Page 2
LIMITED WARRANTY AND LIMITATION OF LIABILITY This Fluke product will be free from defects in material and workmanship for one year from the date of purchase. This warranty does not cover fuses, disposable batteries, or damage from accident, neglect, misuse, alteration, contamination, or abnormal conditions of operation or handling.
Table of Contents Title Page Introduction ............1 How to Contact Fluke ..........1 Safety Information ..........2 Symbols ..............5 Specifications ............6 General Specifications ........6 Electrical Specifications ........7 Software Specifications ........10 Environmental Specifications......10 The Product............11...
Clamp Meter Introduction The Fluke 317 and 319 are hand-held, battery-operated clamp meters (the Product) that measure: • ac and dc current • ac and dc voltage • resistance • continuity • frequency The Product ships with: • test leads •...
317/319 Users Manual Or, visit Fluke’s website at www.fluke.com. To register your product, visit http://register.fluke.com. To view, print, or download the latest manual supplement, visit http://us.fluke.com/usen/support/manuals. Safety Information XWarning To prevent possible electrical shock, fire, or personal injury: • Use the Product only as specified, or the protection supplied by the Product can be compromised.
Page 7
Clamp Meter Safety Information • Do not apply more than the rated voltage, between the terminals or between each terminal and earth ground. • Comply with local and national safety codes. Use personal protective equipment (approved rubber gloves, face protection, and flame-resistant clothes) to prevent shock and arc blast injury where hazardous live conductors are exposed.
Page 8
317/319 Users Manual • Do not use test leads if they are damaged. Examine the test leads for damaged insulation, exposed metal, or if the wear indicator shows. Check test lead continuity. • Disconnect power and discharge all high-voltage capacitors before you measure resistance, continuity, capacitance, or a diode junction.
Direct current Do not dispose of this product as unsorted municipal waste. Go to Fluke’s website for recycling information. Conforms to relevant European Union directives. Equipment is designed to protect against transients in equipment in fixed equipment installations, such as...
317/319 Users Manual Specifications General Specifications Digital Display ......6000 count resolution Low Battery Indication .... Shows when the batteries are below their required voltage Power Source ......Three AAA IEC LR03 batteries Clamp Opening Size....37 mm (1.45 in) Jaw Diameter ......
Clamp Meter Specifications Electrical Specifications The accuracy specification is defined as ±(% reading + digits) at 23 °C ± 5 °C. Function Parameter Range 40.00 A 40.00 A 600.0 A 600.0 A 1000 A Resolution 0.01 A 0.01 A 0.1 A 0.1 A Accuracy 1.6 % ±6 digit...
Page 12
317/319 Users Manual Function Parameter Range 40.00 A 40.00 A 600.0 A 600.0 A 1000 A Resolution 0.01 A 0.01 A 0.1 A 0.1 A (A dc) Accuracy 1.6 % ±6 digit 1.6 % ±6 digit [40 A] [40 A] 1.5 % ±5 digit...
Page 13
Clamp Meter Specifications Function Parameter Range 5.0 - 500.0 Hz Accuracy 0.5 % ±5 digit 10 – 100 Hz ≥5 A, 5 – 10 Hz, Trigger Level 100 – 500 Hz ≥10 A The accuracy specifications apply at 23 °C ± 5 °C (73 °F ±41 °F) Below 18 °C and above 28 °C (64 °F and above 82 °F) accuracy degrades at (0.1) times specification per °C.
317/319 Users Manual Software Specifications Calibration ......Full manual calibration and test One-year calibration cycle Data Integrity and Security ..Calibration parameters stored in flash ROM. Environmental Specifications Operating Temperature ... -10 °C to 50 °C (14 °F to 122 °F) Storage Temperature ....
Clamp Meter The Product The Product ClampMeter 600 V 1000 A 1000 A Tactile Barrier 600 A 40 A HOLD MAXMINAVG ACDC ZERO INRUSH TRUE RMS CLAMP METER 600 V etr111.eps...
Page 16
317/319 Users Manual Jaw Wear Jaw Wear Indicator 600 V 1000 A 1000 A 600 A 40 A 1000 A 600 A 40 A HOLD ZERO INRUSH TRUE RMS CLAMP METER ZERO 600 V etr113.eps...
Page 17
Clamp Meter The Product 1000 A 600 A 40 A HOLD ZERO INRUSH TRUE RMS CLAMP METER 600 V ZERO etr114.eps...
Page 18
317/319 Users Manual 40 A HOLD ZERO INRUSH TRUE RMS CLAMP METER 600 V <30 1000 A 600 A 40 A etr116.eps...
Page 19
Clamp Meter The Product 7 Display Hold 1000 A 600 A HOLD 40 A HOLD 8 MIN MAX AVG 1000 A 600 A 40 A HOLD ZERO INRUSH 2 sec = Exit etr122.eps...
Page 20
317/319 Users Manual 600 V 1000 A 1000 A 600 A 40 A HOLD 600 V 1000 A 1000 A 600 A ZERO INRUSH 40 A TRUE RMS CLAMP METER 600 V HOLD ZERO INRUSH TRUE RMS CLAMP METER 600 V...