Mitsubishi Electric FR-A7AY Instruction Manual

Hide thumbs Also See for FR-A7AY:

Advertisement

Quick Links

INVERTER
Plug-in option
FR-A7AY
INSTRUCTION MANUAL
Analog output function
Digital output function
PRE-OPERATION INSTRUCTIONS
INSTALLATION AND WIRING
PARAMETER LIST
EXTENSION ANALOG OUTPUT
DIGITAL OUTPUT
1
2
3
4
5

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric FR-A7AY

  • Page 1 INVERTER Plug-in option FR-A7AY INSTRUCTION MANUAL Analog output function PRE-OPERATION INSTRUCTIONS Digital output function INSTALLATION AND WIRING PARAMETER LIST EXTENSION ANALOG OUTPUT DIGITAL OUTPUT...
  • Page 2 Thank you for choosing this Mitsubishi Inverter plug-in option. SAFETY INSTRUCTIONS This instruction manual gives handling information and precautions for use of this equipment. Incorrect handling might cause an unexpected fault. Before using the equipment, please 1. Electric Shock Prevention read this manual carefully to use the equipment to its optimum.
  • Page 3 2. Injury Prevention 3) Usage WARNING CAUTION • Do not modify the equipment. • Apply only the voltage specified in the instruction manual to • Do not perform parts removal which is not instructed in this each terminal. Otherwise, burst, damage, etc. may occur. •...
  • Page 4: Table Of Contents

     CONTENTS  PRE-OPERATION INSTRUCTIONS Unpacking and Product Confirmation .....................1 1.1.1 Packing confirmation ............................1 1.1.2 Parts ................................2 1.1.3 Specifications ..............................3 INSTALLATION AND WIRING Pre-Installation Instructions ......................5 Installation Procedure ........................6 Wiring..............................7 PARAMETER LIST EXTENSION ANALOG OUTPUT Wiring Example ..........................11 Internal Block Diagram........................12 Terminals ............................13 Extension Analog Output Function Parameter List..............14...
  • Page 5 DIGITAL OUTPUT Internal Block Diagram........................21 Terminals ............................22 Digital Output Function Parameter List ..................23 Output Signal List ..........................24...
  • Page 6: Pre-Operation Instructions

    PRE-OPERATION INSTRUCTIONS 1.1 Unpacking and Product Confirmation Take the plug-in option out of the package, check the unit name, and confirm that the product is as you ordered and intact. This product is a plug-in option dedicated for the FR-F series.
  • Page 7: Parts

    PRE-OPERATION INSTRUCTIONS 1.1.2 Parts Terminal Mounting Front view Rear view hole block Mounting hole Connector Mounting hole Connect to the inverter option slot (Refer to page 6.) Terminal layout...
  • Page 8: Specifications

    PRE-OPERATION INSTRUCTIONS 1.1.3 Specifications (1) Output signals Voltage output (across terminals AM0-AMC) 0 to 10VMAXDC Current output (across terminals AM1-AMC) 0 to 20mADC (2) Output resolution Voltage output µ Current output (3) Output accuracy (reference value) ±10% of the full-scale output value Depends on the output signal type.
  • Page 9 MEMO...
  • Page 10: Installation And Wiring

    INSTALLATION AND WIRING 2.1 Pre-Installation Instructions Make sure that the input power of the inverter is off. CAUTION With input power on, do not install or remove the plug-in option. Otherwise, the inverter and plug-in option may be damaged.
  • Page 11: Installation Procedure

    INSTALLATION AND WIRING 2.2 Installation Procedure 1) Remove the inverter front cover. 2) Mount the hex-head screw for option mounting into the inverter screw hole (on earth plate). (size 5.5mm, tightening torque 0.56N m to 0.75N m) 3) Securely fit the connector of the plug-in option to the inverter connector along the guides.
  • Page 12: Wiring

    INSTALLATION AND WIRING 2.3 Wiring (1) Strip off the sheath of the cable to wire. Strip off the sheath about the size below. If the length of the sheath pealed is too long, a short circuit may occur among neighboring wires. If the length is too short, wires might come off. Wire the stripped cable after twisting it to prevent it from becoming loose.
  • Page 13 INSTALLATION AND WIRING (3) For wiring of the 30K(00620 (EC Version)) or less, route wires between the control circuit terminal block and front cover. If cables can not be routed between the control circuit terminal block and front cover due to the increased number of cables, remove a hook of the front cover and use a space become available.
  • Page 14: Parameter List

    PARAMETER LIST When the FR-A7AY is mounted on the inverter, the following parameters are extended. Parameter Minimum Initial Refer to Name Setting Range Number Increments alue Page 1 to 3, 5, 6, 8,(9), Analog output signal selection 10 to14,17, 21, 24, 50,...
  • Page 15 PARAMETER LIST Parameter Minimum Initial Refer to Name Setting Range Number Increments alue Page DO0 output selection 0 to 5, (7), 8, 10 to 19, 25, 26, 45 to 47, 64, 70, DO1 output selection (71 to 78), 86 to 96, 98, DO2 output selection 99, 100 to 105, (107), 21 and...
  • Page 16: Extension Analog Output

    (AM0) and current output terminal (AM1). Connect the voltmeter or ammeter as shown below: Inverter Motor MCCB Power supply (Voltmeter) 0 to 10VDC FR-A7AY (Ammeter) 0 to 20 mADC CAUTION The wiring length between the FR-A7AY and the voltmeter/ammeter should be 10m maximum.
  • Page 17: Internal Block Diagram

