Summary of Contents for Hitachi SJ-DN2

  • Page 1: Table Of Contents

    SJ-DN2 (DeviceNet Option) INSTRUCTION MANUAL Thank you for purchase of “HITACHI INVERTER”. This manual explains about treatment of “SJ-DN2 (DeviceNet Option)”. By reading this manual and an instruction manual of inverter use practically for installation, maintenance, and inspection. After reading this manual, keep it handy for future reference.
  • Page 2 (EDS: Electronic Data Sheet) (NOTE): Please use the corresponding EDS file after confirmed the inverter series because SJ700 and SJ300/L300P have their own EDS file. EDS file can be downloaded from the home page as below. http://www.hitachi-ies.co.jp http://securesite.jp/ODVA/TSP/ Revision History Table Revision contents The date of issued Manual No.
  • Page 3: Safety Precautions

    SAFETY PRECAUTIONS SAFETY PRECAUTIONS Carefully read this manual and all of the warning labels attached to the inverter before installing, operating, maintaining, inspecting. Safety precautions are classified into “Warning” and “Caution” in this manual. Indicates a potentially hazardous situation which, if not avoided, can result in serious WARNING injury or death.
  • Page 4 SAFETY PRECAUTIONS WARNING Wiring: Wiring work shall be carried out by electrical experts. Otherwise, there is a danger of electric shock, fire and/or damage of product. Implement wiring after checking that the power supply is off. Otherwise, there is a danger of electric shock and/or fire. Operating: Be sure not to touch the surface or the terminal of option board while energizing.
  • Page 5: Chapter1 Introduction

    1.2.1 REQUIRE WHILE INQUIRING If inquiry of breakage, question, damage etc. is needed, please tell the following information to the supplier you ordered or the nearest Hitachi Distributor. (1) Type(SJ-DN2) (2) Manufacturing number (Item of label, that labeled surface of printed board. SJ-DN2 XXX )
  • Page 6: Appearance And Names Of Parts

    CHAPTER 1 INTRODUCTION 1.3 Outline of product SJ-DN2 is DeviceNet communication board for SJ700/SJ300/L300P series inverter. SJ-DN2 conforms to open field Network DeviceNet and it activates as slave function (Group 2 only server). SJ-DN2 also conforms ODVA’s certification. (SJ-DN2 has been tested by ODVA's authorized Independent Test Lab and found to comply with ODVA Conformance Test (Composite Test Revision)20.) The following functions are available via DeviceNet communication function by installing SJ-DN2 to SJ700/SJ300/L300P series.
  • Page 7 CHAPTER 1 INTRODUCTION 1.5 DeviceNet Version Supported 1.5.1 SJ300/L300P Series SJ-DN2 can be used for the following production number(MFG No) of SJ300/L300P series. After Manufacturing number : XX8KXXXXXXXXXXXX SJ300-0.4-55kW / L300P-11-75kW supported XXEMXXXXXXXXXXXX SJ300-75-132kW / L300P-90-132kW supported (Note) Production number (MFG No) is written in specifications label on main body of SJ300/L300P series. Refer to figure 1-2, figure 1-3.
  • Page 8: Chapter2 Installation Method Of Printed Board

    CHAPTER 2 INSTALLATION METHOD OF PRINTED BOARD 2.1 Mounting method of option board Figure 2-1 describes how to mount the option board to the option port 1 or 2. There are four holes on the option board, match the two of them with the screw holes on the option port 1 or 2.
  • Page 9: Chapter3 Wiring, Connecting

    CHAPTER 3 WIRING, CONNECTING 3.1 Connection for DeviceNet connector SJ-DN2 has a Pluggable open connector (Male contacts), and a Network connector (Female contacts) attached. The inverter and attached connector have a seal which is color coordinated to correspond to the DeviceNet cable.
  • Page 10 7. Basic components for construction of DeviceNet application system are shown as bellow. Refer to the master’s description manuals when DeviceNet Network system comes into operation. Inverter Inverter HITACHI HITACHI Multiple Node branching drop line. Configurater (PC) DeviceNet Master UNIT (PLC)
  • Page 11 CHAPTER 4 SETTING 4.1 Setting methods of Baud rate and MAC ID Follow the procedure as below to set Baud rate in DeviceNet and MAC ID, reset the power supply after changing the setting (setting will be reflected after resetting power supply.). Initialization Baud rate: 125kbps, Initialization MAC ID: 0.
  • Page 12: Chapter4 Setting

