OPERATION (cont.)
Condensate Pump Kit (Optional)
A condensate pump kits are available to allow continuous operation and to
eliminate the need for a drain tank.
When the water collects to level (A) in the pump
reservoir, the condensate pump begins to
operate and discharge the water.
Note: The compressor does not operate while the condensate pump is discharging the
water for the Office Pro 12 and Office Pro 18.
When the water level drops below level (B), the condensate pump stops, and the
compressor restarts.
Note: If for any reason the water level exceeds that of level (A) in the pump reservoir, an
over flow drain switch stops the compressor operation, and the LCD displays "AS".
Note: If the fan mode control DIP switch (see page 18) is set to the STOP position, the
entire unit (including fan operation) turns off either due to the over flow drain switch or
while the condensate pump is discharging the water.
CONDENSATE PUMP
CONDENSATE PUMP
RESERVOIR
O
O
DISCHARGE HOSE
25