IOM Instructions HKV LArge CommerCiAL Heat Controller, Inc. TABLE OF CONTENTS Model Nomenclature ............ 2 Tensioning V-Belt Drives..........19 Physical Data..............3 Blower Sheave Information ........20 Dimensional Data ............4-5 Blower Performance Tables ........21-34 General Information ............6 Unit Commissioning &...
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions HKV084-150 Dimensional Data ALL CONFIGURATIONS REQUIRE SERVICE ACCESS AREA SHOWN BELOW. (RR/FD) AIR OUT AIR OUT RETURN AIR RETURN AIR Control Box CAP+MSP Control Box CSP+CAP+MSP FRONT RETURN TOP DISCHARGE REAR RETURN TOP DISCHARGE NOTES FOR LEGEND: 1.
IOM Instructions HKV LArge CommerCiAL Heat Controller, Inc. HKV168-300 Dimensional Data ALL CONFIGURATIONS REQUIRE SERVICE ACCESS AREA SHOWN BELOW. (RR/FD) AIR OUT AIR OUT AIR OUT AIR OUT RETURN AIR RETURN AIR RETURN AIR RETURN AIR Control Box Control Box...
Installation, Operation, and Maintenance instructions compressor oil, the refrigerant lines of the compressor must are provided with each unit. HKV units are typically be sealed after it is removed. installed in a floor level closet or in a mechanical room.
Valve Vertical Location and Access Duct System Design & Installation Guidelines HKV units are not designed for outdoor installation. The following application guidelines must be used when Locate the unit in an indoor area that allows enough installing HKV units. Failure to follow these guidelines...
Page 9
• replacement unit. Also inspect for and repair all air Do not use HKV units for 100% outdoor air treatment. leaks in existing ducts. Do not add hot-gas-bypass to “convert” a unit for •...
Tighten steel fittings as necessary. Table 1: Metal Hose Minimum Bend Radii Optional pressure-rated hose assemblies designed specifically for use with Heat Controller units are available. Hoses in Inches Minimum Bend Radius Similar hoses can be obtained from alternate suppliers.
IS INSTALLED IN THE DRAIN LINE, IT MUST BE LOCATED AFTER THE TRAP IN THE DIRECTION OF THE CONDENSATE FLOW and opening 46” (117 cm) Figure 3 illustrates a typical trap and vent used with HKV minimum from bottom of unit. (Vent per code) series equipment.
Hose kits are available from Heat Controller in different configurations as shown in Figure 4 for connection between the HKV Series and the piping system. The piping system should be flushed to remove dirt, piping chips, and other foreign material prior to operation.
To avoid possible injury or death due to electrical shock, wiring. Unit terminals are not designed to accept other open the power supply disconnect switch and secure it in an types of conductors. open position during installation. Table 4A: HKV Electrical Data Standard Compressor Total Voltage Min/Max...
General Line Voltage Wiring Figure 6: Typical HKV Series Line Voltage Be sure the available power is the same voltage and phase Field Wiring as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable.
Figure 8: FP1 Jumper closing valve may be required to prevent water hammer. When using an AVM -Taco Slow Closing valve on HKV Series equipment Figure 10 wiring should be utilized. The valve takes approximately 60 seconds to open (very little...
Electrical - Thermostat Typical Thermostat Selection and Wiring Practically any multi-stage contact type thermostat will work with the HKV Series. Figure 11 shows typical thermostat wiring. Thermostats with Triac outputs are not compatible with CXM boards. Figure 11: Typical Manual Changeover 2 heat/...
(1.33 l/s). Sheave setting for ARI is Selection Adjustment 3.5 turns open. The HKV Series is available with standard, low, and high Note 2: All HKV096 ratings @ 3200CFM (1510 l/s) static options. These options will substitute a different w/24GPM (1.51 l/s).
IOM Instructions HKV LArge CommerCiAL Heat Controller, Inc. Tensioning V-Belt Drives General rules of tensioning 1. Ideal tension is the lowest tension at which the belt will not slip under peak load conditions. 2. Check tension frequently during the first 24-48 hours of operation.
7.5HP Belt BX80 BX80 BX78 BX80 BX78 Note 1: D-drive is not available because standard sheave is not available in 1-3/8”. HKV Series Wet Coil to Dry Coil Conversion Table Required Required Air Coil Face Velocity (fpm) Multiplier Multiplier 1.00 1.00...
IOM Instructions HKV LArge CommerCiAL Heat Controller, Inc. Blower Performance HKV 084 Blower Performance All Data is Wet Coil Airflow (cfm) at External Static Pressure (in. wg) Airflow (SCFM) 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10...
Page 23
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions Blower Performance HKV 096 Blower Performance All Data is Wet Coil Airflow (cfm) at External Static Pressure (in. wg) Airflow (SCFM) 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10...