    CHAPTER 4 SETTING 4.3 Explanation of additional parameters The following information provides the explanation of additional parameters which are necessary to be used for SJ-DN2. 4.3.1 P044 (DeviceNet communication watchdog timer) Set the allowable time that is an interval of polled I/O from DeviceNet master when the inverter is running. When the timeout occurs, the inverter’s behavior is as set in command P045.
  • Page 13: Chapter5 Operation

    CHAPTER 5 OPERATION 5.1 Operate with Frequency command [Hz] The following information indicates the explanation of the inverter control data at P046: 100 and P047: 101. See Chapter 6 about explanation of Polled I/O message. Explanation on each data frame [Output data frame] (1) Stop command.
  • Page 14 CHAPTER 5 OPERATION 5.2 Operate with Rotational speed command [min Following information indicate the example of the inverter control data at P046: 21, P047: 71 and P049: 4. See Chapter 6 about explanation of Polled I/O message. Explanation on each data frame. [Output frame] (1) Stop command.
  • Page 15: Chapter6 Devicenet Communication Function

    CHAPTER 6 DEVICENET COMMUNICATION FUNCTION 6.1 Feature of DeviceNet communication function SJ-DN2 conforms to open field Network DeviceNet and activates as slave function (Group 2 only server). There are two methods to communicate with the master, one is polled I/O message communication and the other is explicit message communication.
  • Page 16 CHAPTER6 DEVICENET COMMUNICATION FUNCTION 6.3 Details of Polled I/O communication 6.3.1 Basic I/O instance This I/O instance is standard I/O instance, which is defined by AC drive profile in DeviceNet. Master to SJ-DN2: Instance20 (P046: 20) Byte Bit7 Bit6 Bit5 Bit4 Bit3 Bit2...
  • Page 17 CHAPTER 6 DEVICENET COMMUNICATION FUNCTION 6.3.2 Expansive I/O Instance This I/O instance is standard I/O instance, which is defined by AC drive profile in DeviceNet. Master to SJ-DN2: Instance21 (P046: 21) Byte Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 Fault NetRef NetCtrl...
  • Page 18 CHAPTER6 DEVICENET COMMUNICATION FUNCTION SJ-DN2 to Master: Instance71 (P047: 71) Byte Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 Ref From Ctrl From Running2 Running1 Ready Warning Faulted Reference (Rev) (Fwd) Drive Status Speed Actual (Low Byte) Speed Actual (High Byte) Data Contents It indicates the inverter is in a fault detecting state.
  • Page 19 CHAPTER 6 DEVICENET COMMUNICATION FUNCTION 6.3.3 Hitachi inverter I/O Instance This I/O instance is able to control the operation control, which is necessary to Hitachi inverters. Master to SJ-DN2: Instance100 (P046: 10) Byte Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1...
  • Page 20 CHAPTER6 DEVICENET COMMUNICATION FUNCTION SJ-DN2 to Master: Instance101 (P047: 101) Byte Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 Input Input Input Running2 Running1 Terminal Terminal Terminal Faulted Reference (Rev) (Fwd) 3 State 2 State 1 State Drive Status Speed Actual (Low Byte) Speed Actual (High Byte) Output current (Low Byte) Output current (High Byte)
  • Page 21 CHAPTER 6 DEVICENET COMMUNICATION FUNCTION Data Contents It indicates the inverter’s output current monitor. Output current Monitor range:0 to 6553.5A, Magnification:10 times, Receiving data:0 to FFFF(Hex) Following codes are latest trip history. 00:No trip 01:Over current protection (at constant speed) 02:Over current protection (at deceleration) 03:Over current protection (at acceleration) 04:Over current protection (at the other)
  • Page 22 6.4 Detail of DeviceNet profile 6.4.1 Overall Specification General DeviceNet specification CIP Volume I –Release3.4 Device data CIP Volume III-Release1.5 DeviceNet Adaptation Vendor name Hitachi Industrial 74(SJ300/L300P) / Equipment Systems Co., 1112(SJ700) Ltd. DeviceNet profile name Slave AC Drive Profile No=2 Product Catalog NO.
  • Page 23 CHAPTER 6 DEVICENET COMMUNICATION FUNCTION 6.4.4 Assembly Object (ID=4 Hex) Attribute Access rule Type of data Initial data Instance0 Not supported Instance20 DATA Get/Set 4 Bytes Instance21 DATA Get/Set 4 Bytes Instance70 DATA 4 Bytes Instance71 DATA 4 Bytes Instance100 DATA Get/Set 8 Bytes...
  • Page 24 CHAPTER6 DEVICENET COMMUNICATION FUNCTION 6.4.7 Control Supervisor Object (ID=29 Hex) Attribute Access rule Data type Initial data Instance0 Revision WORD 0001 Instance1 Run1 Get/Set BYTE Run2 Get/Set BYTE NetCtrl Get/Set BYTE State BYTE Running1 BYTE Running2 BYTE Ready BYTE Faulted BYTE Warning BYTE...
  • Page 25: Chapter7 Countermeasure For Abnormality

