Page 1
Powerware Series ® Eaton 5130 Rack/Tower UPS 1000–3000 VA User's Guide...
Page 2
National Fire Protection Association, Inc. Phillips is a registered trademark of Phillips Screw Company.All other trademarks are property of their respective companies. ECopyright 2008–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
Page 3
Class A EMC Statements (Low-Voltage Models) FCC Part 15 This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to NOTE part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol. CAUTION: REFER TO OPERATOR'S MANUAL - Refer to your operator's manual for additional information, such as important operating and maintenance instructions.
— causing hours of lost productivity and expensive repairs. With the Eaton 5130, you can safely eliminate the effects of power disturbances and guard the integrity of your equipment. The Eaton 5130 was designed for critical applications such as PCs, servers, workstations, and telecommunications equipment.
Page 8
INTRODUCTION Providing outstanding performance and reliability, the Eaton 5130's unique benefits include: Hours of extended runtime with up to four EBMs. Start‐on‐battery capability for powering up the UPS even if utility power is not available. Hot‐swappable batteries that simplify maintenance by allowing you to replace batteries safely without powering down the critical load.
To comply with international standards and wiring regulations, the total equipment connected to the output of this UPS must not have an earth leakage current greater than 3.5 milliamperes. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
I overensstemmelse med internationale normer og bestemmelser for el-installation må det udstyr, der er forbundet til udgangen af denne UPS, tilsammen ikke overskride en jordafdelingsspænding på mere end 3,5 milliampere. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Verwijder de ingangsnoer niet of haal de stekker van de ingangsnoer er niet uit terwijl de UPS aan staat. Hierdoor zou de UPS en uw aangesloten apparatuur geen aardebeveiliging meer hebben. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Page 12
Houd onbevoegden uit de buurt van de accu's. De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw plaatselijke voorschriften. Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Page 13
Älä päästä valtuuttamatonta henkilöstöä lähelle akkuja. Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia määräyksiä. Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Page 14
Afin d'être conforme aux normes et règlements internationaux de câblage, le courant de fuite à la terre de la totalité du matériel branché sur la sortie de l'onduleur ne doit pas dépasser 3,5 mA. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Page 15
Leitung zu Masseleiter, abhängig von der USV-Verkabelung. Das Eingangskabel nicht entfernen oder abziehen, während die USV eingeschaltet ist, weil hierdurch die Sicherheitserdung von der USV und den daran angeschlossenen Geräten entfernt wird. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
La TENSIONE contenuta in questo gruppo statico di continuità è LETALE. Tutte le operazioni di riparazione e di manutenzione devono essere effettuate ESCLUSIVAMENTE DA PERSONALE TECNICO AUTORIZZATO. All'interno del gruppo statico di continuità NON vi sono PARTI RIPARABILI DALL'UTENTE. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Page 17
Le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento fare riferimento alle disposizioni locali. Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle fiamme. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Alt utstyr som er forbundet med utgangen av denne UPS'en må ikke ha en sterkere total lekkasjestrøm enn 3,5 milliampere for å være i overensstemmelse med internasjonale standarder og forkablingsbestemmelser. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Page 19
Não remova ou desconecte o cabo de entrada quando a UPS estiver ligada. Isto removerá o aterramento de segurança da UPS e do equipamento conectado. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Page 20
Î Ï À Ñ Í Î Â äàííîì ÈÁÏ èìåþòñÿ ÑÌÅÐÒÅËÜÍÎ ÎÏÀÑÍÛÅ ÍÀÏÐ߯ÅÍÈß. Âñå ðàáîòû ïî ðåìîíòó è îáñëóæèâàíèþ äîëæíû âûïîëíÿòüñÿ ÒÎËÜÊÎ ÓÏÎËÍÎÌÎ×ÅÍÍÛÌ ÎÁÑËÓÆÈÂÀÞÙÈÌ ÏÅÐÑÎÍÀËÎÌ. Âíóòðè ÈÁÏ íåò óçëîâ, ÎÁÑËÓÆÈÂÀÅÌÛÕ ÏÎËÜÇÎÂÀÒÅËÅÌ. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Para cumplir con los estándares internacionales y las normas de instalación, la totalidad de los equipos conectados a la salida de este SIE no debe tener una intensidad de pérdida a tierra superior a los 3,5 miliamperios. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Page 23
är spänningen i de utgående uttagen 115 V (uppmätt från ledare-till-jord eller ledare-till-nolla beroende på UPS:ens anslutning). Ta aldrig bort nätsladden när UPS-enheten är påslagen. Detta tar bort skyddsjordningen från både UPS-enheten och den anslutna utrustningen. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Page 24
Håll ej behörig personal borta från batterierna. Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning. Använda batterier får aldrig brännas upp. De kan explodera. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
NOTE Check the battery recharge date on the shipping carton label. If the date has passed and the batteries were never recharged, do not use the UPS. Contact your service representative. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Install the UPS front cover and snap into place (see Figure 3). Figure 3. Installing the UPS Front Cover Continue to the following section, “UPS Setup.” Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
INSTALLATION UPS Setup The Eaton 5130 UPS is designed for flexible configurations and can be installed in a rack or as a standalone cabinet. If you are installing the UPS in a rack, continue to the following section, “Rackmount Setup;” otherwise, continue to “Tower Setup” on page 25.