Page 24
IOM Instructions HKV LArge CommerCiAL Heat Controller, Inc. Blower Performance HKV 096 Blower Performance Table Continued from Previous Page All Data is Wet Coil Airflow (cfm) at External Static Pressure (in. wg) Airflow (SCFM) 0.00 0.10 0.20 0.30 0.40 0.50 0.60...
Page 25
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions Blower Performance HKV 120 Blower Performance All Data is Wet Coil Airflow (cfm) at External Static Pressure (in. wg) Airflow (SCFM) 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10...
Page 26
IOM Instructions HKV LArge CommerCiAL Heat Controller, Inc. Blower Performance HKV 120 Blower Performance Table Continued from Previous Page All Data is Wet Coil Airflow (cfm) at External Static Pressure (in. wg) Airflow (SCFM) 0.00 0.10 0.20 0.30 0.40 0.50 0.60...
Page 27
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions Blower Performance HKV 150 Blower Performance All Data is Wet Coil Airflow (cfm) at External Static Pressure (in. wg) Airflow (SCFM) 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10...
Page 28
IOM Instructions HKV LArge CommerCiAL Heat Controller, Inc. Blower Performance HKV 150 Blower Performance Table Continued from Previous Page All Data is Wet Coil Airflow (cfm) at External Static Pressure (in. wg) Airflow (SCFM) 0.00 0.10 0.20 0.30 0.40 0.50 0.60...
Page 29
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions Blower Performance HKV 168 Blower Performance All Data is Wet Coil Airflow (cfm) at External Static Pressure (in. wg) Airflow (SCFM) 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10...
Page 30
IOM Instructions HKV LArge CommerCiAL Heat Controller, Inc. Blower Performance HKV 192 Blower Performance All Data is Wet Coil Airflow (cfm) at External Static Pressure (in. wg) Airflow (SCFM) 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10...
Page 31
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions Blower Performance HKV 192 Blower Performance Table Continued from Previous Page All Data is Wet Coil 7600 1.68 1.78 1.88 2.08 2.26 2.38 2.48 2.68 2.86 2.98 3.08 3.28 3.46 3.58 3.68 3.88...
Page 32
IOM Instructions HKV LArge CommerCiAL Heat Controller, Inc. Blower Performance HKV 240 Blower Performance All Data is Wet Coil Airflow (cfm) at External Static Pressure (in. wg) Airflow (SCFM) 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10...
Page 33
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions Blower Performance HKV 240 Blower Performance Table Continued from Previous Page All Data is Wet Coil 9000 2.98 3.08 3.28 3.48 3.68 3.88 4.08 4.18 4.28 4.48 4.68 4.88 5.08 5.28 5.48 5.68...
Page 34
IOM Instructions HKV LArge CommerCiAL Heat Controller, Inc. Blower Performance HKV 300 Blower Performance All Data is Wet Coil Airflow (cfm) at External Static Pressure (in. wg) Airflow (SCFM) 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10...
Page 35
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions Blower Performance HKV 300 Blower Performance Table Continued from Previous Page All Data is Wet Coil 10600 3.68 3.88 4.08 4.28 4.48 4.68 4.88 5.08 5.28 5.48 5.68 5.88 6.18 6.38 6.58 6.78...
IOM Instructions HKV LArge CommerCiAL Heat Controller, Inc. Unit Commissioning & Operating Conditions Environment – This unit is designed for indoor The commissioning table indicates air and water installation only. Do not install in an area subject to temperatures which are suitable for initial unit...
CXM is properly set. and repair appropriately. Unit Fan: Manually rotate fans to assure free 4. Verify all strainers are in place. (Heat Controller recom- rotation and ensure blower wheel is secured to mends a strainer with a #20 stainless steel wire mesh.) motor shaft.
IOM Instructions HKV LArge CommerCiAL Heat Controller, Inc. Unit & System Checkout be cleaned using a 10% solution of dish washing Standby Pumps: Verify the standby pump is detergent. properly installed and in operating condition. Unit Controls: Verify CXM field selection options System Controls: Verify system controls function are proper and complete.
20°F [11°C] and 30°F [17°C]. Heat 5. Two factors determine the operating limits of a Heat of extraction can be calculated and compared to Controller HKV System– (a) return air temperature, and specification catalog. (b) water temperature. When any one of these factors is at f.
IOM Instructions HKV LArge CommerCiAL Heat Controller, Inc. Unit Start Up Procedure Table 7: Coax Water Pressure Drop CXM Safety Control Reset Lockout - In Lockout mode, the Status LED will begin fast flashing. The compressor relay is turned off immediately.
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions Start-up Sheet Log Installer: Complete unit and system checkout and follow unit start-up procedures in the IOM. Use this form to record unit information, temperatures and pressures during start-up. Keep this form for future reference.