    CHAPTER7 COUNTERMEASURE FOR ABNORMALITY 7.1 Trip display When the inverter is in a tripped state, the inverter displays an error code (See table below). The trip history monitor (d081 to d086) also displays the same error code as the inverter. Trip code Inverter’s running condition of trip detected 7.2 Protection function list...
  • Page 26 CHAPTER7 COUNTERMEASURE FOR ABNORMALITY 7.4 LED display and Countermeasure Following states are indicated by module LED and Network LED. MOD (Module status) LED: It indicates Inverter condition. NET (Network status) LED: It indicates Network condition. Color Explanation Countermeasure Green The inverter is in normal condition lamp is ON Green The inverter is in standby condition.
  • Page 27 CHAPTER7 COUNTERMEASURE FOR ABNORMALITY 7.5 Other notes When SJ-DN2 is installed and the Inverter’s setting is below, the behavior of the inverter will be as following by MFG No. Operating mode select (A002) setting: 02(REM) (1) before MFG NO. : XXEGXXXXXXXXXXXX The Inverter will be automatically reset from fault status when it occurs trip while driving from DeviceNet command.
  • Page 28: Appendix Parameter Object Lists

    Trip Count (Param17) 0 to 65530 d080 E01.X to E79.X (E??:Trip cause, X:running condition) Trip 1 Cause (Param18) d081 See 6.3.3 Hitachi inverter I/O Instance(Instance 101) Trip 1 frequency (Param19) 0.00 to 400.00(Hz) d081 Trip 1 Current (Param20) 0.0 to 999.9(A)
  • Page 29 Trip 4 P-ON time (Param41) 0 to 999999(hr) d084 E01.X to E79.X (E??:Trip cause, X:running condition) Trip 5 Cause (Param42) d085 See 6.3.3 Hitachi inverter I/O Instance(Instance 101) Trip 5 frequency (Param43) 0.00 to 400.00(Hz) d085 Trip 5 Current (Param44) 0.0 to 999.9(A)
  • Page 30 APPENDIX PARAMETER OBJECT LISTS Magnifi- Access Com- Function Inst Attr Size Monitoring/Setting Range cation rule mand 00(Invalid)/01(O/OI-no reverse)/ O2 Function Sel (Param67) Get/Set A006 02(O/OI-reverse) O Start Freq Set (Param68) 0.00 to 400.00(Hz) Get/Set A011 O End Freq Set (Param69) 0.00 to 400.00(Hz) Get/Set A012...
  • Page 31 APPENDIX PARAMETER OBJECT LISTS Magnifi- Access Com- Function Inst Attr Size Monitoring/Setting Range cation rule mand Jump Frequency 1 (Param107) 0.00 to 400.00(Hz) Get/Set A063 Jump Freq Width 1 (Param108) 0.00 to 10.00(Hz) Get/Set A064 Jump Frequency 2 (Param109) 0.00 to 400.00(Hz) Get/Set A065 Jump Freq Width 2 (Param110)
