Page 1
A H I G H E R L E V E L O F C O N F I D E N C E ON Series ® e UPS For use with ON Series e 200 - 600 VA, 60 Hz model User Instruction Manual Desktop models Wallmount models...
Please read and save these instructions. This manual contains important instructions for the ON Series e UPS. Follow these instructions during the unpacking, installation and maintenance of the ON Series e UPS. If you have a problem with the unit, please refer to Troubleshooting on page 24 before calling ONEAC Technical Services.
We take pride in every unit that leaves our manufacturing facility Registering Your To ensure that your ON Series e UPS model and serial number are registered, complete and mail ONEAC UPS the enclosed postage-paid warranty card or go on line at www.oneac.com.
ONEAC product. If an ONEAC UPS needs repair or replacement, ONEAC Technical Services will issue a Return Material Authorization (RMA) number along with instructions on how to return the UPS. ON Series e UPS User Instruction Manual...
“OFF” position. Even with the battery disconnected and the unit unplugged, energy is stored in high voltage capacitors and represents a severe shock hazard. ON Series e UPS User Instruction Manual...
Do not cover or install the UPS in a confined or enclosed space. Grounding the Unit To eliminate shock hazard, the ON Series e UPS needs to be connected to a properly grounded AC receptacle. Before applying power, verify that the available line voltage matches the voltage listed on the rear-panel label.
This represents where the top of the enclosure will be. 2. Mark two screw locations, on the line, 7-3/8 inch apart. fig. 1: Mounting the ON Series e Wall-mount UPS ON Series e UPS User Instruction Manual...
UPS, see fig. 2. 2. Connect the battery cable from the next external battery enclosure (if any) to the external battery receptacle on the battery enclosure connected in the previous step. ON Series e UPS User Instruction Manual...
Page 12
Wall-mount UPS External Battery Enclosure of the ON Series e Wall-mount UPS fig. 2: ON Series e Wall-mount UPS and External Battery Connections Desk-top External Battery Enclosure(s) For additional runtime, some ON Series e UPSs can use extra batteries housed in a separate enclosure.
Page 13
Set-up and Installation Repeat step 2 to connect additional external battery enclosures. fig. 3: ON Series UPS and External Battery Connections Connecting Equipment to the UPS Before beginning, shut down and unplug the equipment to be protected. DO NOT make any...
AC input power source, toggle the power switch to the ( | ) “ON” position. Power is immediately supplied to the output connectors. The ON Series e will perform a self-test when turned on. Toggling the power switch to the( ) “standby”...
If the UPS is heavily overloaded, the audible alarm will sound continuously and will shut down in a few seconds. The input breaker may also trip. To reset the breaker, first turn the UPS ON Series e UPS User Instruction Manual...
Page 16
ON Series e 400 - 600 ON Series e 200 -300 ON Series e Wall-Mount fig. 6: ON Series e UPS Circuit Breakers Battery Replacement If the UPS has determined that the battery is no longer functional, the green and red LEDs will be on continuously and the yellow LED will flash.
Pin 20 is used to shut down the UPS when it is operating on battery. A positive signal (3 to 24V DC) with respect to pin 7 shuts down the UPS. A signal at or below ground allows the UPS to keep running. ON Series e UPS User Instruction Manual...
Page 18
Low Battery - normally closed Interface Port Interface Port Interface Port ON Series e 200 -300 ON Series e Wall-Mount ON Series e 400 - 600 fig. 7: ON Series e Interface Port ON Series e UPS User Instruction Manual...
Features and Specifications Features and Your ONEAC ON Series UPS features full output isolation and power conditioning with Specifications ® Virtual Kelvin Ground output filtering. This provides the highest level of protection from power line disturbances available. Intelligent battery management system includes: •...
(pin 10 N.N., pin 18 N.C.) Output Signals - stimulated relay Low battery (pin 1 N.O., pin 25 N.C.) Maximum Collector Voltage 25 VDC Maximum Collector Current 25 mADC Table continued on next page ON Series e UPS User Instruction Manual...
Page 21
ANSI/IEEE C62.41 Category A&B, 6 kV/200 &500 Amp, 100 kHz Ringwave Less than 10 V Normal mode (L-N), less than 0.5 V Common mode (N-G) Surge Voltage Let-through when subjected to ANSI/IEEE C62.41 Cat. A Normal & Common Mode Clamping instantaneous Response Time ON Series e UPS User Instruction Manual...
Features and Specifications Typical Runtime Table 2. Runtime for the ON Series e 200, 300, and 400 VA Desktop UPS Typical ONe200 ONe200D One300 ONe300D ONe400D Runtime by One12 V, 7 AH Two 6 V, 10 AH One 12 V, 7 AH...
Page 23
Features and Specifications Table 2. ON Series e 200 Wall-mount Extendable Runtimes Typical ONe200X Plus1 Plus2 Plus 3 Plus 4 Plus 5 Runtime by Two 12 V, 7 External External External External External System Load AH Batteries Battery Batteries Batteries...
Emissions Test Regulations United States 47 CFR Part 15 Subpart A Canada Interference-Causing Equipment Standard (ICES-003 Issue 2, Rev.1) Table 4. Safety Regulations Safety Regulations United States UL1778 (Uninterruptible Power Supply Equipment) Canada CSA 22.2 ON Series e UPS User Instruction Manual...
5. ON Series e 200 and 300 VA UPSs: using the new battery(ies), connect the red wire to the red positive (+) terminal on the battery.
Page 26
6. Connect the black wire to the (-) terminal on the battery. ON Series e 400 and 600 VA UPSs: insert the battery connector in the plug in the battery compartment. NOTE:The plug is polarized and connector will only fit in one way.
Battery Considerations ON Series e Wall-mount UPS Battery Wires Battery fig. 9: ON Series e Wall-mount UPS Battery Replacement Replacing External For additional runtime, some ON Series e UPSs Battery Enclosure(s) supportsextra batteries housed in a separate enclosure. The UPS power module and battery enclosure(s) are shipped separately.
Then lift the cabinet straight up to disengage from the upper two mounting screws (see fig. 11). fig. 11: ON Series e Wall-mount UPS Battery Replacement Battery Disposal UPS batteries contain toxic and acidic materials.
You can access these numbers on the back panel of the unit on a label located near the receptacles. Always check with ONEAC Technical Services before attempting to repair or return any ONEAC product. ON Series e UPS User Instruction Manual...
Troubleshooting If you have questions or problems regarding you ON Series e UPS, refer to the troubleshooting table below. Table 5. Troubleshooting Problem Possible Cause Solution Front Panel Switch not Switch the Power Switch to (I) “ON”. Reduce the load on the UPS by UPS will not turn ON UPS’s input circuit...
For full details of the warranty, see ONEAC Warranty, Policy and Procedures (part number 955-053). Exclusive Remedies Except as set forth herein and except as to title, there are no warranties, express or implied, or any affirmations of fact or promises by ONEAC...
Page 32
Organizations whose productivity goals allow no possibility for system downtime use ONEAC. They include many of the world's leading companies, in a wide range of applications including telecommunication systems, information technology, retail information systems, computer-integrated manufacturing systems, semiconductor test equipment and biomedical instrumentation and information systems.