IOM Instructions HKV LArge CommerCiAL Heat Controller, Inc. Unit Operating Conditions Table 8: Typical Unit Operating Pressures and Temperatures Cooling Heating Entering Water Water Voltage Suction Discharge Water Suction Discharge Super- Sub- Temp Super- Sub- Temp Temp Pressure Pressure Temp...
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions Preventive Maintenance Water Coil Maintenance – Generally water coil maintenance is not needed however, Compressor if the installation is located in a system with a known Conduct annual amperage checks to ensure amp draw...
IOM Instructions HKV LArge CommerCiAL Heat Controller, Inc. Functional Troubleshooting Fault Htg Clg Possible Cause Solution Main power Problems Green Status LED Off Check Line Voltage circuit breaker and disconnect Check for line voltage between L1 and L2 on the contactor...
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions Functional Troubleshooting Check G wiring at heat pump. Jumper G and R for fan Only Compressor Runs Thermostat wiring operation. Jumper G and R for fan operation. Check for Line voltage Check G wiring at heat pump. Jumper G and R for fan...
Model Number: ________________________ Serial Number: ________________________ IOM Instructions HKV LArge CommerCiAL Heat Controller, Inc. Date: ________________________ Packaged Unit Refrigeration Schematic Location: ________________________ Troubleshooting Form Customer: _____________________________________ Antifreeze: ________________________ Model Number: ________________________ Model#: ________________________ Serial#: ________________ Loop type: _______________ Serial Number: ________________________...
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions Follow All Warnings and Cautions in Field Conversion Options This Manual Before Attempting Conversion. Top Discharge to Straight Discharge Convertible Follow all warnings and cautions in this manual No More Ordering New Panels From the Vendor before attempting conversion.
Page 48
IOM Instructions HKV LArge CommerCiAL Heat Controller, Inc. Step 2: Remove Blockoff Air Handler as shown. Loosen belt and remove. Blockoff Air Handler Step 3: Remove bolts (4x) off blower panel. Remove bolts (4x) (2x ea. side) from blower sides.
Page 49
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions Step 4: Remove bolts (4x) and take blower glides out. Blower Glides (2x) Step 5: Attach Blower Glides to Blower BTM Load Brackets as shown. Use bottom set of holes (.203 Dia.) on Blower BTM Load Brackets.
Page 50
IOM Instructions HKV LArge CommerCiAL Heat Controller, Inc. Step 6: Stand in front and pull Blower ASM on to the ridge of the Blower Glides. Step 7: Rotate Blower ASM using Blower Glides as a guiding track. Step 8: When the Blower ASM is parallel to the floor, push the Blower ASM...
Page 51
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions Step 9: Attach Blower ASM with bolts (4x) as shown. Step 10: Remove Bower Glides (2x) and re-attach back in compressor section. Step 10...
Page 52
IOM Instructions HKV LArge CommerCiAL Heat Controller, Inc. Important! Step 11: Re-bolt Blower ASM to Blower BTM load brackets 4 ¼-20 UNC bolts, (2x) each side Re-attach belt and tighten.
Page 53
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions Step 12: Re-attach Blockoff Air Handler as shown. Blockoff Air Handler Blower Filler Panel C-Box/Motor Access Panel Compressor Panel Access Step 13: Put (3x) panels back on. Reverse steps to change a Straight Discharge to a Top Discharge.
Page 54
IOM Instructions HKV LArge CommerCiAL Heat Controller, Inc. Front Control Box/ Motor Access to Back Access Convertible • No More Dumping Charge/ Adding Charge • No More Unbrazing/ Brazing Copper • No More Heavy Lifting (Blower/ Motor ASM) • No More Flipping Coil Over What may have taken a day can now be a 15-minute job Step 1: Remove the three panels as shown.
Page 55
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions Step 3: Remove screws from Control Box (Qty 4x) and A) flip down, B) slide across and C) flip up as shown using the guide rails inside as a guide. Re-attach control box with screws.
Page 56
IOM Instructions HKV LArge CommerCiAL Heat Controller, Inc. Step 6: Move Bolt-Belt Adjustment ASM to opposite side and re-attach. Step 6 Step 7: Put Belt back on and tighten. Step 8: Place panels back on unit. Put Control Box Cover and Reverse steps to go from Motor Cover on return side.
Page 57
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions • Water In-Out Available on Either Side • Hi-Low Voltage Access on Any Side • Full Filter Frame - Bottom Access - 1”, 2”, or 4” • Filters - 1” or 2” Fiberglass and 4” Merv 8...
Page 58
IOM Instructions HKV LArge CommerCiAL Heat Controller, Inc. Condensate Drain Can Connect to Either Side of Unit TLV Units come with flex hose and 1” FPT condensate connection tied inside (shown above) Installer will untie flex hose and make an internal trap on either the left side (shown above) or on the right side.