    EXTENSION ANALOG OUTPUT 4.2 Internal Block Diagram The following is the internal block diagram about the FR-A7AY analog output function. Voltage amplifier Controller Connector Current amplifier Common to AM0/AM1...
  • Page 18: Terminals

    EXTENSION ANALOG OUTPUT 4.3 Terminals Terminal Symbol Terminal Name Description Voltage output Connect a DC voltmeter (10VDC). terminal Current output Connect a DC ammeter (20mADC). terminal Common Common to AM0 and AM1 terminal Y0 to Y6 Used for analog output function. (Refer to page 21 ) NC (empty) Do not use.
  • Page 19: Extension Analog Output Function Parameter List

    EXTENSION ANALOG OUTPUT 4.4 Extension Analog Output Function Parameter List Parameter Minimum Initial Name Setting Range Number Increments Value 1 to 3, 5, 6, 8, Analog output signal selection (9), 10 to 14, 17, 21, 24, 50, 52, 53 Setting for zero analog output 0 to 100% Setting for maximum analog output 0 to 100%...
  • Page 20: Adjustment Procedure

    EXTENSION ANALOG OUTPUT 4.5 Adjustment Procedure 4.5.1 Setting of analog output signal voltage/current switchover (Pr. 309) Use Pr. 309 Analog output signal voltage/current switchover to select whether to output the same signal or different signals from terminal AM0 (voltage output) and terminal AM1(current output). Parameters Pr.
  • Page 21: Calibration Of Meter

    EXTENSION ANALOG OUTPUT 4.5.2 Calibration of meter (1) Outputting the same select signals from terminals AM0 and AM1 (Pr. 309 = 0 or 10) START Connect a DC voltmeter (or DC ammeter) across At this time, check that the polarity is correct terminals AM0 (or terminal AM1) and AMC.
  • Page 22 EXTENSION ANALOG OUTPUT (2) Outputting different select signals from terminals AM0 and AM1 (Pr. 309 = 1 or 11) START Connect a DC voltmeter (or DC ammeter) across terminals AM0 (or terminal AM1) At this time, check that the polarity is correct and AMC.
  • Page 23: Output Signal Setting

    EXTENSION ANALOG OUTPUT 4.5.3 Output signal setting Set the output signals to be monitored. Set Pr. 306 to output the same signal from terminals AM0 and AM1 and Pr. 306 and Pr. 310 to output different signals. For details of signal definitions, refer to Pr. 54 and Pr. 158 of the inverter manual (applied).
  • Page 24: Analog Signal Adjustment [Pr. 307, Pr. 308, Pr. 311, Pr. 312]

    EXTENSION ANALOG OUTPUT 4.5.4 Analog signal adjustment [Pr. 307, Pr. 308, Pr. 311, Pr. 312] Use Pr. 307 or Pr. 311 to set for zero analog output (meter points 0). In addition, use Pr. 308 or Pr. 312 to set for maximum analog output (full-scale). Use Pr.
  • Page 25: Instructions

    EXTENSION ANALOG OUTPUT 4.6 Instructions (1) A voltmeter having smaller internal impedance (or an ammeter having larger internal impedance) than the value indicated in the Specifications may not deflect to full-scale and may not be calibrated. (2) When calibrating a meter which has a small full-scale value, set the output of terminal AM0 (or AM1) to the minimum without the meter connected.
  • Page 26: Digital Output

    DIGITAL OUTPUT 5.1 Internal Block Diagram The following is the internal block diagram about the FR-A7AY digital output function Connector Controller Common to Y0-T6...
  • Page 27: Terminals

    DIGITAL OUTPUT 5.2 Terminals By setting the Pr. 313 to Pr. 319 values, output signals available with an inverter as standard can be output from the open collector terminals. (1) Open collector output specifications: Permissible load 24V, 0.1ADC (2) The circuit logic is the same as that of the inverter. For details of changing the control logic, refer to the inverter manual (basic).
  • Page 28: Digital Output Function Parameter List

    DIGITAL OUTPUT 5.3 Digital Output Function Parameter List Parameter Number Name Initial Value Setting Range DO0 output selection 9999 0 to 5, (7), 8, 10 to 19, 25, 26, DO1 output selection 9999 45 to 47, 64, 70, (71 to 78), 86 DO2 output selection 9999 to 96, 98, 99,...
  • Page 29: Output Signal List

    DIGITAL OUTPUT 5.4 Output Signal List For details of signal definitions, refer to Pr. 190 to Pr. 196 Output terminal function selection of the inverter manual (applied). Setting Setting Signal Signal Function Function Positive Negative Positive Negative Name Name Logic Logic Logic Logic...
  • Page 30 DIGITAL OUTPUT Setting Setting Signal Signal Function Function Positive Negative Positive Negative Name Name Logic Logic Logic Logic Commercial-power supply side  Life alarm motor 2 connection RO2 Commercial-power supply side  Input MC shut off signal motor 3 connection RO3 Commercial-power supply side Energy saving average value ...
  • Page 31 REVISIONS *The manual number is given on the bottom left of the back cover. Print Date *Manual Number Revision May, 2004 IB(NA)-0600165ENG-A First edition...