Appendix 1 : Product.xml File; Appendix 2 : Configuration_Descriptor.xml File - Dell PowerEdge UPS 500T Notice

Product requirements - dell ups management card
Hide thumbs Also See for PowerEdge UPS 500T:
Table of Contents

Advertisement

5. Appendix 1 : product.xml file

<?xml version="1.0" encoding="UTF-8" ?>
- <PRODUCT_INFO name="Network Management Card" type="Mosaic 4M 16M" version="01.01.007">
- <SUMMARY>
<HTML_PROPERTIES_PAGE url="default.htm" security="none" />
<XML_SUMMARY_PAGE url="upsprop.xml" security="none" />
<CENTRAL_CFG url="config.xml" security="none" />
<CSV_LOGS url="logevent.csv" dateRange="no" eventFiltering="no" security="none" />
</SUMMARY>
- <ALARMS>
<SUBSCRIPTION url="subscribe.cgi" security="basic" />
<BROADCAST port="4680" />
</ALARMS>
- <MANAGEMENT>
<XML_MANAGEMENT_PAGE name="Set Card Time" id="SetTime" url="management/set_time.xml" security="none" />
<MANAGEMENT_PAGE name="Access Control" id="AccessControl" url="ups_cont.htm" security="none" />
</MANAGEMENT>
- <UPS_DATA>
<GET_CONFIG url="configuration_descriptor.xml" security="none" mode="FORM" />
<SET_CONFIG url="Forms/set_obj_2" security="basic" mode="FORM" />
<GET_OBJECT url="get_object.xml" security="none" mode="FORM" />
<SET_OBJECT url="Forms/set_obj_1" security="basic" mode="FORM" />
</UPS_DATA>
</PRODUCT_INFO>

6. Appendix 2 : configuration_descriptor.xml file

<?xml version="1.0" encoding="UTF-8" ?>
-
<SYSTEM_CONFIG
version="1">
-
<GROUP
id="Network">
<ITEM
object="System.Network.HostName" type="String:49" access="WO" default="upsXX" restart="TRUE" version="1" />
<ITEM
object="System.Network.IPAddress" type="IPv4" access="WO" default="192.168.1.2" restart="TRUE" version="1" />
<ITEM
object="System.Network.IPMask" type="IPv4" access="RW" default="255.255.0.0" restart="TRUE" version="1" />
<ITEM
object="System.Network.IPGateway" type="IPv4" access="RW" default="0.0.0.0" restart="TRUE" version="1" />
<ITEM
object="System.Network.DomainName" type="String:49" access="RW" default="ups.domain.com" version="1" />
<ITEM
object="System.Network.DHCP" type="Boolean" access="RW" default="1" restart="TRUE" version="1" />
<ITEM
object="System.Network.PrimaryDNS" type="IPv4" access="RW" default="0.0.0.0" version="1" />
<ITEM
object="System.Network.SecondaryDNS" type="IPv4" access="RW" default="0.0.0.0" version="1" />
<ITEM
object="System.Network.SmtpServer.HostName" type="String:49" access="RW" default="smtpserver" version="1" />
<ITEM
object="System.Network.SmtpServer.Authentication" type="Boolean" access="RW" default="0" version="1" />
<ITEM
object="System.Network.SmtpServer.Login" type="String:49" access="RW" default="smtplogin" version="1" />
<ITEM
object="System.Network.SmtpServer.Password" type="Password:49" access="RW" default="smtppwd" version="1" />
</GROUP>
-
<GROUP
id="System">
<ITEM
object="System.Contact" type="String:49" access="RW"
<ITEM
object="System.Location" type="String:31" access="RW"
<ITEM
object="System.Language" type="List:AUTO,FRE,ENG,SPA,GER,ITA" access="RW" default="AUTO" version="1" />
<ITEM
object="System.History.Log.Interval" type="Time:10..2147483647" unit="s" access="RW" default="60" version="1"
/>
<ITEM
object="System.Environment.Log.Interval"
version="1" />
</GROUP>
-
<GROUP
id="Shutdown.Outlet[1]">
<ITEM
object="System.Outlet[1].iName" type="String:20" access="RW" default="Inverter" version="1" />
<ITEM
object="System.ShutdownDuration" type="Time:120..9999" unit="s" access="RW" default="120" version="1" />
<ITEM
object="System.ShutdownTimerSelected" type="Boolean" access="RW" default="0" version="1" />
<ITEM
object="System.ShutdownTimer" type="Time:0..5999940/60" unit="m" access="RW" default="1800" version="1" />
<ITEM
object="System.RunTimeToEmptyLimit" type="Time:0..99999" unit="s" access="RW" default="180" version="1" />
<ITEM
object="System.RemainingCapacityLimit" type="Integer:0..100" unit="%" access="RW" default="20" version="1" />
<ITEM
object="System.RestartLevel" type="Integer:0..100" unit="%" access="RW" default="0" version="1" />
</GROUP>
-
<GROUP
id="Shutdown.Outlet[2]">
5 |
P a g e
default="Computer Room
default="Computer
type="Time:10..2147483647"
N M C D e l l M 2 M p r o t o c o l ( X M L ) – 1 . 1
Manager" version="1" />
Room" version="1" />
unit="s"
access="RW"
default="300"

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups management card