Mitsubishi Electric City Multi PUHY-P168TSJMU-A Datasheet

Outdoor vrf heat pump system
Hide thumbs Also See for City Multi PUHY-P168TSJMU-A:

Advertisement

Quick Links

(Consists of One PUHY-P96TJMU-A, One PUHY-P72TJMU-A, and One CMY-Y100VBK2 Twinning Kit)
Job Name:
Engineer Name:
System No.:
OUTDOOR VRF HEAT PUMP SYSTEM FEATURES
3-phase, 208/230V
Modular variable refrigerant flow (VRF) systems;
smaller capacity units can be piped together to form a single,
large-capacity two-pipe system
• Required Twinning Kit allows for easy field piping connection
• Selectable fan static, 0.12 or 0.24"WG external static pressure;
factory set to 0"WG
• Maximum Total Refrigerant Piping Length: 3,280'; Maximum
Refrigerant Line Length: 541'; Maximum Control Wiring Length:
1,650'
• Connects to CITY MULTI indoor units; controlled via
CITY MULTI Controls Network (CMCN)
• External finish: Pre-coated Galvanized-steel Sheets
• Operating Temperature Range
Cooling (Outdoor): 23° ~ 115°F (-5° ~ +46°C) DB
Heating (Outdoor): -4° ~ +60°F (-20° ~ +16°C) WB
Specifications
Unit Type
Nominal Cooling Capacity
Nominal Heating Capacity
External Dimensions (H x W x D)
Net Weight
Electrical Power Requirements
Cooling Power Input
Heating Power Input
Cooling Current (208/230V)
Heating Current (208/230V)
Minimum Circuit Ampacity
(MCA)**
Recommended Fuse/Breaker
Size**
Maximum Fuse Size**
Piping Diameter
From Twinning Kit to Indoor Units
(Brazed) (In. / mm)
From Modules to Twinning Kit
(Brazed) (In. / mm)
Indoor Unit
Sound Pressure Levels
Fan
Type x Quantity
Airflow Rate
Direct-drive Inverter Motor Output
Compressor Operating Range
Compressor Type x Quantity
Compressor Motor Output
Compressor Crankcase Heater
Refrigerant
Lubricant
High-pressure Protection Device
Compressor / Fan Protection Device
Inverter Protection Device
Blue Fin Anti-corrosion Protection: Cellulose- and polyurethane-resin coating treatment applied to condenser coil that protects it from air contaminants;
≥1μm thick; Salt Spray Test Method - no unusual rust development to 480 hours.
** Each individual module requires a separate electrical connection. Reference electrical data for each individual module.
PUHY-P168TSJMU-A
Model:
System
PUHY-P168TSJMU-A
Btu/h
168,000
Btu/h
188,000
In. / mm
Refer to Module Data
Lbs. / kg
938 / 425
Voltage, Phase, Hertz
Refer to Module Data**
kW
kW
R.L.A.
42.0 / 37.9
R.L.A.
45.1 / 40.8
A
Refer to Module Data**
A
Refer to Module Data**
A
Refer to Module Data**
Liquid (High Pressure)
5/8 / 15.88
Gas (Low Pressure)
1-1/8 / 28.58
Liquid (High Pressure)
Refer to Module Data
Gas (Low Pressure)
Total Capacity
50 to 130% of ODUs
Model / Quantity
P06 ~ P96 / 1 to 36
dB(A)
Refer to Module Data
CFM
kW
8% to 100%
kW
Refer to Module Data
kW
Refer to Module Data
Refer to Module Data
Location:
Contractor:
Date:
PUHY-P96TJMU-A
OPTIONAL PARTS
□ Twinning Kit*..................................................CMY-Y100VBK2
□ T-Branch Joint (≤ 72,000 Btu/h)............................CMY-Y102S-G2
□ T-Branch Joint (≤ 144,000 Btu/h)..........................CMY-Y102L-G2
□ T-Branch Joint (≤ 234,000 Btu/h)...........................CMY-Y202-G2
□ Header (4-Branch; ≤ 72,000 Btu/h)..........................CMY-Y104-G
□ Header (8-Branch; ≤ 144,000 Btu/h)........................CMY-Y108-G
□ Header (10-Branch; ≤ 234,000 Btu/h)......................CMY-Y1010-G
* Twinning Kit is necessary to combine the refrigerant flows of the
modules and is sold separately.
Module 1
PUHY-P96TJMU-A
96,000
108,000
65 x 48-1/16 x 29-15/16 /
1,650 x 1,220 x 760
497 / 225
13.62
14.65
36 / 34**
40**
50 / 50**
3/8 / 9.52
7/8 / 22.2
61.0
58.0
Propeller Fan x 1
6,180
0.92
Inverter-driven Scroll Hermetic x 1
6.8
0.045
601 psi / 4.15 MPa
Overheat Protection / Thermal Switch
Overheat / Overcurrent Protection
PUHY-P72TJMU-A
Module 2
PUHY-P72TJMU-A
72,000
80,000
65 x 36-1/4 x 29-15/16 /
1,650 x 920 x 760
441 / 200
208 / 230V, 3-phase, 60Hz**
Refer to System Data
Refer to System Data
25 / 24**
30**
30 / 30**
Refer to System Data
3/8 / 9.52
3/4 / 19.05
Refer to System Data
58.0
Propeller Fan x 1
6,180
0.92
Refer to System Data
Inverter-driven Scroll Hermetic x 1
5.1
0.035
R410A
MEL32
601 psi / 4.15 MPa
Overheat Protection / Thermal Switch
Overheat / Overcurrent Protection

Advertisement

loading

Summary of Contents for Mitsubishi Electric City Multi PUHY-P168TSJMU-A

  • Page 1 PUHY-P168TSJMU-A Model: (Consists of One PUHY-P96TJMU-A, One PUHY-P72TJMU-A, and One CMY-Y100VBK2 Twinning Kit) Job Name: Location: Engineer Name: Contractor: System No.: Date: OUTDOOR VRF HEAT PUMP SYSTEM FEATURES • 3-phase, 208/230V • Modular variable refrigerant flow (VRF) systems; smaller capacity units can be piped together to form a single, large-capacity two-pipe system •...
  • Page 2 PUHY-P168TSJMU-A – DIMENSIONS Outdoor Unit:...
  • Page 3 CMY-Y100VBK2 Twinning Kit: Inches (mm) <Reducer Pipe (Accessory)> OD ø 1/2 19-15/16 (505) 7-1/4 (183) (12.7) OD ø 1 (25.4) ID ø 1/2 (12.7) ID ø 7/8 (22.2) OD ø 5/8 OD ø 1/2 OD ø 5/8 ID ø 1/2 ID ø...
  • Page 4 PUHY-P96TJMU-A – DIMENSIONS Module 1:...
  • Page 5: Specifications Are Subject To Change Without Notice

    PUHY-P72TJMU-A – DIMENSIONS Module 2: Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired ISO 9001 certification under Series 9000 of the International Standard Organization (ISO) based on a review of quality warranties for the production of refrigeration and air conditioning equipment.