  • Page 32 APPENDIX PARAMETER OBJECT LISTS (3) Extend Group B object Class ID=103 Magnifi- Access Function Inst Attr Size Monitoring/Setting Range cation rule mand 00(Trip)/01(0Hz Start)/ Restart Mode Sel (Param143) 02(Synchronize)/ Get/Set b001 03(Sync& Stop& Trip) Allowable UVTime (Param144) 0.3 to 1.0(s) Get/Set b002 Restart WaitTime (Param145)
  • Page 33 APPENDIX PARAMETER OBJECT LISTS Magnifi- Access Function Inst Attr Size Monitoring/Setting Range cation rule mand FM Adjustment (Param181) 0 to 255 Get/Set b081 Start Frequency (Param57) 0.1 to 9.99(Hz) Get/Set b082 0.5 to 15.0(kHz) (~55KW) CarrierFrequency (Param182) Get/Set b083 0.5 to 10.0(kHz) (75~132KW) 00(Trip history)/01(Data)/ Initialize Mode (Param183) Get/Set...
  • Page 34 APPENDIX PARAMETER OBJECT LISTS (5) Extend Group C object Class ID=105 Magnifi- Access Function Inst Attr Size Monitoring/Setting Range cation rule mand 01(RV)/02(CF1)/03(CF2)/04(CF3)/ 05(CF4)/06(JG)/07(DB)/08(SET)/ 09(2CH)/11(FRS)/12(EXT)/ 13(USP)/14(CS)/15(SFT)/16(AT)/ 17(SET3)/18(RS)/20(STA)/ 21(STP)/22(F/R)/23(PID)/ 24(PIDC)/26(CAS)/27(UP)/ Digital Input 1 (Param216) Get/Set C001 28(DWN)/29(UDC)/31(OPE)/ 32(SF1)/33(SF2)/34(SF3)/35(SF4)/ 36(SF5)/37(SF6)/38(SF7)/ 39(OLR)/40(TL)/41(TRQ1)/ 42(TRQ2)/43(PPI)/44(BOK)/ 45(ORT)/46(LAC)/47(PCLR)/ 48(STAT)/255(NO) Digital Input 2 (Param217)
  • Page 35 APPENDIX PARAMETER OBJECT LISTS Magnifi- Access Function Inst Attr Size Monitoring/Setting Range cation rule mand Dig Out13 NO/NC (Param244) 00(NO)/01(NC) Get/Set C033 Dig Out14 NO/NC (Param245) 00(NO)/01(NC) Get/Set C034 Dig Out15 NO/NC (Param246) 00(NO)/01(NC) Get/Set C035 AlarmReray NO/NC (Param247) 00(NO)/01(NC) Get/Set C036 OLAlarmSignalSel (Param248)
  • Page 36 APPENDIX PARAMETER OBJECT LISTS (7) Extend Group H object Class ID=107 Magnifi- Access Function Inst Attr Size Monitoring/Setting Range cation rule mand 00(Invalid)/01(Valid(not rotate))/ AutotuningSelect (Param283) Get/Set H001 02(Valid(rotate)) 00(Standard Motor)/ Motor Constant (Param284) Get/Set H002 01(Offline Auto)/02(Online Auto) 00(Standard Motor)/ 2nd Motor Constant (Param351) Get/Set H202...
  • Page 37: Assembly

