3–58
"C" Group: Intelligent Terminal Functions
Func.
Name
Code
C044 PID deviation level
setting
C045 Frequency arrival
setting for acceleration
(2)
C046 Frequency arrival
setting for deceleration
(2)
C055 Over-torque (forward-
driving) level setting
C056 Over-torque (reverse
regenerating) level
setting
C057 Over-torque (reverse
driving) level setting
C058 Over-torque (forward
regenerating) level
setting
C061 Electronic thermal
warning level setting
C062 Alarm code output
C063 Zero speed detection
level
"C" Function
Description
Sets the PID loop error
threshold |SP - PV|
(absolute value) to trigger
intelligent output [OD].
Range is 0.0 to 100%,
resolution is 0.1%
Range is 0.0 to 99.99 /
100.0 to 400.0 Hz
Range is 0.0 to 99.99 /
100.0 to 400.0 Hz
Threshold for intelligent
output terminal [OTQ],
quadrant I. Range is:
0 to 200%, up to –550xxx;
0 to 180%, –750 to 1500xxx
Threshold for intelligent
output terminal [OTQ],
quadrant II. Range is:
0 to 200%, up to –550xxx;
0 to 180%, –750 to 1500xxx
Threshold for intelligent
output terminal [OTQ],
quadrant III. Range is:
0 to 200%, up to –550xxx;
0 to 180%, –750 to 1500xxx
Threshold for intelligent
output terminal [OTQ],
quadrant IV. Range is:
0 to 200%, up to –550xxx;
0 to 180%, –750 to 1500xxx
Sets the threshold for intelli-
gent output [THM].
Range is 0 to 100%
Allows binary alarm codes
to be output to intelligent
terminals.
Three option codes:
00 Disable
01 Enable – 3-bit code
02 Enable – 4-bit code
Range is 0.00 to 99.99 /
100.0 Hz
Defaults
Run
Mode
Edit
–FE
–FU
–FR
Lo Hi
(EU)
(US)
(JP)
✘ ✔
3.0
3.0
3.0
✘ ✔
0.00
0.00
0.00
✘ ✔
0.00
0.00
0.00
✘ ✔
100.
100.
100.
✘ ✔
100.
100.
100.
✘ ✔
100.
100.
100.
✘ ✔
100.
100.
100.
✘ ✔
80.
80.
80.
✘ ✔
00
00
00
✘ ✔
0.00
0.00
0.00
SRW Display
Units
%
>C044 PID
LEVEL
003.0%
Hz
>C045 ARV
ACC2
0000.00Hz
Hz
>C046 ARV
DEC2
0000.00Hz
%
>C055 OV-TRQ
FW-V
100%
%
>C056 OV-TRQ
RV-R
100%
%
>C057 OV-TRQ
RV-V
100%
%
>C058 OV-TRQ
FW-R
100%
%
>C061 E-THM
WARN
080%
>C062 AL-CODE
SELECT
OFF
Hz
>C063 ZS
LEVEL
000.00Hz