AUXILIARY
AC voltage
DC voltage
RELAY OUTPUT : (optional)
Pulsed output
COMMUNICATION OUTPUT : (optional)
Serial communication
Baud Rate
Parity
Auto Detection
ANALOGUE OUTPUTS
3 outputs
Programmable to any 3 parameters (apart
from energy measurements W.h VAr.h VA.h A.h)
Rated value (software selectable)
Accuracy is relative to a standard 20mA or 10V output.
When outputs specified on order the accuracy will be
applicable to that output.
Load influence
Ripple
Response time
Overload
No load voltage
115 or 230 or 277volts (±15%)
12 / 24 / 48 / 110 / 125 volts
W.h or VAr.h or VA.h or A.h User
progammable import or export or used
as a control relay
RS485 output Modbus protocol
Programmable
2400,4800,9600 and 19200
Odd, Even or No parity
RS485
0-1mA into <10kOhm load
0-5mA into <2kOhm load
0-10mA into <1kOhm load
0-20mA into <0.5kOhm load
4-20mA into <0.5kOhm load
0-10 volts >1kOhm load
<0.1%
<0.5% peak-peak at full load
<400 msec for 0-99% at full load
<2 x rated value at full load
<18 volts
60