    APPENDIX PARAMETER OBJECT LISTS (8) Extend Group P object Class ID=109 Magnifi- Access Function Inst Attr Size Monitoring/Setting Range cation rule mand OP1 OpeSel OnErr (Param306) 00(Trip)/01(Run) Get/Set P001 OP2 OpeSel OnErr (Param307) 00(Trip)/01(Run) Get/Set P002 FeedbackOPenable (Param308) 00(Invalid)/01(Valid) Get/Set P010 Encoder Pulse No (Param309) 128 to 65000...
  • Page 38 -1073741823 to +1073741823 (pls) (Param388) Position feedback monitor d030 -1073741823 to +1073741823 (pls) (Param389) Trip Counter (Param17) 0 to 65535 d080 E01.X to E79.X (E??:Trip cause, X:running condition) Trip 1 Cause (Param18) d081 See 6.3.3 Hitachi inverter I/O Instance(Instance 101)
  • Page 39 Trip 1 P-ON time (Param23) 0 to 999999(hr) d081 E01.X to E79.X (E??:Trip cause, X:running condition) Trip 2 Cause (Param24) d082 See 6.3.3 Hitachi inverter I/O Instance(Instance 101) Trip 2 frequency (Param25) 0.00 to 400.00(Hz) d082 Trip 2 Current (Param26) 0.0 to 999.9(A)
  • Page 40 APPENDIX PARAMETER OBJECT LISTS Magnifi- Access Com- Function Inst Attr Size Monitoring/Setting Range cation rule mand BRD load factor monitoring d103 0.0 to 100.0(%) (Param390) Electronic thermal overload d104 0.0 to 100.0(%) monitoring (Param391) Frequency Setting (Param60) 0.00 to 400.00(Hz) Get/Set F001 Accel Time 1 (Param61)
  • Page 41 APPENDIX PARAMETER OBJECT LISTS Magnifi- Access Com- Function Inst Attr Size Monitoring/Setting Range cation rule mand 0.00, “Start Frequency” to Multi-Speed 7 (Param82) Get/Set A027 “n-th Max Frequency”(Hz) 0.00, “Start Frequency” to Multi-Speed 8 (Param83) Get/Set A028 “n-th Max Frequency”(Hz) 0.00, “Start Frequency”...
  • Page 42 APPENDIX PARAMETER OBJECT LISTS Magnifi- Access Com- Function Inst Attr Size Monitoring/Setting Range cation rule mand 0.00,”Start Frequency” to Lower Freq Limit (Param58) Get/Set A062 “Upper Freq Limit” (Hz) 0.00,”Start Frequency” to 2ndLowerFRQLimit (Param328) Get/Set A262 “2ndUpper Freq Limit” (Hz) Jump Frequency 1 (Param107) 0.00 to 400.00(Hz) Get/Set...
  • Page 43 APPENDIX PARAMETER OBJECT LISTS Magnifi- Access Com- Function Inst Attr Size Monitoring/Setting Range cation rule mand OI StartMode Sel (Param136) 00(Set Frequency)/01(0Hz) Get/Set A105 O2 StartFreq Set (Param137) -400.00 to 400.00(Hz) Get/Set A111 O2 End Freq Set (Param138) -400.00 to 400.00(Hz) Get/Set A112 O2 Start Rate (Param139)
  • Page 44 APPENDIX PARAMETER OBJECT LISTS Magnifi- Access Function Inst Attr Size Monitoring/Setting Range cation rule mand 00(Tripping)/01(Starting with 0 Hz)/ 02(Starting with matching frequency)/ Selection of retry after tripping 03(Tripping after deceleration and Get/Set b008 (Param409) stopping with matching frequency)/ 04(Restarting with active matching frequency) Selection of retry count after Get/Set...
  • Page 45 APPENDIX PARAMETER OBJECT LISTS Magnifi- Access Function Inst Attr Size Monitoring/Setting Range cation rule mand 00(All Display)/ 01(Each Func Display)/ Display Select (Param167) 02(User setting)/ Get/Set b037 03(Data comparison display)/04(basic display) 00(Screen displayed when the STR Initial-screen selection key was pressed last)/ Get/Set b038 (Param417)
  • Page 46 APPENDIX PARAMETER OBJECT LISTS Magnifi- Access Function Inst Attr Size Monitoring/Setting Range cation rule mand 0.5 to 15.0(kHz) (~55KW) CarrierFrequency (Param180) Get/Set b083 0.5 to 10.0(kHz) (75~132KW) 00(Trip history)/01(Data)/ Initialize Mode (Param181) Get/Set b084 02(Trip history & Data) Initial Data Sel (Param182) 00(Japan)/01(Europe)/02(USA) Get/Set b085...
