal threaded pipe Coil length x height x width 647*197*25.2...
8.5、Mitsubishi Jin dynasty 85 model of simple three lamp electrically controlled motherboards JS2-B85aC-M01A/2 编号 IC8 7805 零 线 O UT ZR 621-10-126 104/275V AC D1-D4 AC.ZERO IN4007 火 线 F USE IN4007 变 压器 1000UF /35V 220UF/25V 变 压器 次 级 变...
Page 87
③8LED display set temp., also it can display timer time and failure code. [4]LED multi-colour panel ①according to display mode: dehumidification, cooling, ventilation, heating, auto, sleep, fan speed, swing, timer, indoor fan running. Cooling ● Start up the compressor: when the room temperature is more than Ts+1℃, compressor → start-up ●...
Page 88
7° C 1° C -10° C c o m p r e s s o r o u t d o o r b l o w e r f a n d o o r b l o w e r f a n c o m p r e s s o r d o o r b l o w e r f a n...
Page 89
and indoor blower fan ② none defrost ③ TP1< 49℃ ④Tr ≤20℃. ● The electric heating shutdown in the heating mode shall meet one of the following conditions: ① shutdown indoor blower fan ② Tr ≥ 23℃ ③ TP1≥50℃. ● In the heating mode, the indoor flower fan can be set as high/ medium/ low /automatic running mode by remote control however the anti cool air function is prior.
Page 90
over 6 MIN start-up start-up COMPRESSOR start-up outdoor start-up start-up start-up blower fan four-way 2 MIN 2 MIN start-up start-up start-up valve b l o w e r f a n lower lower speed speed speed speed speed...
Page 91
c o m p r e s s o r d o o r b l o w e r f a n Defrost (only applicable to the heating mode) 1. the intelligent defrost In the heating mode, the electric control board checks and compares the temperature of indoor room and indoor coil pipe after the compressor works for a while;...
Page 92
① unit start defrost shall meet one of the following conditions: a. compressor cumulate running time over 30 minutes and it continuous running over 3 minutes, the temperature of coil pipe of the outdoor units is equal to or less than -15℃ for one minutes (Tp ≤-15℃).
Page 93
c o m p r e s s o r o u t d o o r b l o w e r f a n d o o r b l o w e r f a n c o m p r e s s o r o u t d o o r b l o w e r f a n d o o r...
Page 94
defrost time over 15 MIN or TP2 >15° C c o m p r e s s o r o u t d o o r b l o w e r f a n d o o r b l o w e r f a n ■...
Page 95
° C ° C Tr≤10℃ indoor low speed blower fan forbid dehumidify start-up start-up start-up shutdown start-up shutdown shutdown shutdown shutdown d o o r b l o w e r f a n start-up shutdown shutdown shutdown shutdown start-up start-up start-up shutdown...
Page 96
mode had set , it doesn’t change by Tr and the default set temperature is 25 ℃. 26° C m o d e Time on and time off When the time on or time off is used, the clock of remote controller shall be corresponding to the current clock and the timing times is less than or equal to 24 hours, when the timing time is reached, unit will start-up or shutdown.
Page 97
off state at on/off sensor fault (the resistance is 5КΩ in the normal temperature state 25 ) ℃ , when it is abnormal the sensor should be replaced. 2、 Check whether there is short circuit or open circuit in the wire of the sensor, and whether the plug is connected well, whether there is welding off or rosin joint on the electric control board, if there is any, it should be repaired.
Page 98
damaged, replace the controllable silicon or electric control board when they are damaged. 1、Firstly check whether the indoor fan is normal. PG motor display 2、Check whether the signal outputting from the flicker 6/8 no over zero display at integrated chip of the electric control board is at off signal normal, the electric control board should be...
10. TROUBLE SHOOTING Indoor Tr sensor error Is CN (Tr sensor connector) Connect CN properly. connected properly? Is Tr sensor resistance value Replace TA sensor. (5KO at 25? ) normal? Indoor P. C. board is defective. Replace P. C. board. Indoor TP1 sensor error Is CN (TP1 sensor connector)
Page 100
Only indoor fan motor does not operate. <Primary check> (1) Is it possible to detect the power supply voltage (200-240V) between L and N on the terminal block? (2) Does the indoor fan motor operate in cooling operation? Turn off power supply once, and turn it on again.
Page 101
Compressor does not operate. Turn on power supply. <Primary check> (1) Is the room temperature higher than the preset temperature in cooling operation? (2) Is the crossover cable connected properly? Does OPERATION Check power supply. indication indicate? Does compressor delay Is resistance value of room Room sensor or heat three minutes by...
Page 102
The unit does not beep at all. Press START/STOP OPERATION indication on button. indoor unit is not indicated. Is transmission mark indicated? Press RST button on remote control Is receiver on with tip of pencil. indoor unit exposed to direct sunlight? Does indoor unit Is there any thyristor operate when...
Page 103
Trouble shooting Trouble Is the unit display Is the power Check power supply mains or normal? applied to the unit? interconnection wires Does outdoor unit run? Is the power normal? check Check the wiring of indoor and the voltage between L&N of outdoor terminal block Check the...
Page 104
Indoor unit and outdoor unit don’t operate Indoor and outdoor unit don’t operate Does the electric switch Does the electric switch Is the power supply no Make the power cut off after a few supply ok. cut off? problem? nimutes? Is the wires of indoor Change a good remote, Replace remote...