Electrical installation • Instalación eléctrica
Installation électrique • Instalação eléctrica
5
4
2
3
7
KL 2
8
Vac - voltages
KL1
KL2
4
3
2
3
2
1
9
10
10
10
9
11
KL 1
KL 5
(optional)
KL 2
1
Vdc - voltage
KL5
KL4
6
5
4
3
1
2
9
*)
12
6
9
10
KL 4
(optional with 2 or 6 contacts
opcional de 2 ó 6 poles
en option, 2 ou 6 pôles
opcional bibolar ou 6 poles)
KL2
3
2
1
2
1
10
BEKOMAT 21 PRO
Note before wiring:
• The mains voltage must corre-
spond to the permissible voltage
on the type plate (1)!
• Please ensure that the instal-
lation is carried out according to
the valid regulations.
• Please assign terminals as indi-
cated!
• Remove screws (5) and lift off hou-
sing top (4) paying attention to the
cable.
• Unplug connector (7) from terminal
on control PCB (8).
• Fit board holder (2) with power sup-
ply board into the housing top (4).
Connect power supply
• Unscrew union nut (6) and remove
blanking disk (12)
• Guide a 3-core cable (9) for power
supply through screwed cable fitting
and connect to board terminal KL1
or KL4.
• Guide a 5-pole cable (10) for poten-
tial-free contact and for external test
button through screwed cable fit-
ting.
Terminal assignment in the case
of Vac devices: L = phase conductor
(black), N = neutral conductor (blue),
PE = protective earth conductor
(green/yellow)
Note: There is no metallic isola-
tion between terminals KL4.1-6 or
KL 5.1-2 and the condensate area.
In the case of 24 Vdc operation, do not
connect +24 Vdc to frame because
the internal housing potential of the
device is negative.
*) When supplying several BEKO-
MAT 21 units simultaneosusly from a
single 24 Vdc source we recommend:
connect operating voltage preferably
to KL4.4 + KL4.5 instead of KL4.1 +
KL4.2 while observing the polarity.
Potential-free alarm contact
KL2.3-2 N.C.–COM:
Contact closed during malfunction or
power failure (fail-safe principle).
KL2.1-2 N.O.–COM:
Contact closed during normal operation.
External test (optional)
KL5.1-2 oder KL4.2-4 0V–IN1: Con-
tacts connected
= test active = discharge
Contacts open = test inactive
Assembly
• Pull cables (9+10) tight and screw
down cable fittings (6)
• Move board holder (2) with power
supply board upwards (must click
into place).
• Plug connector (7) to terminal on
control PCB (8).
• Slide housing top (4) with board
holder (2) into the guiding grooves.
• Tighten the screws (5).