  • Page 47 APPENDIX PARAMETER OBJECT LISTS Support service Service name Code Get_Attribute_Single H’0E Set_Attribute_Single H’10 (5) Extend Group C object Class ID=105 Magnifi- Access Function Inst Attr Size Monitoring/Setting Range cation rule mand 01(RV)/02(CF1)/03(CF2)/ 04(CF3)/05(CF4)/06(JG)/07(DB)/ 08(SET)/ 9(2CH)/11(FRS)/ 12(EXT)/13(USP)/14(CS)/15(SFT)/ 16(AT)/17(SET3)/18(RS)/20(STA)/ 21(STP)/22(F/R)/23(PID)/ 24(PIDC)/26(CAS)/27(UP)/ 28(DWN)/29(DWN)/31(OPE)/ 32(SF1)/33(SF2)/34(SF3)/35(SF4)/ 36(SF5)/37(SF6)/38(SF7)/ 39(OLR)/40(TL)/41(TRQ1)/...
  • Page 48 APPENDIX PARAMETER OBJECT LISTS Magnifi- Access Function Inst Attr Size Monitoring/Setting Range cation rule mand AlarmRerayOutput (Param236) Same above Get/Set C026 00(Output Frequency)/ 01(Output Current)/ 02(Output Torque)/ 03(Digital Outp-frq)/ 04(Output Voltage)/ 05(Input Power)/ FM Mode Select (Param237) Get/Set C027 06(Therm Load Rate)/ 07LAD frequency)/ 08(Digital Current Monitoring)/ 09(Motor Temperature)/...
  • Page 49 APPENDIX PARAMETER OBJECT LISTS Magnifi- Access Function Inst Attr Size Monitoring/Setting Range cation rule mand 0 to 200(%) (~55KW) OV-TRQ FW-R (Param256) Get/Set C058 0 to 180(%) (75~132KW) (constant current 1%) Thermal Warn Lvl (Param257) 0 to 100(%) Get/Set C061 AlarmMode Select (Param258) 00(Invalid)/01(3bit)/02(4bit) Get/Set...
  • Page 50 APPENDIX PARAMETER OBJECT LISTS Magnifi- Access Com- Function Inst Attr Size Monitoring/Setting Range cation rule mand Output 14 on-delay time Get/Set C136 0.0 to 100.0(s) (Param457) Output 14 off-delay time Get/Set C137 0.0 to 100.0(s) (Param458) Output 15 on-delay time Get/Set C138 0.0 to 100.0(s)
  • Page 51 APPENDIX PARAMETER OBJECT LISTS Magnifi- Access Com- Function Inst Attr Size Monitoring/Setting Range cation rule mand Same as the settings of C021 to Logical output signal 6 selection Get/Set C158 C026 2 (Param479) (except those of LOG1 to LOG6) Logical output signal 6 operator Get/Set C159 00(AND)/01(OR)/02(XOR)
  • Page 52 APPENDIX PARAMETER OBJECT LISTS Magnifi- Access Function Inst Attr Size Monitoring/Setting Range cation rule mand 2nd MotorPole Select(Param346) 0(2P)/1(4P)/2(6P)/3(8P)/4(10P) Get/Set H204 Speed Response (Param281) 0.001 to 65.535 1000 Get/Set H005 2nd Speed Response(Param347) 0.001 to 65.535 1000 Get/Set H205 StabilizedFactor (Param282) 0 to 255 Get/Set H006...
  • Page 53 APPENDIX PARAMETER OBJECT LISTS Magnifi- Access Function Inst Attr Size Monitoring/Setting Range cation rule mand Feed-ForwardGain (Param313) 0.00 to 655.35 Get/Set P022 Pos-CtrlLoopGain (Param314) 0.00 to 100.00 Get/Set P023 Position bias setting (Param494) -2048 to 2048 Get/Set P024 Compensation R2 (Param315) 00(Invalid)/01(Valid) Get/Set P025...
  • Page 54 APPENDIX PARAMETER OBJECT LISTS Magnifi- Access Function Inst Attr Size Monitoring/Setting Range cation rule mand Position setting range reverse Multistage position setting side to forward side Get/Set P063 3(Param512) (upper 4 digits including “-“) Position setting range reverse Multistage position setting Get/Set P064 side to forward side...
  • Page 55 APPENDIX PARAMETER OBJECT LISTS Magnifi- Access Function Inst Attr Size Monitoring/Setting Range cation rule mand Easy sequence user parameter Get/Set P110 0 to 65535 U(10) (Param533) Easy sequence user parameter Get/Set P111 0 to 65535 U(11) (Param534) Easy sequence user parameter Get/Set P112 0 to 65535...