3.4 Technical Information

SAE Compliant
Vehicle Interface
Cable Length
AC Max Charging Power Output**
Voltage and Current Rating
AC Power Input
Recommended Service Panel
Breaker
Ground Fault Protection
Ground Monitoring
Standby Power
Outdoor Rated
Safety Compliance
Surge Protection
EMI Compliance
Operating Temperature
Operating Humidity
Unit Weight
Dimensions
**WattStation determines the maximum power consumption. EV determines the actual
power consumption.

3.5 Fault Indication

When the fault indicator illuminates red, WattStation is indicating a fault.
WattStation faults will be either self-correcting or non-correcting.
Self-correcting: When the fault icon and LED ring around the coupler are
illuminated, the system is experiencing a self-correcting fault. In this state the
system will reset after 15 minutes, or a manual reset can be performed. Simply
remove and replace the connector to the EV, or power cycle the unit by holding
down the power button until the system turns off and pressing the power button
again to restart.
Non-correcting: When fault icon is illuminated and LED ring is not illuminated a
fault has occurred which requires a manual reset. Simply remove and replace the
connector to the EV, or power cycle the unit by holding down the power button
until the system turns off and pressing the power button again to restart.
If a fault condition persists have your local certified electrician inspect the system.
11
Level II per J1772
SAE J1772 EV connector
16' cable
7.2 kW (240VAC @ 30A)
208-240VAC @ 30A
208-240VAC requiring only Line 1, Line 2 and
Earth ground
2-pole 40A breaker on dedicated circuit
Internal 20mA CCID with auto-re-closure, does
not require a GFCI in service panel
Ensures ground is present between vehicle and
WattStation, and between WattStation and
load center
0 W when not charging and turned off by
pushbutton switch
NEMA 3R
ETL and CETL listed conforming to UL 2594,
2231 and 1998
6kV @ 3000A
FCC Part 15 Class A
-30°C to +50°C ambient
Up to 95% non-condensing
35 lbs
24" H x 16" W x 6" D
GE Energy
©2011 GE Company All Right Reserved