Secure the rail to the front of the rack with two M5 washers and two M5 screws. Repeat Steps 3 and 4 for the other rail. Figure 4. Installing the Rail Kit Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
The setup varies depending on the size of the cabinet you are installing: Carefully position the cabinet upright with the air vents at the top (see Figure 5). Air Vents Figure 5. 3U Cabinet Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Page 32
Align the pedestals with the screw holes on the sides of the UPS cabinet. Secure the pedestals with the captive screws. Figure 6. Installing UPS Pedestals (for One 2U Cabinet) Continue to the following section, “Installing the UPS.” Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Page 33
NOTE Joining brackets are required for installations with two or more cabinets. Joining Bracket Figure 7. Installing the Joining Brackets If installing additional EBMs, repeat Step 5 for each cabinet. Continue to the following section, “Installing the UPS.” Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
RJ-11 port. See Figure 8. Up to four EBMs may be connected to the UPS. EBM Communication Cable EBM Cable EBM Battery Connectors Figure 8. UPS Installation with Four EBMs Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Page 35
For rackmount installations only. If your rack has conductors for grounding or bonding of ungrounded metal parts, connect the ground cable (not included) to the ground bonding screw. See “UPS Rear Panels” on page 33. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Page 36
If you are installing a remote power-off or a remote on/off switch, see the following section, “RPO and ROO Installation,” to install the switch before powering on the UPS. Continue to “Turning the UPS On” on page 35. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
INSTALLATION RPO and ROO Installation The Eaton 5130 includes a two-position terminal (see Figure 11) that can be either left closed or configured one of two ways: RPO: Allows a remote contact to be used to disconnect all equipment connected to the UPS. Restarting the UPS requires manual intervention.
Page 38
Activate the external RPO or ROO switch to test the function. Verify the status change on the UPS front panel. 10. RPO only. De-activate the external RPO switch and restart the UPS. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
INSTALLATION UPS Rear Panels This section shows the rear panels of the Eaton 5130 models. Receptacles USB Port [(6) 5-15R - 1000–1500 VA RS-232 Port EBM Battery Connector (8) 5-15/5-20R - 2200 VA] Communication Bay Ground Bonding Screw EBM RJ-11...
24 hours after installation or long-term storage. NOTE If more than two EBMs are installed, an external battery charger is recommended for faster recharge times. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Standby mode (if utility power is available) and removes power from your equipment. Unplug the UPS. If you do not unplug the UPS, it remains in Standby mode. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
OPERATION Operating Modes The Eaton 5130 front panel indicates the UPS status through the UPS indicators. Figure 17 shows the UPS front panel indicators and controls. Indicator Legend Unlit Normal Mode Indicator Load Not Protected Indicator On/Off Button Flashing Load Level Indicators...
