CG i
GAS-
FIRED wATER BOILER- sERIEs a -
Boiler Manual
6
Field wiring
I&
WARNING!
NOTICE
For
your safety,
tum off electrical power supply
at
service
entrance panel before making
any
electrical
connections
to avoid possible
electric
shock
hazard. Failure to do so can cause severe
personal injury
or
death.
Wiring must be
N.
E.C. Class 1.
If original rollout thermal fuse element wire as
supplied
with boiler must
be
replaced,
use only
type
200'C
wire or equivalent. If other original
wiring as supplied with
boiler must
be replaced,
type
105'C
wire or equivalent
must
be used.
Boiler must be
electrically
grounded
as required
by
National
Electrical
Code
ANSI/NFPA
70
-
latest edition.
Electrical installation must comply
with:
1.
National
Electrical
O>de
and
any
other
national, state,
pro-
vincial
or
local codes
or
regulations.
2.
In
Canada, CSA
C22.1
canadian Electrical
Code
Part
1,
and
any local codes.
Wiring connections
Boiler is shipped with controls
completely
wired
Thermostat
1. Connect thermostat as shown
on
wiring
diagram on
boiler.
2.
Install on inside wall away from influences
of
drafts, hot
or cold
water pipes, lighting fixtures, television. sun rays,
or
fireplaces.
3.
If thermostat has a
heat
anticipator,
set heat anticipator in
thermostat to
match power
requirements of
equipment
con-
nected
to it. 1f connected directly to boiler,
set
for 0.1 amps
plus gas
valve current. See
infom1ation on wiring diagram
as
shown in Figure 32,
page 39.
For
other devices,
refer
to
manufacturer's
specifications.
Wiring diagram
on
boiler gives
setting for
control
module and gas valve. Also see instructions
with
them1ostat.
DHW
1.
O>nnect
DHW
aquastat as shown in
wiring below.
Economy
ftmction
isn't utilized
with
DHW
input.
Junction Box (furnished)
1.
O>nnect
120 V AC
power wiring as shown in
Figure
27.
2.
Fused
disconnect or service switch {15 amp. recommended)
may be
mounted on
this box.
For
those installations with
local codes which
prohibit installation
of fused
disconnect
or service switch
on
boiler,
install
a
2
x
4
cover
plate
on
the
boiler junction box
and
mount the service switch remotely
as required by the code.
Wiring multiple zones
Refer to zone valve manufacturer's literature fo
r
wiring
and
ap-
plication. A separate
transfom~er
is required to
power
zone
valves.
Zoning
with circulators requires a
relay
for
each
circttlator.
IACAUTIDNI
DO NOT
connect
directly from
3-wire zone
valve.s to the T-T terminals on the
boiler.
When using 3·wire zone valves, install
an
isolation
relay. Connect the zone valve end switch \vires to
the
isolation
relay coil. Connect the
isolation
relay
contact
across the
boiler
T-T terminals. Failure to
comply can result
in
damage to
boiler
components
or
cause unreliable operation, resulting in severe
property damage.
NOTICE
The
CGi
control module
is
polarity-sensitive. The
hot and
neutral
wires
must
be cOJmected to
the
correct
leads.
A flashing
POWER
light usually
indicates reversed
polarity
of
120 VAC
lead
wires.
Figure
27
Field
w1r1ng
connec-
tions
-
service
switch,
DHW
(If
used) and
thennostat
(or
end
switch)
provided
by
Installer
t
120VAC
A
Hoc
"TT'
Neutral
I
I
II
1
I
U
f
...
s. .....
,
~
~
'""""
:r
I
.... ..-.
u
~
I
I
~
I
Part
Number 550-142-780/0712
;>i
I
~;';:;.~"'
I
1
.......
~
1
I
I
I
I
I
I
I
I
)
)
"
"
"'"
-·-
;>i
I
Ot<W
I
I
'~"..:'
I
I
I
I
I
I
I
I
I
)
)
"
"
...
S!tYioe
sw~h
.,.._
Thermostat
or end swich
·--
3
1
Need help?
Do you have a question about the CGi Series 3 and is the answer not in the manual?
Questions and answers