Heating and hot water for the professionals Installation and Servicing Instructions THEMA F I N W A R R A N T Y THIS IS A CAT II2H3+ APPLIANCE T E C H N I C A L H E L P L I N E 01773 828400 01773 828100...
INSTALLATION AND SERVICING INSTRUCTIONS THEMA F 23 E - THEMA F SB 18 E - THEMA F SB 23 E Note! The boiler serial number is marked on the label attached to the inside of the boiler. Refer to the 'Introduction' section page 3 for a description of the basic functions of the boiler.
INTRODUCTION The THEMA F 23 E boiler is a wall mounted modulat- The boiler is supplied for rear outlet flue connec- ing combination boiler with electronic ignition pro- tion. Alternatively, the boiler is designed to allow viding central heating and instantaneous domes- the flue system to be connected to the top of the tic hot water.
TECHNICAL DATA Heating output automatically variable from (kW) (BTU/H) 30,000 30,000 30,000 to (kW) 23,3 18,5 23,3 (BTU/H) 80,000 63,000 80,000 Efficiency 91,5 90,5 91,5 Heating adjustment 38 C to 90 C Expansion vessel effective capacity Expansion vessel charge pressure (bar) Maximum system capacity at 75 C Safety valve, maximum service pressure...
FIXING JIG THEMA F 23 E From left to right, the fixing jig comprises: - Heating return with isolating valve (m). - Cold water inlet with isolating valve (p). - Heating flow with isolating valve (q), drain screw (r) and safety valve (s).
HEATING SYSTEM DESIGN • The THEMA F boiler is compatible with any type of An additional expansion vessel can be fitted to the installation. system if required, see diagram 6. • Heating surfaces may consist of radiators, convec- • Provision shall be made for a drain valve at the tors or fan assisted convectors.
• Check that both the hook and connecting plate are level. Should any doubt exist as to the permissible posi- tion of the terminal, contact the Saunier Duval If the boiler is not installed immediately, protect the Technical Helpline 01773 828400.
BOILER INSTALLATION Statutory requirements Installing the boiler The installation of this boiler must be carried out by Prior to starting work, the system must be thoroughly a competent person in accordance with the rel- flushed so as to eliminate any foreign bodies and evant requirements of the current issue of: contaminants such as filings, solder particles, oil, grease etc.
Page 11
REAR OUTLET FLUE INSTALLATION B - Rear outlet side flue Mark the horizontal centre line on the rear wall. Extend the horizontal centre line to the side wall and mark the vertical centre line of the flue hole 255 mini as shown in diagram 12.
Page 12
REAR OUTLET FLUE INSTALLATION Extended flue The horizontal flue is extended by using one or more Outer pipe of the 1000 mm extension pipes, Saunier Duval part number 85091. These are connected together by push fit type joints, clamps and seals. Cutting length Calculation of flue cutting lengths for extended flue •...
The horizontal flue is extended by using one or more of the when fitting. 1000 mm extension pipes, Saunier Duval part number 85091. Important: If the flue has been cut, ensure that there are no These are connected together by push fit type joints, clamps burrs that could damage the 'O' ring.
Connection of the whole electrical system and any A mechanical or digital time clock is available as heating system controls to the electrical supply must an accessory, Saunier Duval part N 86148 (me- be through a common isolator. chanical) or 86149 (digital).
COMMISSIONING The commissioning and first firing of the boiler must only be done by a competent person. Gas installation It is recommended that any air is purged from the supply at the gas inlet test point on the left hand side of the gas valve, see diagram 20.
The THEMA F 23 E boiler has a built in frost protec- In case of power supply failure The boiler no longer operates. tion device that protects the boiler from freezing. If...
6. Any bypass must be fitted before system controls. PCB Settings The PCB on the Thema F 23 E can be set to operate in different ways to suit individual installations. The dip switch SW1, see diagram 27, should be set as...
ROUTINE CLEANING AND INSPECTION To ensure the continued efficient and safe opera- tion of the boiler it is recommended that it is checked and serviced at regular intervals. The fre- quency of servicing will depend upon the particu- lar installation conditions and usage, but in gen- eral once a year should be enough.
• Replace all outer panels. REPLACEMENT OF PARTS To replace microswitch assembly exept SB models) microswitch on THEMA F 23 E • Disconnect microswitch by pulling off plug. • Unclip external controls connector from mount- ing bracket.
REPLACEMENT OF PARTS • Fit replacement PCB in reverse order to removal. Important: When fitting replacement PCB, ensure that control knob spindles correctly locate into PCB adjuster slots. • Refit connectors and covers in reverse order to removal. To replace ignition PCB •...
REPLACEMENT OF PARTS • Push water valve back to disengage it from re- versing valve. • Unclip and remove loss of water pressure switch from left of reversing valve assembly, see diagram • From below boiler, undo and remove three screws holding reversing valve to bottom plate of boiler.
REPLACEMENT OF PARTS • Remove clip holding pipe to heat exchanger in rear of water valve. From front of boiler, grip clip with long nosed pliers and pull upwards. • Unscrew and remove large screw holding water valve to back plate of reversing valve assembly, see diagram 32.
REPLACEMENT OF PARTS To replace safety valve • Unscrew pipe connection nut from expansion vessel and disengage pipe from connection. Keep • Drain down entire heating system. • From below boiler, disconnect heating flow pipe sealing washer. from rear of fixing jig. •...
REPLACEMENT OF PARTS • Unclip thermistor from pipe. To replace burner • Pull off electrical cennections from thermistor. • Pull off ignition and flame sense leads from elec- • Fit replacement thermistor in reverse order to re- trodes. moval. • Remove burner from boiler as described in 'Rou- Note: No heat sink compound is required.
FAULT FINDING Prior to fault finding, check : For example: Inlet gas pressure = 20 mbar If the domestic hot water works but the heating Electrical supply = 240 V - 50 Hz doesn’t, refer to chart No. 1. Central heating system is pressurised at 1 - 1,5 bar. If heating works correctly but the hot water doesn’t, Overheat thermostat on RHS of heat exchanger has refer to chart No.