4. TECHNICAL CHARACTERISTICS

4.2. TECHNICAL CHARACTERISTICS
MECHANICAL
Metal 19" rack case, 2 units high
IP51 Protection (as per IEC 529)
Local HMI: LCD (2 rows, 16 characters) and 20 key keyboard
Rear connection for wiring: 4 blocks, 12 terminals each (6 blocks when optional expansion board)
Dimensions: 437 x 164 x 88 mm
Weight: Net 6 kg. Shipping 7 kg.
ELECTRICAL
Frequency:
Rated current:
DC Power Supply
Operational range
Digital Input Voltage
Thermal Capacity
Current circuits
- Permanent
- 3s duration
- 1 s duration
Temperature ranges
-Operation
-Storage
Humidity
Trip contacts:
AC
-Continuous Capacity
-Rated Breaking Capacity
-Make
-Operating Time
DC Breaking Capacity
- Resistive
- Resistive
- Inductive(L/R=40 ms)
Burden
-Current circuits
Consumption:
-At DC rated voltage
-Digital inputs
Accuracy
-Current
-Time
- Error index
Repeatability
-Operating value
-Operating time
22
50 or 60 Hz (selectable by setting)
1 or 5 A (different models)
48/125 Vdc or 110/250 Vdc (different models)
80% to 120% of rated values
For standard models: 48-125, 110-250 VDC
(according to selected model). For special models,
please refer to section 4.1.1.
4 x In
50 x In
100 x In
-20º C to + 55ºC
-40ºC to + 70ºC
Up to 95% without condensation
16A
4000VA
25A for 4 sec
8 ms or less
9A at 30V
0.65A at 100V
0.5A at 30V
0.5 VA at I
0.1 VA at I
12 W idle state
16 W all relays activated
8 mA (1 W at V
5%
5% or 30ms (whichever is greater)
Class E-5 as per IEC 255-4
1%
2% or 30 ms (whichever is greater)
DBF Breaker Failure Protection
= 5 A
r
= 1A
r
= 125 VDC)
rated
GEK-106168E