Floor Brackets for panel radiators
Floor Brackets
Model numbers: 22
Model numbers: 21
Optional covers for brackets
Flow Setter Valve:
Each radiator is equipped with a flow setter valve
mounted on the same side as the water connections of
the panel radiator. This valve consists of two part integral
components for temperature control and flow balancing.
Flow Balancing:
Flow balancing is done by adjustment of the ring marked
1-7 and N on the flow setter valve, lining the desired
setting up with the dimple in the first ring. Turning of the
ring adjusts the diameter available for water flow. The N
marking indicates a fully open setting; the 1 marking
indicates nearly full restriction. The diagram on page 13
shows the pressure drop across the radiator as a function
of the flow rate and setting of the flow setter.
1 2 |
Technical specifications are subject to change without prior notice
Table 4
Part Number
817-BUD
817-BUD-1
81606400
Fig. 3
Air Vent and Drain Plug
Each radiator is equipped with a manual air vent (1/2")
and removable drain plug (3/4") for draining the radiator.
A flat head screw driver is needed to open the air vent.
Panel Radiator
Design Manual
Flow setter valve adjustment