Download Print this page

Dell 3750W Site Preparation Manual page 6

Site preparation guide
Hide thumbs Also See for 3750W:

Advertisement

Optional 32A 1phase, 3m, UPS Input Cord Kit
If you ordered the optional 32A input cord kit, refer to the below drawings for advice on fitting the cable:
Step 1: Remove the cover-plate from the rear of the UPS
Step 2: Remove the back (side nearest cable bare ends)
to access rear-plate terminals and cable access port
of the plastic stuffing gland from the input cord kit
Step 3: Thread the input cord through the UPS back-
Step 4: Secure the bare cable ends to the UPS terminals
plate and secure with the plastic stuffing gland. Ensure
& replace the cover-plate.
you leave enough free cord to connect to the UPS
terminals.
Wire Colour
Terminal Position
UPS Wire Function
Terminal Wire Size Rating
Tightening Torque
Grey/Yellow Stripe
G
Input Ground
2
5.26-16mm
2.26Nm
Blue
N
Neutral In
(10-6AWG)
(20 lb in)
Brown
L
Line (Live) In
Dell UPS Site Preparation Guide, EMEA (230V)
Revision 1, February 2012

Advertisement

loading

This manual is also suitable for:

4200w5600w