UPS output receptacles. The battery recharges when necessary. NOTE For 230V models, the output receptacles may remain electrically live (up to 115V). Unplug the UPS to ensure power is not available to the output receptacles. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
USB port RS-232 communication port Communication card Load segments (PowerShare) The Eaton 5130 UPS includes a USB port, a RS-232 communication port, and a bay for an optional communication card. The USB and RS-232 ports cannot operate simultaneously. USB Port...
Page 46
ADDITIONAL UPS FEATURES Figure 20. The USB Port Install the LanSafe Power Management Software and USB drivers according to the instructions provided at www.eaton.com/powerquality. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Table 4. Communication Port Pin Assignment Pin Number Function 1, 3, 4, 5, 6, 10 Not used Common Low Battery Operation on battery power UPS ON, equipment supplied Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
To customize the UPS settings: Download the UPS Configuration tool from www.eaton.com/powerquality. Follow the on-screen instructions for the Eaton 5130. It is possible to modify the settings listed below (detailed comments are available in the UPS Configuration tool). Table 5. Main Output Options...
Page 50
Maximum input-voltage range Disabled Enabled Low threshold for transfer to battery is 150V. Table 7. UPS Sensitivity Options Function Factory Setting Other Available Settings UPS-sensitivity level Normal High or low Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Page 51
Low-battery warning 0–100% Battery protection against deep discharge Enabled Disabled Audio alarm Enabled Disabled Additional battery module Automatic detection of number of For specific batteries, 25–81 Ah battery modules Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Verify that the UPS is unplugged and turned off. Disconnect the UPS internal battery connector using the steps in “Connecting the UPS Internal Battery” on page 22 in reverse order. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
2) Use tools with insulated handles; 3) Do not lay tools or metal parts on top of batteries. ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors. Attempting to alter wiring can cause injury. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Pull the battery out onto a flat, stable surface. The battery is unsupported when you pull it out of the UPS. To ensure safety and high performance, use only batteries supplied by Eaton. To replace the UPS internal batteries: Remove the UPS front cover. Press the button on the left side of the cover and then pull the left side (see Figure 25).
Page 56
See “Recycling the Used Battery or UPS” on page 52 for proper disposal. Figure 28. Removing the Battery Block Install the new batteries in the reverse order of removal. Replace the metal battery cover. Replace the UPS front cover. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
C A U T I O N Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
The high and low thresholds can be adjusted using the UPS Configuration tool (see page 43). Up to 40 Hz in low-sensitivity mode (programmable using the UPS Configuration tool). Adjustable to 100V (10% derating of output power) 120/127V. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Page 60
33.8 kg (74.5 lb) 17.3” 3.4” 25.0” PW5130i3000-XL2U 634 mm PW5130G3000-XL2U 35.3 kg (77.9 lb) 17.3” 3.4” 25.0” 484 mm PW5130i3000-XL3U 34.3 kg (75.6 lb) 17.3” 5.2” 19.0” Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
Page 68
Batteries” on page 48). bar graph indicators flash. test. UPS fault condition. The load is Contact your service representative. indicator alone is on and not supplied. the alarm sounds continuously. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
A replacement or repair unit will be shipped, freight prepaid for all warrantied units. Help NOTE For critical applications, immediate replacement may be available. Call the Desk for the dealer or distributor nearest you. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
This limited warranty (this “Warranty”) applies only to the original End-User (the “End-User”) of any Eaton 3105, 5110, 5115, 5125, and 5130 Products (individually and collectively, the “Product”) purchased on or after August 19, 2009 and cannot be transferred. This Warranty applies even in the event that the Product is initially sold by Company for resale to an End-User.
Page 72
Product is sold, Company shall have no obligation under this Warranty. Also during such time, the period of this Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any overdue or unpaid amounts. Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide 164201730 Rev 4 www.eaton.com/powerquality...
In the USA, call the Customer Reliability Center 7x24 at 800-356-5737. Outside of the USA, call your local Eaton product sales or service representative. For comments or questions about this Warranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.
Page 74
This Guaranty is not valid: (a) unless the End-User returns to Company the Warranty Registration Card or completes the registration form on www.eaton.com/PQ/Register within thirty (30) days of purchase; or (b) if the Product's serial numbers have been removed or are illegible.