Summary of Contents for Northern Lights PX-300K2 Series A.C. Generators
Page 1
& ARTS ANUAL ANUAL PX-300K2 SERIES A.C. GENERATORS For Generator Models: PX- 308 K 2 , PX309K2, PX- 310 K 2 , PX- 312 K 2 , PX- 316 K 2 , PX- 320 K 2, PX-320C2, PX-325K2, PX-332K2, and PX-332C2...
Introduction • Insulation Resistance and Dielectric: When This manual describes procedures for operation, measuring insulation resistance and dielectric, be maintenance, inspection and adjustment. It will help the sure to disconnect the AVR and rectifi er. operator realize peak performance through effective, economical and safe operation.
M984W ............PX-332K2 M33CW ............PX-332C2 SERIAL NUMBERS • When referencing Northern Lights equip ment by serial number, it is important to differentiate between the engine, generator end, and generator set serial numbers. • The engine serial number is either on a metal tag or stamped directly into the engine block.
Mechanical Construction STATOR COUPLING WITH PRIME MOVER The stator frame is fabricated from rolled steel. The PX-300K series single bearing generators make round construction provides rigidity and strength to centering and direct coupling easy. Coupling bolt size resist excessive mechanical shocks. The stator core is and torque will vary according to the engine made of high quality silicon steel plates coated with manufacturer.
Performance and Function EXCITATION SYSTEM The excitation system of the PX-300K Series genera tor uses an Automatic Voltage Regulator (AVR) which uses a portion of the output power to supply controlled DC power to the exciter fi eld (EX) as show in Figure 2. When DC power is supplied to the exciter fi...
Characteristics VOLTAGE REGULATION SHORT CIRCUIT ± Generator terminal voltage regulation is within 1% of the PX-300K2 Series AC generators can provide over 300% rated voltage in lagging power factor. 1.0 to 0.8, when the of the rated current for a short period of time, with an load is varied gradually from no load to full load.
Operation – Generator Set STARTING STOPPING Before starting generator, check the following: After putting the running generator in a no-load condition 1. Make sure that the wiring is correct. by removing the generator load, stop the engine in 2. Be sure that nothing is blocking the air inlet/ outlet. accordance with the Engine Manual.
Operation – Automatic Voltage Regulator SAFETY RULES 2. Voltage Adjustment: • Do not leave AVR connected when testing generator If the voltage output is low, increase the voltage by with high-pot or megger. turning the Voltage Adjust (VR1) slowly clockwise. •...
Maintenance BEARING INSPECTION b. Using a bearing puller, extract bearing from For bearing inspection, make sure that there is no abnormal sound during normal running and no over- shaft. c. When installing a new bearing, place a steel pipe heating. Greasing is not necessary for generators using the on the inner race surface, and fi...
Page 12
Maintenance 2. Replacement of Rotary Rectifi er Parts: • Good surge absorber elements have about 10-30 K a. Rotary rectifi er parts are all located at the rear ohms, but if the resistance reading is near 0 ohms, of Exciter rotor. For parts replacement, remove the surge absorber elements is defective and must be the bearing shield.
4. Rotating Rectifi er Assembly Detailed Structure: Figure 9. Rotating Rectifi er. Maintenance – Automatic Voltage Regulator 1. Keep the AVR clean at all times. Make sure no dust or moisture accumulates on the AVR. 2. Inspect periodically making sure that wiring connections are not loose. OPX300K2 05/12...
Automatic Voltage Regulator: DST-100-2FAK Sensing Output Frequency 50 Hz 60 Hz Voltage 100 Volt Class 100V 120V (86.5V~110V~120V) 200 Volt Class 200V 240V (173V~220V~240V) Phase: Single Phase Single Phase Power Input Voltage: 100V ~ 127V ~ 139V Frequency: 50 Hz / 60 Hz Phase: Single Phase...
Trouble Shooting PROBLEM POSSIBLE CAUSE RECOMMENDATION(S) Only a FEW VOLTS Loss of residual magnetism of the exiter fi eld • Flash fi eld. of output Disconnection or short circuit of windings • Check the insulation of all windings and check the resistance value. Defective AVR •...